Ceiling Concealed Chilled Water Fan Coil Unit (50Hz)

Technical Manual

MCW - C/F/H - 2009

(50Hz)

Models: MCW200?MCW300?MCW400 MCW600?MCW800?MCW1000 MCW1200Air?Flow:?

112~2040m3/h

Literature No.: TM-MCW(C/H/F)-0901A

?Supersedes: TM-MCW(C/H/F)-0708A?

Part No.: M08039110020 Contents

Nomenclature (2)

Features (3)

Electric Heater Power (3)

Specifications (4)

Sound Data (8)

Performance Data-Cooling (9)

Performance Data-Heating (18)

Air Flow vs ESP Curve (21)

Operating Limits (22)

Water Flow Rate vs Pressure Drop Chart (23)

Outlines and Dimensions (25)

Electrical Data (27)

Wiring Diagrams (28)

Installation (30)

Exploded View & Part List (32)

Guide Specifications (35)

Note:?Installation and maintenance are to be performed only by qualified personnel who are familiar?with?local?codes?and?regulations,?and?experienced?with?this?type?of?equipment.

Caution: Sharp?edges?and?coil?surfaces?are?a?potential?injury?hazard.?Avoid?contact?with?them.

Warning:?Moving?machinery?and?electrical?power?hazard.?May?cause?severe?personal

injury?or?death.?Disconnect?and?lock?off?power?before?servicing?equipment.

“McQuay”?is?a?registered?trademark?of?McQuay?International.?All?rights?reserved?throughout?the?world.

??2009?McQuay?International

“Bulletin?illustrations?cover?the?general?appearance?of?McQuay?International?products?at?the?time?of?publication

and?we?reserve?the?right?to?make?changes?in?design?and?construction?at?any?time?without?notice.”

Nomenclature

Description?of?Products

A-Standard?Drain?Pan

F1-Drain?Pan?Extended?100mm

F2-Drain?Pan?Extended?200mm

Material?of?Drain?Pan

A-Standard?Material

S-Stainless?Steel

Power?Supply

A-220V/1Ph/50Hz

F-With?Filter

X-Without?Filter

B-Back?Return?Air?Plenum?

D-Bottom?Return?Air?Plenum

X-Back return air plenum & bottom draw filter

C-Without?return?air?plenum

Pipe?Connection

R-Facing?Air?Flow?Right?Hand

L-Facing?Air?Flow?Left?Hand

0-0Pa?External?Static?Pressure

3-30Pa?External?Static?Pressure

6-60Pa?External?Static?Pressure

8-80Pa?External?Static?Pressure

"-"-Original?Design

"A"-First?Design?Improve

Electric?Heater?Power

10-10x100?W

With?Electric?Heater

C-3?Rows?and?2?Pipes(3+0)

H-4?Rows?and?4?Pipes(3+1)

F-4?Rows?and?2?Pipes(4+0)

Nominal?Air?Flow?(CFM)

(CFM,1CFM=1.7m3/h)

McQuay?Ceiling?Concealed?Chilled?Water?FCU

Features

Extra Low Noise Design

Enlarged fan wheels design allows lower fan RPM selection for the same external static pressure and airflow requirement. Thereby, noise level is significantly reduced.

Flexibility

Water?connection?side?can be changed easily in the field by changing positions of fan-motor assembly or the supply air flange assembly. Fan-motor assembly is not cased allowing back return or bottom return installations.

High Efficiency Heat Exchanger

A boundary layer film of air adhering to the fin surface will insulate the fin surface and severally reduces the heat exchange efficiency. Mcquay slit fin design eliminates this boundary layer of air and creates continuous for best heat exchange efficiency.

Variable External Static Pressure

Four?types?of?external?static?pressure?are?available?for?every?unit:0PA,?30Pa,,60Pa,80Pa.

Compact Design

This?series?of?fan?coil?units?are?designed?to?suit?most?ceiling?concealed?installations.?Unit?height?is?only?251mm?across?the?entire?model?range.?The?feature?also?maximizes?provisions?for?drain?fall?requirements. New design realizes all the filters removal both fr om?the?side?and?bottom(Option).

Auxiliary Electric Heater (Only For Type C)

The heating source of Mcquay fan coil unit is PTC (Positive Temperature Coefficient) heater.

1. Safety

A?fuse?(135°C,10A)?is?connected?in?each?PTC?main?wiring?circuit.?A?thermostat?(50°C,10A)?is?connected?in?the?control?wiring?circuit.?If?the?fan?of?the?units?is?not?running,?the?thermostat?or?fuse?will?cut?off?the?power?of?the?unit.?In?addition?the?surface?of?the?PTC?heater?is?without?electric?power.?So?the?fan?coil?unit?is?safe?enough.

2. Save Energy

Quick?heating?spread,?strong?heating?capacity,?steady?performance?and?save?energy?are?characters?of?PTC?heater.

3. Easy To Install And Maintain

Needn’t?remove?the?air?duct?when?maintain?the?electric?components?of?the?units.?Please?refer?to?the?corresponding?sections?for?installation?and?maintenance.

Electric Heater Power

Unit Size Power Supply kW kW kW kW kW kW kW kW kW kW kW kW kW MCW200CD 220-240V/1Ph/50Hz 1.0 1.5 2.0 2.5?---------MCW300CD 220-240V/1Ph/50Hz 1.0 1.5 2.0 2.5 3.0 3.5?------MCW400CD 220-240V/1Ph/50Hz 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5?-----MCW600CD 380-415V/3Ph/50Hz?-- 2.0 2.5 3.0 3.5 4.0 4.5?-----MCW800CD 380-415V/3Ph/50Hz?-- 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5?---MCW1000CD 380-415V/3Ph/50Hz?-- 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5?---MCW1200CD 380-415V/3Ph/50Hz?---- 3.0 3.5 4.0 4.5 5.0 5.5 6.0?7.0?8.0?

Specifications

General Data

MCW-C

NoteS:

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL THE UNITS ARE BEING TESTED UNDER FOLLOWING CONTITION: a) COOLING: 27°C DB/19.5°C WB INDOOR AND WATER INLET 7°C OUTLET 12°C b) HEATING: 21°C DB INDOOR AND WATER 60°C INLET.WATER FLOW:SAME WITH COOLING CONDITION.

MODEL

MCW200MCW300MCW400MCW600MCW800MCW1000MCW1200Air Flow

HIGH

m 3/h 3905307601040142016202040CFM 2293124476128359531200MEDIUM m 3/h 260370490780109011401500CFM 153218288459641671882LOW

m 3/h 1902403405007408301020CFM 112

141

200

294435

488

600

EXTERNAL STATIC PRESSURE Pa 0,30,60,80in.wg 0,0.12,0.24,0.32

TOTAL COOLING CAPACITY

W 22003200439061607810883010700Btu/h 7507109191497921019266493012936510SENSIBLE COOLING CAPACITY W 1738235932424401604064097763Btu/h 593080491106215017206092186826488TOTAL HEATING CAPACITY

W 3500510073009960130801478019170Btu/h 11942174022490933985446315043165411WATER FLOW RATE m 3/h 0.40.60.8 1.1 1.4 1.6 1.9USGPM 1.8 2.5 3.4 4.8 6.1 6.98.5HEAD LOSS (COOLING)

kPa 14.612.021.638.218.421.032.7in.wg.58.448.086.4152.873.684.0130.8DIMENSIONS

UNIT DIMEN-SIONS HEIGHT mm 251251251251251251251WIDTH mm 71488410141214146415641824DEPTH mm 556556556556556556556PACKING DIMEN-SION

HEIGHT mm 260260260260260260260WIDTH mm 72489410241224147415741834DEPTH

mm 570570570570570570570UNIT WEIGHT (Without plenum) kg 19.020.026.030.041.044.046.0lb 41.944.157.366.190.497.0101.4UNIT GROSS WEIGHT (Without plenum) kg 21.724.829.533.644.047.851.2lb 47.854.765.074.197.0105.4112.9UNIT WEIGHT (With plenum) kg 20.024.028.033.044.047.050.0lb 44.152.961.772.897.0103.6110.2UNIT GROSS WEIGHT (With plenum)

kg 22.728.831.536.647.050.855.2lb

50.0

63.5

69.4

80.7103.6

112.0

121.7

CONDENSATE DRAIN PIPE SIZE

R3/4

NoteS:

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL THE UNITS ARE BEING TESTED UNDER FOLLOWING CONTITION: a) COOLING: 27°C DB/19.5°C WB INDOOR AND WATER INLET 7°C OUTLET 12°C b) HEATING: 21°C DB INDOOR AND WATER 60°C INLET.WATER FLOW:SAME WITH COOLING CONDITION.

MODEL

MCW200 MCW300 MCW400 MCW600 MCW800MCW1000MCW1200 Air Flow

HIGH

m 3/h 3605107501010138015702000CFM 2123004415948129241176MEDIUM m 3/h 25035047077010701101470CFM 147206276453629653865LOW

m 3/h 1802303304907208201010CFM 106

135

194

288424

482

594

EXTERNAL STATIC PRESSURE

Pa 0,30,60,80in.wg 0,0.12,0.24,0.32

TOTAL COOLING CAPACITY W 21303100426059807580857010380Btu/h 7268105781453620405258642924235418SENSIBLE COOLING CAPACITY

W 1683228531464272586262207531Btu/h 574277981073514578200022122425696TOTAL HEATING CAPACITY (1 ROW) W 1350228032104290512069408490Btu/h 460677801095314638174702368028969WATER FLOW RATE (3 ROWS)

m 3/h 0.40.60.8 1.1 1.4 1.6 1.9USGPM 1.8 2.5 3.4 4.8 6.1 6.98.5WATER FLOW RATE (1 ROW)

m 3/h 0.20.20.20.20.20.50.5USGPM 1.1 1.1 1.1 1.1 1.1 2.2 2.2HEAD LOSS (COOLING) (3 ROWS)

KPa 12.021.638.218.421.032.712.0in.wg.58.448.086.4152.873.684.0130.8DIMENSIONS

UNIT DIMEN-SIONS

HEIGHT mm 251251251251251251251WIDTH mm 71488410141214146415641824DEPTH

mm 556556556556556556556PACKING DIMEN-SION

HEIGHT

mm 260260260260260260260WIDTH

mm 72489410241224147415741834DEPTH

mm 570570570570570570570HEAD LOSS (HEATING) (1 ROW)

KPa 12.013.514.820.7 4.012.814.6in.wg.48545983165159UNIT WEIGHT (Without plenum) kg 20.024.028.032.044.047.049.0lb 44.152.961.770.597.0103.6108.0UNIT GROSS WEIGHT (Without plenum)

kg 22.726.831.535.647.050.854.2lb 50.059.169.478.5103.6112.0119.5UNIT WEIGHT (With plenum) kg 22.027.031.036.048.052.056.0lb 48.559.568.379.4105.8114.6123.5UNIT GROSS WEIGHT (With plenum)

kg 24.729.834.539.651.055.861.2lb

54.5

65.7

76.1

87.3112.4

123.0

134.9

CONDENSATE DRAIN PIPE SIZE

R3/4

NoteS:

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL THE UNITS ARE BEING TESTED UNDER FOLLOWING CONTITION: a) COOLING: 27°C DB/19.5°C WB INDOOR AND WATER INLET 7°C OUTLET 12°C b) HEATING: 21°C DB INDOOR AND WATER 60°C INLET.WATER FLOW:SAME WITH COOLING CONDITION.

MODEL

MCW200MCW300MCW400MCW600MCW800MCW1000MCW1200Air Flow

HIGH

m 3/h 3605107501010138015702000CFM 2123004415948129241176MEDIUM m 3/h 25035047077010701101470CFM 147206276453629653865LOW

m 3/h 1802303304907208201010CFM 106

135

194

288424

482

594

EXTERNAL STATIC PRESSURE kPa 0,30,60,80in.wg 0,0.12,0.24,0.32

TOTAL COOLING CAPACITY

W 262234185277718586911026112791Btu/h 8948116611800724517296533501343644SENSIBLE COOLING CAPACITY W 1783240635365047636572979382Btu/h 608582101206617222217192489932011TOTAL HEATING CAPACITY

W 41965468844411496139051641820465Btu/h 14317186582881139227474455602069830WATER FLOW RATE m 3/h 0.50.60.9 1.3 1.5 1.8 2.3USGPM 2.0 2.7 4.1 5.5 6.88.010.1HEAD LOSS (COOLING)

kPa 1.3 6.0 1.327.08.812.020.0in.wg. 5.224.1 5.2108.335.348.180.2DIMENSIONS

UNIT

D I M

E N - SIONS HEIGHT mm 251251251251251251251WIDTH mm 71488410141214146415641824DEPTH mm 556556556556556556556PACKING DIMEN-ENSION

HEIGHT mm 260260260260260260260WIDTH mm 72489410241224147415741834DEPTH

mm 570570570570570570570UNIT WEIGHT (Without plenum) kg 20.024.028.032.044.047.049.0lb 44.152.961.770.597.0103.6108.0UNIT GROSS WEIGHT (Without plenum) kg 22.726.831.535.647.050.854.2lb 50.059.169.478.5103.6112.0119.5UNIT WEIGHT (With plenum) kg 22.027.031.036.048.052.056.0lb 48.559.568.379.4105.8114.6123.5UNIT GROSS WEIGHT (With plenum)

kg 24.729.834.539.651.055.861.2lb

54.5

65.7

76.1

87.3112.4

123.0

134.9

CONDENSATE DRAIN PIPE SIZE

R3/4?

Components Data

MCW-C/H/F

MCW200MCW300MCW400MCW600MCW800MCW1000MCW1200

FAN TYPE CENTRIFUGAL?(BLADE:?FORWARD)

QUANTITY1234 MATERIAL GALVANIZED?STEEL

DRIVE DIRECT?DRIVE

DIAMETER

mm160

in 6.25

LENGTH

mm200

in7.875

MOTOR TYPE SINGLE?PHASE?CAPACITOR?RUNNING QUANTITY12 IP/INSULATION GRADE IP20/E

COIL TUBE

MATERIAL COPPER

DIAMETER

mm9.52

in3/8

THICK-

NESS

mm0.30

in0.012

FIN

MATERIAL HYDROPHILIC?ALUMINUM

THICK-

NESS

mm0.11

in0.0043

FACE

AREA

m20.090.130.150.190.240.260.32

ft20.98 1.35 1.64 2.07 2.62 2.84 3.41 ROW

C3

H/F4

FIN?PER?INCH11

AIR FILTER (Option)TYPE NYLON/ALUMINIUM?FRAME

SIZE

LENGTH

mm462632762962121213111572

in18.1924.8830.0037.8747.7251.6161.89 WIDTH

mm205

in8.07

THICK-

NESS

mm8

in0.31

NoteS:

ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

NoteS:

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) SOUND PRESSURE LEVELS ARE TESTED IN SEMI-ANECHOIC ROOM,WITH BACKGROUND LEVEL: 11.5dB(A),

MICROPHONE POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.

MCW-C/H/F

Sound Data

ESP 0Pa

30Pa

Unit Speed 1/1 Octave Sound pressure level

(dBA, ref 20μPa)Total dB (A)1/1 Octave Sound pressure level

(dBA, ref 20μPa)Total dB (A)631252505001k 2k 4k 8k 631252505001k 2k 4k 8k 200 High 151923282823141333151924282924151333Medium

141819242419141329121722262623151331Low 131417201814131325151818202015121326300 High 162126323430191437162126323430191437Medium

151923282823141333121722262623151331Low 151519232318111128141819242419141329400 High 142025313228161436162128333431201338Medium

121722262623151331132026293127181435Low

151818202015121326151924282924151333600 High 152530353733251841162832363937302143Medium

142428333532221639142428333532221639Low 151923282823141333141823272823151332800 High 142329343732211540152530353733251841Medium

162128333431201338162128333431201338Low 1418232728231513321519242829241513331000 High 152530353733251841162832363937302143Medium

162128333431201338162126323430191437Low 1519232828231413331420232830271613341200High 162832363937302143172832374138282144Medium

142329343732211540142428333532221639Low

13

20

26

29

3127

18

14

35

15

19

24

28

2924

15

13

33

ESP 60Pa

80Pa

Unit Speed 1/1 Octave Sound pressure level

(dBA, ref 20μPa)Total dB(A)1/1 Octave Sound pressure level

(dBA, ref 20μPa)Total dB(A)631252505001k 2k 4k 8k 631252505001k 2k 4k 8k 200 High 162126323430191437162128333431201338Medium

142023283027161334132026293127181435Low 121722262623151331141823272823151332300 High 162128333431201338142428333532221639Medium

132026293127181435142025313228161436Low 121722262623151331141823272823151332400 High 152530353733251841163034384238292245Medium

142025313228161436152530353733251841Low 151923282823141333132026293127181435600 High 193636414340302647193540434643343150Medium

172832374138282144183435404239312046Low 162128333431201338182631363835271642800 High 193636414340302647183439424543343049Medium

172832374138282144193636414340302647Low 1424283335322216391728323741382821441000 High 183439424543343049183439424543343049Medium

183435404239312046183238404442362948Low 1423293437322115401630343842382922451200High 183439424543343049183439424543343049Medium

163034384238292245183238404442362948Low

18263136

38

35

27

16

42

16

30

34

38

42

38

29

22

45

MCW-C

Performance Data-Cooling

MODEL WATER

FLOW

(m3/h)

W.P.D

(kPa)

ENTERING AIR: DB27oC, WB19.5oC

ENTERING WATER TEMPERATUREoC

678910 TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE

W W W W W W W W W W

MCW2000.24 5.61940142018201400172013701590131014001260 0.339.72190160020801560194015501800152016601480 0.4214.82370174022101700208016601940164017901610 0.5121.62500183022701800219017502030170018801680

MCW3000.36 4.02910215027302100251020502300202022501990 0.489.23230238030202330282023002600227025202220 0.613.23480255032402490302024502780241026802390 0.7218.73660270034202630317026002920255028202490

MCW4000.427.33650266034102600320025502950251025702460 0.613.84190297039403040369030103410299031302930 0.7821.64580336043903320398032803710324034103200 0.9631.04850351045303490423034503900341035903380

MCW6000.7218.75850426054804220510041804670411042703970

0.932.76310441058904360546042605070420046504110

1.0838.26670466061604460578044005330436049004350 1.2650.06970483064904780603047005560468050904600

MCW8001.1412.57780572073005630674055706060545055305320 1.4418.78410588079005800737057506820570062205680

1.7426.28920632083406250775062007200612066205980

2.0434.59320652087106460810064107500637069106220

MCW10001.213.68610571080406190741063006820614062806030 1.520.19280655087106440808064107460634067806240

1.826.59850689091906780852067207900671072306690

2.13

3.710300721096107080892070108210697075506940

MCW12001.5621.5107107490100107400928073608490727077407190

1.923

2.7114808470107008240997081409170807083807710

2.2840.71211087101129086501046085809610846088208120 2.6454.312600895011750881010890871010020862091408410

NoteS:

1) THE COOLING CAPACITY IS TESTED UNDER HIGH SPEED.THE CAPACITY UNDER MEDIUM AND LOW FAN SPEED MUST

MULTIPLY A CORRECTION FACTOR.

2) W.P.D:WATER PRESSURE DROP

totAL: TOTAL COOLING CAPACITY SENSIBLE:SENSIBLE COOLING CAPACITY

Cooling Capacity Correction Factors:

MODEL MCW200C MCW300C MCW400C MCW600C MCW800C MCW1000C MCW1200C

MEDIUM TOTAL 0.850.820.840.840.870.850.86 SENSIBLE 0.780.750.780.800.800.800.80

LOW TOTAL 0.660.600.650.650.680.700.71 SENSIBLE 0.580.550.580.600.620.630.66

NoteS:

1) THE COOLING CAPACITY IS TESTED UNDER HIGH SPEED.THE CAPACITY UNDER MEDIUM AND LOW FAN SPEED MUST

MULTIPLY A CORRECTION FACTOR.

2) W.P.D:WATER PRESSURE DROP

totAL: TOTAL COOLING CAPACITY SENSIBLE:SENSIBLE COOLING CAPACITY

Cooling Capacity Correction Factors:

MODEL MCW200C MCW300C MCW400C MCW600C MCW800C MCW1000C MCW1200C

MEDIUM TOTAL 0.850.820.840.840.870.850.86 SENSIBLE 0.780.750.780.800.800.800.80

LOW TOTAL 0.660.600.650.650.680.700.71 SENSIBLE 0.580.550.580.600.620.630.66

MODEL WATER

FLOW

(m3/h)

W.P.D

(kPa)

ENTERING AIR: DB28oC, WB21oC

ENTERING WATER TEMPERATUREoC

6789

TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE

W W W W W W W W

MCW2000.24 5.621601580202015601910152017701460 0.339.724301780231017302160172020001690 0.4214.826301930246018902310184021601820 0.5121.627802030274020002430194022601890

MCW3000.36432302390303023302790228025602240 0.489.235902640336025903130256028902520 0.613.238702830360027703360272030902680 0.7218.740703000380029203520289032402830

MCW4000.427.340602960379028903560283032802790 0.613.846603300438033804100334037903320 0.7821.650903730488036904420364041203600 0.963153903900503038804700383043303790

MCW6000.7218.765004730609046905670464051904570

0.932.770104900654048406070473056304670

1.0838.274105180684049606420489059204840 1.265077405370721053106700522061805200

MCW8001.1412.586406360811062607490619067306060 1.4418.793406530878064408190639075806330

1.7426.299107020927069408610689080006800

2.0434.5103607240968071809000712083307080

MCW10001.213.695706340893068808230700075806820 1.520.1103107280968071608980712082907040

1.826.51094076601021075309470747087807460

2.13

3.71144080101068078709910779091207740

MCW12001.5621.51190083201120822010310818094308080

1.923

2.7127609410118909160110809040101908970

2.2840.7134609680125409610116209530106809400 2.6454.314000994013060979012100968011309580

MODEL WATER

FLOW

(m3/h)

W.P.D

(kPa)

ENTERING AIR: DB25oC, WB18oC

ENTERING WATER TEMPERATUREoC

678910 TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE

W W W W W W W W W W

MCW2000.24 5.61750128016401260155012301430118012601130 0.339.71970144018701400175014001620137014901330 0.4214.82130157019901530187014901750148016101450 0.5121.62250165022201620197015801830153016901510

MCW3000.3642620194024601890226018502070182020301790 0.489.22910214027202100254020702340204022702000 0.613.23130230029202240272022102500217024102150 0.7218.73290243030802370285023402630230025402240

MCW4000.427.33290239030702340288023002660226023102210 0.613.83770267035502740332027103070269028202640 0.7821.64120302039502990358029503340292030702880 0.96314370316040803140381031103510307032303040

MCW6000.7218.75270383049303800459037604200370038403570

0.932.75680397053003920491038304560378041903700

1.0838.26000419055404010520039604800392044103920 1.26506270435058404300543042305000421045804140

MCW8001.1412.57000515065705070607050105450491049804790 1.4418.77570529071105220663051806140513056005110

1.7426.28030569075105630698055806480551059605380

2.0434.58390587078405810729057706750573062205600

MCW10001.213.67750514072405570667056706140553056505430 1.520.18350590078405800727057706710571061005620

1.826.58870620082706100767060507110604065106020

2.13

3.79270649086506370803063107390627068006250

MCW12001.5621.59640674090106660835066207640654069706470

1.923

2.710330762096307420897073308250726075406940

2.2840.7109007840101607790941077208650761079407310 2.6454.3113408060105807930980078409020776082307570

NoteS:

1) THE COOLING CAPACITY IS TESTED UNDER HIGH SPEED.THE CAPACITY UNDER MEDIUM AND LOW FAN SPEED MUST

MULTIPLY A CORRECTION FACTOR.

2) W.P.D:WATER PRESSURE DROP

totAL: TOTAL COOLING CAPACITY SENSIBLE:SENSIBLE COOLING CAPACITY

Cooling Capacity Correction Factors:

MODEL MCW200C MCW300C MCW400C MCW600C MCW800C MCW1000C MCW1200C

MEDIUM TOTAL 0.850.820.840.840.870.850.86 SENSIBLE 0.780.750.780.800.800.800.80

LOW TOTAL 0.660.600.650.650.680.700.71 SENSIBLE 0.580.550.580.600.620.630.66

MCW-H

MODEL WATER

FLOW

(m3/h)

W.P.D

(kPa)

ENTERING AIR: DB27oC, WB19.5oC

ENTERING WATER TEMPERATUREoC

678910 TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE

W W W W W W W W W W

MCW2000.24 5.61882137717651358166813291542127113581222 0.339.72124155220181513188215041746147416101436 0.4214.82299168821441649201816101882159117361562 0.5121.62425177522021746212416981969164918241630

MCW3000.3642823208626482037243519892231195921831930 0.489.23133230929292260273522312522220224442153 0.613.23376247431432415292923772697233826002318 0.7218.73550261933172551307525222832247427352415

MCW4000.427.33541258033082522310424742862243524932386 0.613.84064288138222949357929203308290030362842 0.7821.64443325942583220386131823599314333083104 0.96314705340543943385410333473783330834823279

MCW6000.7218.75675413253164093494740554530398741423851

0.932.76121427857134229529641324918407445113987

1.0838.26470452059754326560742685170422947534220 1.26506761468562954637584945595393454049374462

MCW8001.1412.57547554870815461653854035878528753645160 1.4418.78158570476635626714955786615552960335510

1.7426.28652613080906063751860146984593664215801

2.0434.59040632484496266785762187275617967036033

MCW10001.213.6835255397799600471886116615595660925849 1.520.19002635484496247783862187236615065776053

1.826.59555668389146577826465187663650970136489

2.13

3.79991699493226868865268007964676173246732

MCW12001.5621.510389726597107178900271398235705275086974

1.923

2.711368216103797993967178968895782881297479

2.2840.71174784491095183911014683239322820685557876 2.6454.31222286821139885461056384499719836188668158

NoteS:

1) TTHE COOLING CAPACITY IS TESTED UNDER HIGH SPEED.THE CAPACITY UNDER MEDIUM AND LOW FAN SPEED MUST

MULTIPLY A CORRECTION FACTOR.

2) W.P.D:WATER PRESSURE DROP

totAL: TOTAL COOLING CAPACITY SENSIBLE:SENSIBLE COOLING CAPACITY

Cooling Capacity Correction Factors:

MODEL MCW200H MCW300H MCW400H MCW600H MCW800H MCW1000H MCW1200H

MEDIUM TOTAL 0.850.820.840.840.870.850.86 SENSIBLE 0.780.750.780.800.800.800.80

LOW TOTAL 0.660.600.650.650.680.700.71 SENSIBLE 0.580.550.580.600.620.630.66

MODEL WATER

FLOW

(m3/h)

W.P.D

(kPa)

ENTERING AIR: DB28oC, WB21oC

ENTERING WATER TEMPERATUREoC

678910 TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE

W W W W W W W W W W

MCW2000.24 5.62095153319591513185314741717141615131358 0.339.72357172722411678209516681940163917851591 0.4214.82551187223861833224117852095176519301736 0.5121.62697196926581940235718822192183320271814

MCW3000.3643133231829392260270622122483217324252144 0.489.23482256132592512303624832803244427162396 0.613.23754274534922687325926382997260028912580 0.7218.73948291036862832341428033143274530362687

MCW4000.427.33938287136762803345327453182270627742648 0.613.84520320142493279397732403676322033763162 0.7821.64937361847343579428735313996349236763453 0.96315228378348793764455937154200367638703647

MCW6000.7218.76305458859074549550045015034443345984278

0.932.76800475363444695588845885461453050154433

1.0838.27188502566354811622747435742469552774685 1.26507508520969945151649950635995504454904957

MCW8001.1412.58381616978676072726560046528587859565733 1.4418.79060633485176247794461987353614067036121

1.7426.29613680989926732835266837760659671396441

2.0434.510049702393906965873069068080686874506703

MCW10001.213.69283615086626674798367907353661567716499 1.520.110001706293906945871169068041682973046722

1.826.510612743099047304918672468517723677897207

2.13

3.7110977770103607634961375568846750881387479

MCW12001.5621.51154380701078679731000179359147783883427750

1.923

2.71237791281153388851074887699884870190318313

2.2840.713056939012164932211271924410360911895068749 2.6454.313580964212668949611737939010796929398559060

NoteS:

1) TTHE COOLING CAPACITY IS TESTED UNDER HIGH SPEED.THE CAPACITY UNDER MEDIUM AND LOW FAN SPEED

MUST MULTIPLY A CORRECTION FACTOR.

2) W.P.D:WATER PRESSURE DROP

totAL: TOTAL COOLING CAPACITY SENSIBLE:SENSIBLE COOLING CAPACITY

Cooling Capacity Correction Factors:

MODEL MCW200H MCW300H MCW400H MCW600H MCW800H MCW1000H MCW1200H

MEDIUM TOTAL 0.850.820.840.840.870.850.86 SENSIBLE 0.780.750.780.800.800.800.80

LOW TOTAL 0.660.600.650.650.680.700.71 SENSIBLE 0.580.550.580.600.620.630.66

MODEL WATER

FLOW

(m3/h)

W.P.D

(kPa)

ENTERING AIR: DB25oC, WB18oC

ENTERING WATER TEMPERATUREoC

678910 TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE

W W W W W W W W W W

MCW2000.24 5.61698124215911222150411931387114512221096 0.339.71911139718141358169813581571132914451290 0.4214.82066152319301484181414451698143615621407 0.5121.62183160121531571191115331775148416391465

MCW3000.3642541188223861833219217952008176519691736 0.489.22823207626382037246420082270197922021940 0.613.23036223128322173263821442425210523382086 0.7218.73191235729882299276522702551223124642173

MCW4000.427.33191231829782270279422312580219222412144 0.613.83657259034442658322026292978260927352561 0.7821.63996292938322900347328623240283229782794 0.96314239306539583046369630173405297831332949

MCW6000.7218.75112371547823686445236474074358937253463

0.932.75510385151413802476337154423366740643589

1.0838.25820406453743890504438414656380242783802 1.26506082422056654171526741034850408444434016

MCW8001.1412.56790499663734918588848605287476348314646 1.4418.77343513168975063643150255956497654324957

1.7426.27789551972855461677154136286534557815219

2.0434.58138569476055636707155976548555860335432

MCW10001.213.67518498670235403647055005956536454815267 1.520.18100572376055626705255976509553959175451

1.826.58604601480225917744058696897585963155839

2.13

3.78992629583916179778961217168608265966063

MCW12001.5621.59351653887406460810064217411634467616276

1.923

2.710020739193417197870171108003704273146732

2.2840.710573760598557556912874888391738277027091 2.6454.3110007818102637692950676058749752779837343

NoteS:

1) TTHE COOLING CAPACITY IS TESTED UNDER HIGH SPEED.THE CAPACITY UNDER MEDIUM AND LOW FAN SPEED

MUST MULTIPLY A CORRECTION FACTOR.

2) W.P.D:WATER PRESSURE DROP

totAL: TOTAL COOLING CAPACITY SENSIBLE:SENSIBLE COOLING CAPACITY

Cooling Capacity Correction Factors:

MODEL MCW200H MCW300H MCW400H MCW600H MCW800H MCW1000H MCW1200H

MEDIUM TOTAL 0.850.820.840.840.870.850.86 SENSIBLE 0.780.750.780.800.800.800.80

LOW TOTAL 0.660.600.650.650.680.700.71 SENSIBLE 0.580.550.580.600.620.630.66

MCW-F

MODEL WATER

FLOW

(m3/h)

W.P.D

(kPa)

ENTERING AIR: DB27oC, WB19.5oC

ENTERING WATER TEMPERATUREoC

678910 TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE

W W W W W W W W W W

MCW2000.240.512134156220001500190014001800140015401300 0.330.962400170022001600210015841900159618001495 0.42 1.562600184924001700220016962100172219001626 0.51 2.292700194425001800240017882200178520001697

MCW3000.36 2.193201236530002250277320952604215924752053 0.48 3.893540252931942390305323502744238427332242 0.6 6.083818270935192490319425043009253128452414 0.728.763953286937672630347426573165267830002515

MCW4000.42 3.084015292637472786353526063340268228272538 0.6 6.294592315641673118399430763599314033942959 0.7810.65024357047673320421033524016340236203232 0.9616.15238372949893490463635264227358138193414

MCW6000.7210.046435468660224521563442725287439246974096

0.915.696915468662304472591043535352441050424151

1.082

2.597317495166904460611344965770457852014394 1.2630.757528513271484780660848036026491454154646

MCW8001.14 5.538558629280226032744556926860582460835489 1.448.839216624883565949797858767199598567455737

1.741

2.899786671590576250819763367794642670276040

2.0417.7210066692895936460887765508128668973516282

MCW10001.2 6.449471628188356632818564387721656269086221 1.510.110170695992136605874665507874665773526302

1.814.4910806732199806780901268678552704676746757

2.119.7211247661105847080977571648898731980327009

MCW12001.5611.211178182391100079291025175219611776985147418

1.9216.981258189991131784511079283189679847490877787

2.282

3.9413285925412261865011063876810403888393628201 2.6432.113608950912941881011934890110859905197238494

NoteS:

1) THE COOLING CAPACITY IS TESTED UNDER HIGH SPEED.THE CAPACITY UNDER MEDIUM AND LOW FAN SPEED MUST

MULTIPLY A CORRECTION FACTOR.

2) W.P.D:WATER PRESSURE DROP

totAL: TOTAL COOLING CAPACITY SENSIBLE:SENSIBLE COOLING CAPACITY

Cooling Capacity Correction Factors:

MODEL MCW200F MCW300F MCW400F MCW600F MCW800F MCW1000F MCW1200F

MEDIUM TOTAL 0.850.820.840.840.870.850.86 SENSIBLE 0.780.750.780.800.800.800.80

LOW TOTAL 0.660.600.650.650.680.700.71 SENSIBLE 0.580.550.580.600.620.630.66

MODEL WATER

FLOW

(m3/h)

W.P.D

(kPa)

ENTERING AIR: DB28oC, WB21oC

ENTERING WATER TEMPERATUREoC

678910 TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE

W W W W W W W W W W

MCW2000.240.512376173822201671211015532004156017161444 0.330.96266318912443177423381758211177519951656 0.42 1.562885205126711890244318802338191121121808 0.51 2.293002215730182000266319822449198522231889

MCW3000.36 2.193553262933302496308223302898239427502280 0.48 3.893934280535542656338826163051264630362495 0.6 6.084246300739102770355427803345281431632687 0.728.764396318841852920385829533511297233302798

MCW4000.42 3.084466325641653096393328923713298231462817 0.6 6.295107350646333467443834134001348637733293 0.7810.65584396353003690467537204460378040233596 0.9616.15821414455403880515139144693398042453798

MCW6000.7210.047150520366925025626347425875488452144550

0.915.697682520669174964657148345943490456064616

1.082

2.598129550474284960679049976408508257744878 1.2630.758359570679415310734253346698546060215161

MCW8001.14 5.539504699689126707827463267619647667546098 1.448.8310236693892876605886565308001664774936373

1.741

2.89108727459100676940910770418660714078126706

2.0417.7211897693106617180986372769028743481706979

MCW10001.2 6.4410527697498137371909171538581728976786913 1.510.1112997735102387344972172768751739281656999

1.814.491200281391108875301001676349504783385237504

2.119.721235585111176278701086079619884812789267787

MCW12001.5611.2113090915212220880711389835910675863594608244

1.9216.98139849998125769395119949238107569419100958656

2.282

3.941476610285136189610122909739115619870104029110 2.6432.115120105611438397901326098921206210059108099433

NoteS:

1) THE COOLING CAPACITY IS TESTED UNDER HIGH SPEED.THE CAPACITY UNDER MEDIUM AND LOW FAN SPEED MUST

MULTIPLY A CORRECTION FACTOR.

2) W.P.D:WATER PRESSURE DROP

totAL: TOTAL COOLING CAPACITY SENSIBLE:SENSIBLE COOLING CAPACITY

Cooling Capacity Correction Factors:

MODEL MCW200F MCW300F MCW400F MCW600F MCW800F MCW1000F MCW1200F

MEDIUM TOTAL 0.850.820.840.840.870.850.86 SENSIBLE 0.780.750.780.800.800.800.80

LOW TOTAL 0.660.600.650.650.680.700.71 SENSIBLE 0.580.550.580.600.620.630.66

MODEL WATER

FLOW

(m3/h)

W.P.D

(kPa)

ENTERING AIR: DB25oC, WB18oC

ENTERING WATER TEMPERATUREoC

678910 TOTAL SEN-SIBLE TOTAL SEN-SIBLE TOTAL SEN-SIBLE TOTAL SEN-SIBLE TOTAL SEN-SIBLE

W W W W W W W W W W

MCW2000.240.511925140818021350171212571619126113861166 0.330.962159153019781436189414311710143916161343 0.42 1.562337166821611530197815231894155417091465 0.51 2.292430175324451620215916151983160717981525

MCW3000.36 2.192882213427032025249718912343194522331847 0.48 3.893189227428772154274921152470214224612020 0.6 6.083434244431712240287722582706227925582172 0.728.763553258233922370312323912850241527022262

MCW4000.42 3.083619262933742507318123503011241525412280 0.6 6.294132283737552810359427693241282530582666 0.7810.64520320942902990378730153615306632592909 0.9616.14720335844933140417531783804322434363070

MCW6000.7210.045797421354184071507038424755395442243683

0.915.696225421856064021531539144813396945433737

1.082

2.596582445260164010550040475196411646813959 1.2630.756772462264324300595143235419442148724181

MCW8001.14 5.537700566572205432670551206170524754784942 1.448.838296562175205354717752936481538760725161

1.741

2.898809604681565630738357027014578663265434

2.0417.729061623786345810798958967315601766175656

MCW10001.2 6.448525565479565968736857946951591062155602 1.510.19151626982925949787058967083599666145676

1.814.499731658889816100811361827696634269106080

2.119.7210012689695266370880064488009658472346313

MCW12001.5611.2110604741499017136922467658649698976676675

1.9216.98113218096101867610971074918708762381767009

2.282

3.94119588330110337790995378899363799184287383 2.6432.11224785641165279301074080129775814887557646

NoteS:

1) THE COOLING CAPACITY IS TESTED UNDER HIGH SPEED.THE CAPACITY UNDER MEDIUM AND LOW FAN SPEED MUST

MULTIPLY A CORRECTION FACTOR.

2) W.P.D:WATER PRESSURE DROP

totAL: TOTAL COOLING CAPACITY SENSIBLE:SENSIBLE COOLING CAPACITY

Cooling Capacity Correction Factors:

MODEL MCW200F MCW300F MCW400F MCW600F MCW800F MCW1000F MCW1200F

MEDIUM TOTAL 0.850.820.840.840.870.850.86 SENSIBLE 0.780.750.780.800.800.800.80

LOW TOTAL 0.660.600.650.650.680.700.71 SENSIBLE 0.580.550.580.600.620.630.66

Performance Data-Heating MCW-C

MODEL WATER

FLOW

(m3/h)

W.P.D

(kpa)

ENTERING AIR: DB21oC

ENTERING WATER TEMPERATUREoC

404550556065707580

W W W W W W W W W

MCW200 0.24 4.5156019702380279031903600402044204830 0.337.8167021102550299034303860430047405190 0.4211.8174022002650311035804030449049405410 0.5117.3179022602730319036704140461050805550

MCW300 0.36 3.2216027203300387044405010557061406700 0.487.4241030503690433049705600623068807520 0.610.6252031803850452051705830651071507810 0.7215.0259032703960463053106000667073608050

MCW400 0.42 5.8315039704810562064607290811089409770 0.611.03410440052006100700078908780968010570 0.7817.335504500543064707300824091801012011040 0.9624.836604620559065507520848094501040011370

MCW600 0.7215.04510571069008090928010460116501284014030

0.926.24710596072008440968010920121601341014640

1.0830.64850613074108690996011250125101380015070 1.2640.049606270757088701018011480127901409015400

MCW800 1.1410.0614077709400110301266014290159201755019190 1.4415.0640081209820115201322014920166201833020030

1.7421.06600835010110118601361015360171201887020620

2.0427.66740853010320121101390015690174901927021060

MCW1000 1.210.96860870010530123701421016050178801972021560 1.516.17180910011020129401486016790187102063022550

1.821.27410939011370133501533017310192902127023250

2.127.07580960011630136601568017700197302177013740

MCW1200 1.5617.285601085013150157801776020070213902467026970

1.9226.294901191014330167501917021590240202645028870

2.2832.697801228014780172701977022270247602726029750 2.644

3.4100101257015120176702022022780253302788030440

NoteS:

1) THE HEATING CAPACITY IS TESTED UNDER HIGH SPEED.THE CAPACITY UNDER MEDIUM AND LOW FAN SPEED MUST

MULTIPLY A CORRECTION FACTOR.

2) W.P.D:WATER PRESSURE DROP

Heating Capacity Correction Factors:

MODEL MCW200C MCW300C MCW400C MCW600C MCW800C MCW1000C MCW1200C MEDIUM0.800.780.780.810.830.800.81 LOW0.580.560.570.580.620.600.61

MCW-H

MODEL WATER

FLOW

(m3/h)

W.P.D

(kpa)

ENTERING AIR: DB21oC

ENTERING WATER TEMPERATUREoC

404550556065707580

W W W W W W W W W

MCW2000.12 3.24305406908309501180137018201980 0.187.353068078094011601360180019802180 0.2412.0620760920117013501780193021602460 0.3621.98009101150125017301900215024402640

MCW3000.12 3.77909801180138015801780197021702360 0.188.2100012401490174019902240249027402980 0.2413.5114014201700199022802560285031303420 0.3625.0134016601990234026603000333036603990

MCW4000.12 5.2117014301760204023402620291031903490 0.1810.0143017902860250028603210358039304280 0.2414.8161020102410279032103600403044204820 0.3629.0190023702830332037904270474052105630

MCW6000.128.2157019802380276031403570399043704770 0.1814.0189023902890335037904220480052405730 0.2420.7212027003240379042904870545059906530 0.3636.0252032003850454051805860653071207830

MCW8000.12 2.4189023502830329037704240472051805650 0.18 4.8227028403400397045405100566062406800 0.247.8257032003840448051205760640070507690 0.3611.5304038104560532060806840760083609130

MCW10000.3 5.5207026003290380043604790607064407430 0.48.8283033004240440056606350709076109290 0.512.83610409051805400694075509230962010550 0.618.5406049005290634085109370101501130012380

MCW12000.3 6.0298035404210523059706440765082709250 0.49.936504270565063507150798094141028011080 0.514.6430052006490758084909400109001190012980 0.620.048305910766087901042011200123801361014850

NoteS:

1) THE HEATING CAPACITY IS TESTED UNDER HIGH SPEED.THE CAPACITY UNDER MEDIUM AND LOW FAN SPEED MUST

MULTIPLY A CORRECTION FACTOR.

2) W.P.D:WATER PRESSURE DROP

Heating Capacity Correction Factors:

MODEL MCW200H MCW300H MCW400H MCW600H MCW800H MCW1000H MCW1200H MEDIUM0.800.780.780.810.830.800.81 LOW0.580.560.570.580.620.600.61

麦克维尔风冷热泵机组操作手册

适用于麦克维尔模块式风冷冷水/热泵机组 MAC210/MAC230D /DS/DM/DR/DRS/DR MC302l控制器使用手册 一、操作 1、开关机 按ON/OFF键,机组在开机(RUN灯亮)、关机(RUN灯灭)之间切换。 2、模式选择 按“模式”键可在制冷/制热模式之间切换,须注意的是,模式却换必须在关机状态下进行。 3、参数查询 使用本控制器能查询它所联网的任意一台机组的工作状态及参数(有哪几台压缩机在工作、进水设置温度、进水温度、出水设置温度、出水温度、机组的定时设置、制冷防冻温度、冬季防冻温度、除霜温度等)。 按“机组”键后机组号码闪烁,此时按“▲”或“▼”键改变机组号,查看到的是不同机组的当前参数,若要查询某个机组的工作参数,找到欲查询的机组号时按“确定”键即可查询该机组的工作参数了,按“▲”或“▼”键查看该机组的不同的参数。 4、参数设置 ①按“密码”键显示器左下框内显示“密码输入”和“00”,按“▲”或“▼”键改变数值,当选择到正确的用户密码后按“确定”键(出厂密码为“00”),显示框内显示时间,则表示已经输入正确的用户密码,可以进行以下设置: A、运行参数修改:在输入正确密码后,按照步骤②→③→④就能够完成运行参数的修改设置。 B、用户密码修改:在输入正确密码后,按“密码”键显示框内只显示“00”,则表示进入用户密码修改设置,按“▲”或“▼”键改变数值后,按“确定”键修改拥护密码完成,同时跳出参数设置状态。 ② 按“机组”键后机组号码闪烁,此时按“▲”或“▼”键改变机组号,找到欲设

置参数的机组号时按“确定”键即可设置该机组的工作参数了(可设置的参数有:制冷进水温度、制热进水温度)。 ③ 按“▲”或“▼”键选择要设置的参数,按“确定”键后就可以按“▲”或“▼”键设置参数值,设置完成后按“确定”键保存设置结果。 ④ 重复步骤②可设置其他参数(注意:60秒内没有按键则退出参数设置)。 ⑤ 设置参数值必须在关机状态下进行。 5、实时时钟设置 用针形工具按“模式”键上方的小孔,液晶显示器上显示“星期设置”的字样,按“▲”或“▼”键设置当前时间是星期几,设置好了之后再按小孔,星期设置成功,同时显示器上显示“时钟设置”时间会闪烁,此时按“▲”键修改小时,按“▼”键修改分钟,再按小孔即可保存设置的时钟。 6、定时设置 ①按“定时”键后显示器上同时显示“星期设置”和“定时设置”的字样,此时按“▲”或“▼”键选择要设置定时的时间在星期几,选好后按“确定”键,显示器上显示“定时设置”的字样,此时已经选定定时星期,进入定时次数设置。 ②进入定时次数设置后,按“▲”或“▼”键选择要设置当天的哪个定时(能设置4个,在“机组号”上方有指示),按“确定”键选定某个定时,进入定时开或关的选择。 ③按“▲”或“▼”键选择“定时开”和“定时关”,按“确定”键选定当前这个定时是开还是关,进入定时时间选择,此时显示器上显示“定时设置”和“时钟设置”并且时间闪烁。 ④再按“▲”键修改小时,按“▼”键,修改分钟,设置好时间后按“确定”键完成这个定时的所有设置,同时保存这个设置,此时显示器上显示“定时设置”并且跳到步骤③,其中定时次数和定期星期顺序递增,循环设置一个星期的定时,直到退出定时设置。 ⑤如果要取消某个定时,需将此定时的定时时间设置为上午00:00。如果要取消全部定时,需同时按下“模式”和“机组”键,在“滴-----”一声长鸣后,此时所有的定时全部清除。

风机盘管型号参数表

FP系列风机盘管 简述 FP系列风机盘管主要由风机、盘管、凝结水盘、控制和手动放气阀等组成,具有结构简单、节能、噪音低、耗电省及安装维护简便、操作方便等优点,是目前配合户室空调、中央空调进行室内温度及空气调节的理想产品。 本公司可提供用户多种规格及型式选择,标准工况下风量340m3/h~2380m3/h,机组余压0Pa~50Pa;型式有:普通型卧式/立式暗装、超薄型卧式/立式/明装/暗装、嵌入式、扇形吊顶式、立柜式、挂壁式等,更多了一份人性化设计,以完全满足用户对风量、冷量、风压及安装条件的要求。 特点 产品换热器系用美国TRIDAN公司的生产线制造而成,由无缝紫铜管串套高效双边翻铝片,采用机械涨管工艺,使管片结合紧密,传热性能优良,并经过特殊处理,在使用过程中,换热器的空气阻力明显减少,在风速较大时,不会产生冷凝水珠分溅,同时表面防腐蚀性能加强,采用锻黄铜结构集水头,大大延长了产品的使用寿命; 电动机采用三速低噪音专用马达,高精度封闭轴承,运行过程中无需加油维护,运转平稳可靠,使用寿命长达35000小时,电机引出线用金属软管保护,以免损伤; 采用广角蜗壳,金属多叶离心风轮,动平衡性高; 凝结水盘整体冲压一次成型,杜绝滴漏水现象,表面喷塑防腐处理,经久耐用; 保温材料采用高密度聚氨酯,导热系数小,耐水性能高,抗老化、阻燃、无毒,能保证各地全天候使用而无凝露现象发生。 吊装孔配有橡胶减震垫,最大限度降低机组噪音。 FP系列风机盘管性能参数表

注:低静压机组的额定风量是机外余压为0Pa时的值,在不带风口和过滤器的余压值为12Pa。 供冷工况参数:进口空气干球温度27℃,湿球温度19.5℃,进水温度7℃,水温差5℃。 供热工况参数:进口空气干球温度21℃,进水温度60℃,热水流量同供冷工况。 上述表格中性能参数如有更改,恕不另行通知。 FP系列暗装风机盘管外型及安装尺寸 (请在订货时注明出风及回风形式) FP系列立式暗装风机盘管外型及安装尺寸 FP系列暗装风机盘管风管安装示意图 CFP系列超薄型风机盘管特点 超薄型豪华风机盘管系吸取国外同类产品之精华,并采纳空调专家和工程安装技术人员的宝贵意见,精心研制而成,具有: 机体厚度薄(明装仅188mm),占地面积小,就位安装方便,可任意调节安装高度; 超静音设计,采用精心研制的铝合金贯流风叶,同时采用优质吸音保温材料,使噪音降到最低; 采用优质注塑面板,整体外形设计美观流畅; 可内置双盛水盘,立式、卧式任意选择安装; 产品包装采用专用模具制成塑料泡沫内衬,确保机组在运输中不被损坏。 CFP系列超薄型风机盘管性能参数表

政府机关办公楼物业服务管理方案

政府机关办公楼物业服务管理方案 篇一:政府机关办公楼物业服务管理方案 “XXXXXX公司” 物业服务方案 XXXXXXXXXXXX公司 201 年月日 第一章第二章第三章第四章第五章第六章第七章第八章第九章第十章结束语 XX市XX办公楼物业管理方案 目录 XXXXXXXXX公司简介 XX市XXX办公楼概况及管理特点分析 XX市XXX办公楼物业管理服务思路物业管理服务承诺前期物资装备一览表物业管理服务费用测算固定岗服务方案保洁服务方案紧急事件处理规程管理用房配置方案 XXXXXXXX公司受XX市XXXX委托,拟对XXXXX办公楼(以下简称“XX办公大楼”)提供全委托物业管理服务。针对该办公楼的特点,制定本方案。 第一章 XXXXXXXXX公司简介 我们的实力 XXXXXXXXXXX公司成立于2010年3月,注册资金50万元,是具

有独立法人资格和国家叁级物业资质的专业物业管理公司。目前管理着社区高档住宅及商业物业项目 公司大力拓展物业管理业务,以物业管理为主导,保洁服务、绿化服务、维修服务、家政服务以及代租代售等为一体,形成多元化的服务体系。公司下设综合事物部、品质管理部、物业管理处、财务部。公司一方面确立“寓管理于服务之中,寓效益于服务之中”的服务指导思想。另一方面挑战物业管理服务新概念,打造“贴心业主,亲情服务”的公司品牌,即:全方位近距离、全过程专业化、一站式亲情服务。 公司为了与沿海大城市物业管理的先进理念和方式接轨,每年都要派出管理人员到上海、深圳、广州等城市的大型物业管理公司观摩、学习,掌握先进的物业管理经验。我们的理念 ? ? ? 服务宗旨:尽心、尽力、尽责,善待每位客户。质量方针:为业主创造价值,让客户持续满意。团队精神:企业的命运就是个人的命运, 企业的发展就是个人的发展。 ? 发展目标:以“生态型发展体系”为依托, 致力于打造成都物业第一品牌。 我们的目标 ? ? ? 立足基础服务,树立XXX物业诚信高效形象。强化服务意识,

风机盘管技术参数要求

风机盘管技术参数要求文件编码(008-TTIG-UTITD-GKBTT-PUUTI-WYTUI-8256)

风机盘管技术要求 1.基本技术参数及要求 盘管的耐压性能:工作压力,按国际规定的实验压力应≥倍的工作压力。 额定风量和全压:在国际规定的下,风量实测值不低于额定值的95%;全压实测值不低于额定值的93%,功率实测不超过额定值的10%。(须提供测试报告)风机盘管应有良好的凝结水处理措施,排放流畅,不应有凝结水外滴。 风机应选用耗电省、噪音低、E级绝缘,调速范围宽且满足高、中、低三档转速稳定运行的叶轮风机。风机在工厂制造完成后,经动、静平衡实验,使其振动小,不老化,不变形。电机应选用三种速度可调节的永久性电容电机,达到节电的效果。三速风机应设独立的熔断器保护,风机及阀门的控制端子应集中设置。 应提供风机盘管三速噪音指标,应满足国家有关标准或规定。 高效换热盘管应选用优质铝箔片,带有波纹型的翅片,应有高抗拉高延伸高纯度的防氧化铝箔,片型应为双条缝型桥式结构,与铜管交叉连接,钢管与铝箔应涨接紧密,确保传热效率高,充分保证盘管的性能和质量。 铜管采用TP2脱氧磷铜,采用整体机械涨管工艺涨管,盘口焊接采用气体保护焊接工艺。 风机轴承采用无油润滑滚动轴承。 投标产品应经过泄漏检测,电机绝缘检测,电机绝缘试验,启动试验,耐压试验等,并符合国家有关标准。 箱体应采用优质的镀锌板材料,水盘涂层均匀,色泽一致,无流痕气泡及剥

落。结构应体积小且薄,外型简洁。 凝结水盘应一体拉模成型,采用冷轧钢板经磷化处理后喷漆,并进行整体保温,保温材料应选用防火等级难燃B1级保温板。 表冷器能完全满足技术表所规定的技术要求。表冷器的设计为逆交叉束,冷冻水进出水管设在同侧,管内流速控制在及迎面风速控制在s以保证不飞水,风速均匀度均大于80%。表冷器进行水压试验,在下列条件时无泄漏:±,保压时间不小于3Min。 所有风机盘管须提供 25 毫米厚可清洗重用的铝制空气过滤器,过滤器的安装设计不需拆卸即可抽出清洗。 除轴承、密封圈及转动部件可能在正常寿命期间更换外,其余的材料和部件在正常情况下运行不小于10年。 机组可在环境温度不超过40℃、相对湿度不超过95%的条件下连续运行。 风机盘管外表面无明显划伤、锈斑和压痕,表面光洁。 所有提供的铭牌、指示、警告标识必须具有中文表示。铭牌内容应符合国家有关标准规定,其材料应是耐腐蚀、耐磨损的金属材料,必须牢固着于设备显着位置。 设备出厂前,中标单位应邀请不少于2人的建设单位人员到厂进行生产检验运行,这种检验和试运行不应作为最终验收,最终验收试车应在设备到达目的地后进行。所有必须的检验应在工厂完成,中标单位应提供建设单位一份检验标准和计划由需方认可。检验工作完成后,中标单位应向需方提交实验报告。 机组所有电器,电机应符合国家标准规定的安全要求。 投标厂家须提供所投设备型号真实可靠的出厂性能检测报告。

风机盘管全参数尺寸

风机盘管参数尺寸 技术参数表 型号项目FP-34 FP-51 FP-68 FP-85 FP-102 FP-136 FP-170 FP-204 FP-238 02# 03# 04# 05# 06# 08# 10# 12# 14# 风量m3/h 高340 510 680 850 1020 1360 1700 2040 2380 中255 383 510 638 765 1020 1275 1530 1785 低170 255 340 425 510 680 850 1020 1190 制冷量 W 高1800 2700 3600 4500 5400 7200 9000 10800 12600 中1620 2440 3290 4120 4850 6550 8190 9730 11580 低1310 2010 2650 3320 3900 5300 6610 7860 9350 制热量 w 高2700 4050 5400 6750 8100 10800 13500 16200 18900 中2350 3520 4530 6040 6850 9260 11740 14140 16360 低1620 2470 3130 4170 4740 6500 8180 9710 11290

型号 A B C FP-34 890 620 490 FP-51 990 720 590 FP-68 1090 820 690 FP-85 1190 920 790 FP-102 1320 1050 920 FP-136 **** **** 1240 FP-170 1840 1470 1440 FP-204 2050 1780 1650 FP-238 2150 1880 1750

分享约克风机盘管型号

汕头大学中央空调维护保养设备型号数量及 主要要求 整理表 姓名: 职业工种: 申请级别: 受理机构: 填报日期:

A4打印/ 修订/ 内容可编辑

汕头大学中央空调维护保养设备型号、数量及主要要求 1.大礼堂中央空调系统 空调主机:约克活塞式冷水机组 100冷吨×2台、50冷吨×1台 冷冻水泵:11KW×2台、5.5KW×1台 冷却水泵:7.5KW×2台、3.7KW×1台 冷却塔:2座 风柜机:7台 2.E座教学楼中央空调(共22台) 201阶梯教室:广东华宝风冷式冷水机组 10匹×5台 204阶梯教室:广东华宝风冷式冷水机组 10匹×5台 一楼东电脑机房:广东华宝风冷式冷水机组 10匹×2台、5匹×1台 一楼西电脑机房:广东华宝风冷式冷水机组 10匹×2台、5匹×1台 六楼多媒体电教室:广东华宝风冷式冷水机组 10匹×6台 3.体育馆中央空调系统 开利活塞式水冷柜机:60冷吨×4台 冷却水泵:7.5KW×2台 冷却塔:1座 4.电话总机室空调 乐声风冷式分体柜机:15匹×1台 五、图书馆中央空调、附属馆多联空调及排风系统 (一)、基本情况 汕头大学新图书馆建筑面积21244.73平方米,建筑高度17.05米,为三层楼钢筋混凝土框架结构。馆内为中央空调、附属馆为多联空调(设备基本都采用麦克维尔公司产品),馆内和附属馆都有排风系统。 (二)、维护保养内容 (A)维护保养内容表(1年期)

(B)管道系统化学清洗工艺及技术要求 1.化学清洗液采用专用于清洗制冷机组、中央空调水循环系统的高效安全清洗液,是含有渗透剂的酸性化学除垢剂,可溶解水垢和铁锈,可渗透溶解和分散脱离碱垢,碳酸盐和其他不溶性物质,清洗效果良好,但不损伤管壁。。 2.清洗前准备工作: 清洗前需要清除管道系统中的杂物。如水泵进水口过滤器,制冷机组进水室,分集水器底部,冷却塔集水盘等容易积集杂物、污泥的部位,在化学清洗以前必须清除干净。清除制冷机组传热管内的污物,以利于清洗液顺畅流通。对于冷却水系统(冷却水系统为开始式系统)清洗前要加杀菌灭藻剂循环,杀灭系统中的菌类藻类。 3.除垢、除锈、除油: 开启循环水泵,加入补充水使循环水泵运行半小时左右,等系统循环稳定,水泵进出口压力平稳,关闭补充水阀,从系统底部排出部分清水,从系统顶部加入高效安全清洗液,从冷水系统的补充水箱加液,冷却水系统的冷却塔集水盘加液。 4.循环清洗: 连续运行循环水泵,并观察清洗效果,检测清洗液,根据清洗效果确定循环运行时间(一般为12小时-24小时)、增加清洗液用量及添加溶解加速剂。 5.冲洗: 化学清洗完毕后用清水循环冲洗,排出脱落的污物,排除制冷机组。风机盘管,空调机组传热管表面的残留物。并调整系统管路内水的PH值到中性,为预膜做准备。 6.预膜: 加入预膜液,继续运行循环泵,运行6-8小时后浸泡8小时完毕。预膜作用是使传热铜管表面生成保护膜,减缓金属的氧化和腐蚀。 7.添加缓蚀阻垢剂: 在循环水中添加缓蚀阻垢剂能在设备表面生成一层致密的保护膜,减缓管路表面金属的腐蚀和结垢。保护膜还具有自身修补作用,一旦保护膜受损,水中的药剂马上在破损点成膜,维持保护膜的完整性。改药剂还具有除氧防腐作用。 附:系统设备清单

麦克维尔07MAC户式中央空调样本.

缔造尊享品质生 活 https://www.sodocs.net/doc/571494617.html, 全球标准化专业售后服务 麦克维尔MAC户式中央空调 PM-MAC-C003 ★印刷资料内的产品可能与实物有差别,购买时请参考实机。 ★所有资料经过仔细审核,如有任何印刷错漏,麦克维尔公司不承担因此产生的后果。 ★机型、参数、性能会因产品的改良有所改变,恕不另行通知。具体参数请以产品铭牌为准。CH1007-3000-F

百年来麦克维尔一直致力于中央空调及相关科技的研究0101010101010101010101010101010101010101010101010101010101010101010101 0010101010101010101010101010101010101001010101010101010101010101010101 0101010101010101010101010101010101010101010101010101010101010101010101 0101010010101010101010101010101010101010101001010101010101010101010101 0101010101010101010101010101010101010101010101010101010101010010101010 101010101010101010101010101001010101 统部件齐全,可一步到位,安装简单、应用成熟,无管道长短限制,无制冷剂泄漏等安全隐患。 统一采购,可享受麦克维尔优质便捷的售后服务,在总效益成本上达到最佳。出的系统能效比,与传统家用空调相比可省电30%,机组使用寿命长达15-20 年。 型式丰富,用户可根据实际装修灵活选用,尽显时尚个性。 健康节能舒适美观全面提升您的生活品质 67 89 麦克维尔MAC户式中央空调

风机盘管价格,最新全国风机盘管规格型号价格大全

全国各规格型号风机盘管 价格大全 来源:造价通工程造价信息网 概述:造价通工程造价信息网为您实时提供全国各省市地区各种规格/型号风机盘管 价格查询。 标签:风机盘管价格,风机盘管价格表,风机盘管规格,风机盘管型号,最新风机盘管 价格,风机盘管报价,风机盘管价格查询,风机盘管市场价 编者按:造价通——是中华人民共和国国家标准《建设工程人工材料设备机械数据标 准》(GB/T 50851-2013)的参编单位和唯一数据提供方。

材料名规格/型号单位品牌省份城市查询账号账号密码 风机盘管 (高静压行机外余压 50Pa)QL=12.94KW, QR=21.74(中速), N=295W 台金华利广东深圳市misschen1988 lzl639528417 风机盘管 (高静压行机外余压 51Pa)QL=11.12KW, QR=18.38(中速), N=230W 台金华利广东深圳市misschen1988 lzl639528417 风机盘管 (高静压行机外余压 52Pa)QL=9.07KW, QR=15.91(中速), N=200W 台金华利广东深圳市misschen1988 lzl639528417 风机盘管 (高静压行机外余压 53Pa)QL=7.92KW, QR=12.79(中速), N=150W 台金华利广东深圳市misschen1988 lzl639528417 风机盘管 (高静压行机外余压 54Pa)QL=5.81KW, QR=9.38(中速), N=118W 台金华利广东深圳市misschen1988 lzl639528417 风机盘管 (高静压行机外余压 55Pa)QL=4.84KW, QR=7.84(中速), N=90W 台金华利广东深圳市misschen1988 lzl639528417 风机盘管 (高静压行机外余压 56Pa)QL=4.17KW, QR=6.68(中速), N=75W 台金华利广东深圳市misschen1988 lzl639528417 风机盘管 (高静压行机外余压 57Pa)QL=3.26KW, QR=5.32(中速), N=60W 台金华利广东深圳市misschen1988 lzl639528417 风机盘管 (高静压行机外余压 58Pa)QL=2.13KW, QR=3.48(中速), N=40W 台金华利广东深圳市misschen1988 lzl639528417 风机盘管02-2H 1.形式:卧式暗装 2.型号规格:风量 270(m/h),冷量 1.78(kW),热量 3.06(kW),机外余压 30(Pa) 套四川成都市misschen1988 lzl639528417 风机盘管05-2H 1.形式:卧式暗装 2.型号规格:风量 660(m/h),冷量 4.01(kW),热量 7.03(kW),机外余压 30(Pa) 套四川成都市misschen1988 lzl639528417 风机盘管05-2S 1.形式:卧式暗装 2.型号规格:风量 套四川成都市misschen1988 lzl639528417

McQuay麦克维尔模块式风冷冷水MCl控制器使用手册

MC302l控制器使用手册 适用于麦克维尔模块式风冷冷水/热泵机组 MAC210/MAC230D /DS/DM/DR/DRS/DR 一、操作 1、开关机 按ON/OFF键,机组在开机(RUN灯亮)、关机(RUN灯灭)之间切换。 2、模式选择 按“模式”键可在制冷/制热模式之间切换,须注意的是,模式却换必须在关机状态下进行。 3、参数查询 使用本控制器能查询它所联网的任意一台机组的工作状态及参数(有哪几台压缩机在工作、进水设置温度、进水温度、出水设置温度、出水温度、机组的定时设置、制冷防冻温度、冬季防冻温度、除霜温度等)。 按“机组”键后机组号码闪烁,此时按“▲”或“▼”键改变机组号,查看到的是不同机组的当前参数,若要查询某个机组的工作参数,找到欲查询的机组号时按“确定”键即可查询该机组的工作参数了,按“▲”或“▼”键查看该机组的不同的参数。 4、参数设置 ①按“密码”键显示器左下框内显示“密码输入”和“00”,按“▲”或“▼”键改变数值,当 选择到正确的用户密码后按“确定”键(出厂密码为“00”),显示框内显示时间,则表示已经输入正确的用户密码,可以进行以下设置: A、运行参数修改:在输入正确密码后,按照步骤②→③→④就能够完成运行参数的修改设 置。 B、用户密码修改:在输入正确密码后,按“密码”键显示框内只显示“00”,则表示进入用 户密码修改设置,按“▲”或“▼”键改变数值后,按“确定”键修改拥护密码完成, 同时跳出参数设置状态。 ②按“机组”键后机组号码闪烁,此时按“▲”或“▼”键改变机组号,找到欲设置参数的机 组号时按“确定”键即可设置该机组的工作参数了(可设置的参数有:制冷进水温度、制热进水温度)。 ③按“▲”或“▼”键选择要设置的参数,按“确定”键后就可以按“▲”或“▼”键设置参 数值,设置完成后按“确定”键保存设置结果。 ④重复步骤②可设置其他参数(注意:60秒内没有按键则退出参数设置)。 ⑤设置参数值必须在关机状态下进行。 5、实时时钟设置 用针形工具按“模式”键上方的小孔,液晶显示器上显示“星期设置”的字样,按“▲”或“▼” 键设置当前时间是星期几,设置好了之后再按小孔,星期设置成功,同时显示器上显示“时钟设置”时间会闪烁,此时按“▲”键修改小时,按“▼”键修改分钟,再按小孔即可保存设置时钟。 6、定时设置 ①按“定时”键后显示器上同时显示“星期设置”和“定时设置”的字样,此时按“▲”或“▼” 键选择要设置定时的时间在星期几,选好后按“确定”键,显示器上显示“定时设置”的字样,此时已经选定定时星期,进入定时次数设置。 ②进入定时次数设置后,按“▲”或“▼”键选择要设置当天的哪个定时(能设置4个,在“机 组号”上方有指示),按“确定”键选定某个定时,进入定时开或关的选择。 ③按“▲”或“▼”键选择“定时开”和“定时关”,按“确定”键选定当前这个定时是开还是 关,进入定时时间选择,此时显示器上显示“定时设置”和“时钟设置”并且时间闪烁。 ④再按“▲”键修改小时,按“▼”键,修改分钟,设置好时间后按“确定”键完成这个定时 的所有设置,同时保存这个设置,此时显示器上显示“定时设置”并且跳到步骤③,其中定时次数和定期星期顺序递增,循环设置一个星期的定时,直到退出定时设置。

麦克维尔模块式风冷冷水热泵机组

适用于麦克维尔模块式风冷冷水/热泵机组MAC210/MAC230D /DS/DM/DR/DRS/DR MC3021控制器使用手册一、操作1、开关机按 ON/OFF键,机组在开机(RUN灯亮)、关机(RUN灯灭)之间切换。2、模式选择按模式”键可在制冷/制热模式之间切换,须注意的是,模式却换必须在关机状态下进行。3、参 数查询使用本控制器能查询它所联网的任意一台机组的工作状态及参数(有哪几台压缩机在工作、进水设置温度、进水温度、出水设置温度、出水温度、机组的定时设置、制冷防冻温度、冬季防冻温度、除霜温度等)。按机组”键后机组号码闪烁,此时按“▲或“▼键 改变机组号,查看到的是不同机组的当前参数,若要查询某个机组的工作参数,找到欲查询的机组号时按确定”键即可查询该机组的工作参数了,按“▲或“▼键查看该机组的不同 的参数。4、参数设置① 按密码”键显示器左下框内显示密码输入”和“00;'按“▲或键改变数值,当选择到正确的用户密码后按确定”键(出厂密码为“00J,显示框内显示时 间,则表示已经输入正确的用户密码,可以进行以下设置:A、运行参数修改:在输入正 确密码后,按照步骤②③r④就能够完成运行参数的修改设置。B、用户密码修改:在 输入正确密码后,按密码”键显示框内只显示“00;'则表示进入用户密码修改设置,按或“▼键改变数值后,按确定”键修改拥护密码完成,同时跳出参数设置状态。②按机 组”键后机组号码闪烁,此时按“▲或“▼键改变机组号,找到欲设置参数的机组号时按确定”键即可设置该机组的工作参数了(可设置的参数有:制冷进水温度、制热进水温度)。③ 按或“▼键选择要设置的参数,按确定”键后就可以按“▲或“▼键设置参数值,设置 完成后按确定”键保存设置结果。④ 重复步骤②可设置其他参数(注意:60秒内没有按 键则退出参数设置)。⑤设置参数值必须在关机状态下进行。5、实时时钟设置用针形 工具按模式”键上方的小孔,液晶显示器上显示星期设置”的字样,按“▲或“▼键设置当 前时间是星期几,设置好了之后再按小孔,星期设置成功,同时显示器上显示时钟设置”时间会闪烁,此时按“▲键修改小时,按“▼键修改分钟,再按小孔即可保存设置的时钟。 6、定时设置①按定时”键后显示器上同时显示星期设置”和定时设置”的字样,此时按 “▲或“▼键选择要设置定时的时间在星期几,选好后按确定”键,显示器上显示定时设置”的字样,此时已经选定定时星期,进入定时次数设置。② 进入定时次数设置后,按 或“▼键选择要设置当天的哪个定时(能设置4个,在机组号”上方有指示),按确定”键 选定某个定时,进入定时开或关的选择。③ 按或"▼键选择定时开"和定时关",按 确定”键选定当前这个定时是开还是关,进入定时时间选择,此时显示器上显示定时设置” 和时钟设置”并且时间闪烁。④ 再按“▲键修改小时,按“▼键,修改分钟,设置好时间 后按确定”键完成这个定时的所有设置,同时保存这个设置,此时显示器上显示定时设置” 并且跳到步骤③,其中定时次数和定期星期顺序递增,循环设置一个星期的定时,直到退 出定时设置。⑤如果要取消某个定时,需将此定时的定时时间设置为上午00: 00。如果 要取消全部定时,需同时按下模式”和机组”键,在滴-----”一声长鸣后,此时所有的定时

各种风机盘管型号与图片集成

·北京普莱斯特设备安装有限公司 产品 公司 求购 首 页 产品展示 产品目录 公司介绍 技术文章 公司动态 联系我们 客户留言 您现在的位置: >> 首页 站内产品搜索 产品分类 风机盘管 电机 空调箱 联系我们 公司:北京普莱斯特设备安装有限公司 给我留言 联系方式 您可能感兴趣 杭州格力空调价格 风管机价格 天花机价格

智能型商用变频空 调 杭州东芝中央空调销 售 杭州盾安空调厂家直 销 格力空调,商用变频空 调 还未提交工商注册信息 推荐产品: 新晃风机盘管-SGCR豪宅专用盘管 风机盘管标准型SCR-600 风机盘管标准型SCR-300

风机盘管标准型SCR-400 风机盘管标准型SCR-1200 公司简介: 优质推荐 Goepe AdWords 风冷模块 家用中央空调直销 杭州三菱中央空调批发商三菱中央空调杭州总代理

HYZK系列组合式工业空调 机组 北京普莱斯特设备安装有限公司,成立于2000年3月,公司是专业从事制冷中央空调设备的设计、销售、安装、维护型企业。经营以麦克维尔中央空调销售安装工程为主。多年以来始终坚持为客户提供名优品牌、优质产品之路,普莱斯特人坚信:工程质量是企业长期发展的基石。 我们先后承接昆仑饭店改造工程、可口可乐亦庄改造工程、中科院微电子所、中国石油干休所等在内的200多个项目,均得到客户一致好评。我公司施工过程中贯彻工程质量与安全生产两者兼得的宗旨,保质保量完成客户交给我们的工程,得到用户的信任,成为客户长期可信赖的中央空调服务商。 公司依赖一支具有竟争力的销售队伍,优秀的设计人员并配有丰富经验的专业安装、维修服务队伍…… 公司主营产品:销售:新晃系列产品 风机盘管 盘管电机 服务:中央空调设备的设计、安装、改造、维保等。…… 详细>> 公司动态: 尚未发布任何新闻! 技术文章: 尚未发布任何文章! 免责声明:以上所展示的信息由企业自行提供,内容的真实性、准确性和合法性由发布企业负责。Goepe 对此不承担任何保证责任。 北京普莱斯特设备安装有限公司地址:北京市海淀区志新路41号 技术支持:谷瀑环保管理员入口 | 环宝通档案

风机盘管型号参数表

风机盘管型号参数表标准化管理部编码-[99968T-6889628-J68568-1689N]

FP系列风机盘管 简述 FP系列风机盘管主要由风机、盘管、凝结水盘、控制和手动放气阀等组成,具有结构简单、节能、噪音低、耗电省及安装维护简便、操作方便等优点,是目前配合户室空调、中央空调进行室内温度及空气调节的理想产品。 本公司可提供用户多种规格及型式选择,标准工况下风量340m3/h~2380m3/h,机组余压0Pa~50Pa;型式有:普通型卧式/立式暗装、超薄型卧式/立式/明装/暗装、嵌入式、扇形吊顶式、立柜式、挂壁式等,更多了一份人性化设计,以完全满足用户对风量、冷量、风压及安装条件的要求。 特点 产品换热器系用美国TRIDAN公司的生产线制造而成,由无缝紫铜管串套高效双边翻铝片,采用机械涨管工艺,使管片结合紧密,传热性能优良,并经过特殊处理,在使用过程中,换热器的空气阻力明显减少,在风速较大时,不会产生冷凝水珠分溅,同时表面防腐蚀性能加强,采用锻黄铜结构集水头,大大延长了产品的使用寿命; 电动机采用三速低噪音专用马达,高精度封闭轴承,运行过程中无需加油维护,运转平稳可靠,使用寿命长达35000小时,电机引出线用金属软管保护,以免损伤; 采用广角蜗壳,金属多叶离心风轮,动平衡性高; 凝结水盘整体冲压一次成型,杜绝滴漏水现象,表面喷塑防腐处理,经久耐用; 保温材料采用高密度聚氨酯,导热系数小,耐水性能高,抗老化、阻燃、无毒,能保证各地全天候使用而无凝露现象发生。 吊装孔配有橡胶减震垫,最大限度降低机组噪音。 FP系列风机盘管性能参数表

注:低静压机组的额定风量是机外余压为0Pa时的值,在不带风口和过滤器的余压值为12Pa。 供冷工况参数:进口空气干球温度27℃,湿球温度℃,进水温度7℃,水温差5℃。 供热工况参数:进口空气干球温度21℃,进水温度60℃,热水流量同供冷工况。 上述表格中性能参数如有更改,恕不另行通知。 FP系列暗装风机盘管外型及安装尺寸 (请在订货时注明出风及回风形式) FP系列立式暗装风机盘管外型及安装尺寸 FP系列暗装风机盘管风管安装示意图 CFP系列超薄型风机盘管特点 超薄型豪华风机盘管系吸取国外同类产品之精华,并采纳空调专家和工程安装技术人员的宝贵意见,精心研制而成,具有: 机体厚度薄(明装仅188mm),占地面积小,就位安装方便,可任意调节安装高度; 超静音设计,采用精心研制的铝合金贯流风叶,同时采用优质吸音保温材料,使噪音降到最低; 采用优质注塑面板,整体外形设计美观流畅; 可内置双盛水盘,立式、卧式任意选择安装; 产品包装采用专用模具制成塑料泡沫内衬,确保机组在运输中不被损坏。 CFP系列超薄型风机盘管性能参数表

麦克维尔风冷模块式冷水机知识情况

麦克维尔空调MAC风冷模块式冷水机组 1开关机 ·按ON/OFF键,机组在开机(RUN灯亮)、关机(RUN灯灭)之间切换。 2模式选择 ·按“模式”键可在制冷/制热模式之间切换,须注意的是,模式切换必须在关机状态下进行,这样对压缩机能起到一定的保护作用。 3参数查询 ·使用本控制器能查询它所联网的任意一台机组的工作状态及参数(有哪几台压缩机在工作、设定的进水温度、实际进水温度、设定的出水温度、实际出水温度、机组的定时设置、制冷防冻温度、冬季防冻温度、除霜温度等)。 ·按“机组”键后机组闪烁,此时按“▲”或“▼”键改变机组号,查看到的是不同机组的当前参数,若要查询某个机组的工作参数,找到欲查询的机组号时按“确定”键即可查询该机组的工作参数了,按“▲”或“▼”键查看该机组的不同的参数。 4参数设置 按“机组”键后机组闪烁,此时按“▲”或“▼”键改变机组号,找到欲设置参数的机组号时按“确定”键即可设置该机组的工作参数了(可设置的参数有:制冷进水温度、制冷出水温度、制热进水温度、制热出水温度、防冻温度、除露点A温度、除露点B温度、除霜温度)。(password:55)按“▲”或“▼”键选择要设置的参数,按“确定”键后就可以按“▲”或“▼”键设置参数值,设置完成后按“确定”键保存设置结果。 重复步骤②可设置其它参数。 5实时时钟设置 ·用针形工具按“模式”键上方的小孔,液晶显示器上显示“星期设置”的字样,按“▲”或“▼”键设置当前时间是星期几,设置好了之后再按小孔,星期设置成功,同时显示器上显示“时钟设置”字样,时间会闪烁,此时按“▲”键修改小时,按“▼”键修改分钟,再按小孔即可保存设置的时钟。 6定时设置 按“定时”键后显示器上同时显示“星期设置”和“定时设置”的字样,此时按“▲”或“▼”键选择要设置定时的时间在星期几,选好后按“确定”键,显示器上显示“定时设置”的字样,此时按“▲”键选择要设置当天的哪个定时(能设置4个,在“机组号”上方有指示),按“▼”键选择“定时开”或“定时关”,按“确定”键后再按“▲”键修改小时,按“▼”键修改分钟,设置好时间后按“确定”键保存这个定时设置。 重复步骤①可设置其它的定时设置。如果想取消某一个定时设置,只需将它的定时时间设为上午0:00即可。 注意:定时开机和定时关机是以线控器上的时钟时间为准,如果时钟时间不准确,定时开机和定时关机的时间也将不准。在定时设置过程中,若按下“机组”、“模式”、“密码”等键将退出定时设置(不保存设置结果)。 7除霜 ·机组在制热状态时按“▲”或“▼”键直到“手动除霜”字样出现时按“确定”键,即进入手动除霜状态。退出除霜的条件:①除霜时间大于10分钟;或者②如果除霜感温探头检测到的温度大于设置的除霜温度且除霜时间大于1分钟。 8复位 ·按“▲”键上方的小孔可复位。 麦克维尔空调MAC风冷模块式冷水机组维修故障代码A

风机盘管详细参数[1]

一. 中央空调的最佳搭档: AFP系列风机盘管空调器主要有热交换器(高效换热盘管)、低噪声离心风机、凝水盘、壳体及控制器组成,是中央空调系统的末端装臵,设计先进,品种齐全,性能优越,用途广泛,通常用于噪声小,温度调节灵活的各种 机器精致、适用范围广 ●高能量、高效率 优质材料、工艺精湛 ●结构紧凑、占地少 ●遥控调控、任选室温 ●超低噪音、运转宁静 ●防菌装臵、健康伴侣 二. 机组结构特色: 盘管:超高效传热-采用高纯度无紫铜管 与美国TRIDAN专用翅片冲床冲制 的正弦波形铝制散热翅片,经机械 胀管与铝片紧密结合;专用水流分 布均匀的集水头。这些都能发挥理 想的整体传热效果。 壳体:坚固、简洁、漂亮。暗装壳体使用 一级热镀锌钢板经专用模具加工成 型,结构坚实不易变形。明装壳体 明亮流畅,工艺上采用酸洗、磷化、 烘烤后喷塑涂妆,以确保机体防锈及美观。 水盘:专用模具一次性拉伸成型,无焊缝存在,随后表面进经热浸电著烤漆处理。底部和四周均沾贴δ5PE板避免水盘表面冷凝水存在。 风机:运转宁静-风轮为高效率低噪声之翼截式离心风叶,动平衡性高。

电机:效率高耗电少-三速电机可依靠不同,转速调整风机风量和压头。轴承为含油滑动轴承,可自动填注润滑油,延长使用寿命,机座采用橡胶减振,降低运转噪音。 遥控开关:中央空调电子式风机开关,由于应用了国际最先进的微型集成电路中央处理器技术,从而使产品的电气性能更加稳定可靠,遥控开关外型小巧,操作简便。可与机组联动,实现异地控制机组启停。开关带有启停、风速调节、定时、控制盘管循环回路中电动阀的通断\等功能。红外线遥控,最大接受距离15m。 三. 健康环保机型: 风机盘管的健康伴侣 ——新型物理防菌装臵 风机盘管在制冷运行时,会产生大量的冷凝水,冷凝水会在积水盘中形成一层水膜。由于温湿度适宜(10℃左右)。病菌便会在水盘中存活,然后在风机盘管停止工作后,水盘中的温度便达到室温(30℃左右),病菌便会大量繁殖,久而久之,水盘中存在大量各种不同的病菌,成为一个污染源,严重恶化室内空气品质,尤其是适合空气传播的病菌在水盘中生存和繁殖后,便会成为病源。 为解决这一难题,成功开发出了专有技术。采用特殊的PTC材料,在风机盘管停止运行后,将水盘保持在干燥和高温状态(60℃以上),这样使病菌无法生存和繁殖。 由于采用物理方法,在杀灭病菌时,就不会产生二次污染,也不会象使用某些消毒液时对人体和环境造成不利的影响。

技术规格书风机盘管

.一般要求 本章说明有关风机盘管的制造、安装及调试所需的各项技术规格要求。 应按照设备表内所标注的供冷量/供热量、送风量、用电量、水流量及容许的噪声等技术要求选取及提供合适的机种。有关要求是按照风机盘管在中速运行时所能提供的功能而定。 质量标准 有关设备须符合下列有关国际认可的机构/组织或中国有关政府机关所制定的条例和规范: a)所有国内有关单位的规范要求。 b)JB/T 50056-99。 c)JB/T 9066-99。 d)美国制冷协会标准(ARI)440-2005。 e)美国制冷协会标准(ARI)410-2001。 设备应由业主认可的制造厂制造,制造厂须有十年以上生产同类型设备之经验,并需要有超过十套或以上已成功运行五年或以上同类型设备的记录。生产厂家需要具有ISO9001 全面质量管理体系的认证。 有关设备,无论在运送、储存及安装期间,应采取正确的保护设施,以确保设备不受破损。

.技术要求 每台风机盘管须附有原厂的标志牌,详细标明厂家名称\机种型号和系列编号。 盘管的工作和试验压力,须符合本技术说明书第四章“系统试验及试运行”中所规定的要求。 每台风机盘管的风机设计须可提供不少于30Pa的机外余压以应付风机盘管所接允的送/回风管及格栅或散流器所产生的阻力。 所有风机盘管在正常操作时,如发觉所产生的振动和噪声超越可接受的程度时,承包单位应提供足够的减振和消声措施。 应提供由原厂装配的风机备用管包括风机、盘管、冷凝水盆、电动机及配件等装配在一保温的金属外壳内。所有风机盘管不可含有任保有棉或有石棉产品。 每台风机盘管应配备一套设有由人手操控的三速控制开关的温度控制器。 风机盘管须设有适当的接口供冷冻/采暖水管、冷凝水管、送/回风管、电源及控制线接驳。 风机 a)风机的叶轮及外壳须为全金属制造。 b)风机应为直驱式离心前弯式叶片型。 c)风机须经静态及动态平衡,并能在三个不同的速度运作。 空气过滤器

风机盘管型号全参数表

风机盘管型号全参数表 The Standardization Office was revised on the afternoon of December 13, 2020

FP系列风机盘管 简述 FP系列风机盘管主要由风机、盘管、凝结水盘、控制和手动放气阀等组成,具有结构简单、节能、噪音低、耗电省及安装维护简便、操作方便等优点,是目前配合户室空调、中央空调进行室内温度及空气调节的理想产品。 本公司可提供用户多种规格及型式选择,标准工况下风量340m3/h~2380m3/h,机组余压0Pa~50Pa;型式有:普通型卧式/立式暗装、超薄型卧式/立式/明装/暗装、嵌入式、扇形吊顶式、立柜式、挂壁式等,更多了一份人性化设计,以完全满足用户对风量、冷量、风压及安装条件的要求。 特点 产品换热器系用美国TRIDAN公司的生产线制造而成,由无缝紫铜管串套高效双边翻铝片,采用机械涨管工艺,使管片结合紧密,传热性能优良,并经过特殊处理,在使用过程中,换热器的空气阻力明显减少,在风速较大时,不会产生冷凝水珠分溅,同时表面防腐蚀性能加强,采用锻黄铜结构集水头,大大延长了产品的使用寿命; 电动机采用三速低噪音专用马达,高精度封闭轴承,运行过程中无需加油维护,运转平稳可靠,使用寿命长达35000小时,电机引出线用金属软管保护,以免损伤; 采用广角蜗壳,金属多叶离心风轮,动平衡性高; 凝结水盘整体冲压一次成型,杜绝滴漏水现象,表面喷塑防腐处理,经久耐用; 保温材料采用高密度聚氨酯,导热系数小,耐水性能高,抗老化、阻燃、无毒,能保证各地全天候使用而无凝露现象发生。 吊装孔配有橡胶减震垫,最大限度降低机组噪音。

风机盘管型参数表讲解

风机盘管型参数表讲解 Document number【SA80SAB-SAA9SYT-SAATC-SA6UT-SA18】

FP系列风机盘管 简述 FP系列风机盘管主要由风机、盘管、凝结水盘、控制和手动放气阀等组成,具有结构简单、节能、噪音低、耗电省及安装维护简便、操作方便等优点,是目前配合户室空调、中央空调进行室内温度及空气调节的理想产品。 本公司可提供用户多种规格及型式选择,标准工况下风量340m3/h~2380m3/h,机组余压 0Pa~50Pa;型式有:普通型卧式/立式暗装、超薄型卧式/立式/明装/暗装、嵌入式、扇形吊顶式、立柜式、挂壁式等,更多了一份人性化设计,以完全满足用户对风量、冷量、风压及安装条件的要求。 特点 产品换热器系用美国TRIDAN公司的生产线制造而成,由无缝紫铜管串套高效双边翻铝片,采用机械涨管工艺,使管片结合紧密,传热性能优良,并经过特殊处理,在使用过程中,换热器的空气阻力明显减少,在风速较大时,不会产生冷凝水珠分溅,同时表面防腐蚀性能加强,采用锻黄铜结构集水头,大大延长了产品的使用寿命; 电动机采用三速低噪音专用马达,高精度封闭轴承,运行过程中无需加油维护,运转平稳可靠,使用寿命长达35000小时,电机引出线用金属软管保护,以免损伤; 采用广角蜗壳,金属多叶离心风轮,动平衡性高; 凝结水盘整体冲压一次成型,杜绝滴漏水现象,表面喷塑防腐处理,经久耐用; 保温材料采用高密度聚氨酯,导热系数小,耐水性能高,抗老化、阻燃、无毒,能保证各地全天候使用而无凝露现象发生。 吊装孔配有橡胶减震垫,最大限度降低机组噪音。 FP系列风机盘管性能参数表

相关主题