Schweitzer Engineering Laboratories, Inc.SEL-751A Data Sheet

SEL-751A Feeder Protection Relay

Major Features and Benefits

The SEL-751A Feeder Protection Relay provides an exceptional combination of protection, monitoring, control, and communication in an industrial package.

?Protection Features. Phase, negative-sequence, residual-ground, and neutral-ground overcurrent elements protect lines

and equipment. Implement load shedding and other control schemes with over- and underfrequency and optional over-and undervoltage elements.

?Operator Controls. Four programmable front-panel pushbuttons allow for easy trip and close of the breaker. Implement

remote and local control functions.

?Relay and Logic Settings Software. AC SEL ERATOR ? QuickSet? SEL-5030 Software reduces engineering costs for

relay settings and logic programming. Tools in AC SEL ERATOR QuickSet make it easy to develop SEL OGIC ? control equations.

?Metering and Mo nito ring. Built-in metering functions eliminate separately mounted metering devices. Analyze

Sequential Events Recorder (SER) reports and oscillographic event reports for rapid commissioning, testing, and post-fault diagnostics. Unsolicited SER protocol allows station-wide collection of binary SER messages.

?Wye or Delta V oltage Inputs. Settings allow either wye-connected, open-delta-connected, or single voltage inputs to the

relay (optional).

?Additional Standard Features. Includes Modbus ?RTU, Event Messenger support, M IRRORED B ITS ? communications,

load profile, support for 12 external RTDs (SEL-2600 series module), IRIG-B input, and advanced SEL OGIC .

?Optional Features. Includes IEC 61850, Modbus TCP/IP , 10 internal RTDs, expanded digital/analog I/O, voltage inputs,

additional EIA-232 or EIA-485 communication ports, fiber-optic serial port, and configurable labels.

SEL-751A Data Sheet Schweitzer Engineering Laboratories, Inc.

2

Functional Overview

Figure 1Functional Diagram

Protection Features

The SEL-751A includes a robust set of phase, negative-sequence, residual, and neutral overcurrent elements.Each element type has four levels of instantaneous protec-tion. Each element type has two time-overcurrent elements (except negative-sequence that has one time-overcurrent element).

The curves available in the SEL-751A are listed in Table 1.

The SEL-751A has two reset characteristic choices for each time-overcurrent element. One choice resets the elements if current drops below pickup for at least one cycle. The other choice emulates electromechanical induction disc elements, where the reset time depends on the time dial setting, the percentage of disc travel, and the amount of current.

Overcurrent Elements for Phase Fault Detection

Phase and negative-sequence overcurrent elements detect phase faults. Negative-sequence current elements ignore three-phase load to provide more sensitive coverage of phase-to-phase faults. Phase overcurrent elements detect three-phase faults, which do not have significant negative-

sequence quantities.

Table 1Time-Overcurrent Curves US

IEC

Moderately Inverse Standard Inverse Inverse Very Inverse Very Inverse Extremely Inverse Extremely Inverse Long-Time Inverse Short-Time Inverse

Short-Time Inverse

3

Overcurrent Elements for Ground Fault Detection

Residual (IG), neutral (IN), and negative-sequence over-current elements detect ground faults. In addition to the 1A/5 A neutral CT, the SEL-751A offers an optional high-sensitive neutral element with sensitivity as low as 0.125mA secondary.

Wye or Open-Delta Voltages

Wye-connected (four-wire) voltage or open-delta-con-nected (three-wire) voltage can be applied to three-phase voltage inputs V A, VB, VC, and N, as shown in Figure2. You only need to make a global setting (DELTA_Y = WYE or DELTA_Y = DELTA, respectively) and an exter-nal wiring change—no internal relay hardware changes or adjustments are required. Thus, a single SEL-751A model meets all your distribution protection needs, regardless of available three-phase voltage.

Figure2Connect Wye or Open-Delta Voltage to

SEL-751A Three-Phase Voltage Inputs

In addition, the SEL-751A supports single voltage input. For customers with a single PT input, the SEL-751A will assume balanced voltage input for all protection and metering functions.Loss-of-Potential Logic

The SEL-751A includes loss-of-potential logic that detects one, two, or three blown potential fuses. This pat-ented loss-of-potential logic is unique, as it does not require settings and is universally applicable. The loss-of-potential feature allows for the blocking of protection elements to add security during fuse failure.

Voltage and Frequency Elements for Extra Protection and Control Over- and Undervoltage Elements

Phase-to-ground or phase-to-phase overvoltage (59) and undervoltage (27) elements in the SEL-751A create the following protection and control schemes:

?Trip/alarm or event report triggers for over- and undervoltage conditions.

?Undervoltage (27) load shedding scheme (having both 27 and 81U load shedding schemes allows

detection of system MVAR- and MW-deficient

conditions)

Over- and Underfrequency Protection

Four levels of secure overfrequency (81O) or underfre-quency (81U) elements detect true frequency distur-bances. Use the independently time-delayed output of these elements to shed load or trip local generation. Fre-quency measurements are made with the voltage input (if available) and switches automatically to current input when voltages are not available.

Implement an internal multistage frequency trip/restore scheme at each breaker location using the multiple over-/underfrequency levels. This avoids the cost of wiring a complicated trip and control scheme from a separate frequency relay.

Additional Ordering Options

The following options can be ordered for any SEL-751A model (see the Model Option Table for details).

?Ethernet 10/100BASE-T, Modbus TCP, FTP, Telnet ?IEC 61850

?DeviceNet

?EIA-232 or EIA-485 Communications

?Fiber-Optic Serial Port

?Additional EIA-232 or EIA-485 Port

?Analog I/O (4 AI/4 AO, 8 AI)

?Digital I/O (4 DI/4 DO, 8 DI, 3 DI/4 DO/1 AO)

?V oltage Inputs

?10 RTDs

?Conformal coating for chemically harsh and high moisture environments

Schweitzer Engineering Laboratories, Inc.SEL-751A Data Sheet

4

Operator Controls

Operator Controls Eliminate Traditional Panel Control Switches Four conveniently sized operator controls are located on the relay front panel (see Figure2). The SER can be set to track operator controls. Change operator control functions using SEL OGIC control equations.

Figure3Operator Controls (Standard Model) Note: All text can be changed with the configurable labels—see Configurable Labels on page7.The following operator control descriptions are for factory-set logic.

AUX 1:The {AUX 1} operator control allows the SEL-751A to switch the active setting group between the main setting group (Group 1) and the alternate setting group (Group 2). The corresponding LED illuminates to indicate that the alternate setting group is active. Lock:The {LOCK} operator control blocks selected functions. Press it for at least three seconds to engage or disengage the lock function. While locked in position, the following operator controls cannot change state if pressed: {AUX 1}, {TRIP}, and {CLOSE}.

Close and Trip:Use the {CLOSE} and {TRIP} operator controls to close and open the connected circuit breaker. They can be programmed with intentional time delays to support operational requirements for breaker-mounted relays. This allows the operator to press the {CLOSE} or {TRIP} pushbutton, then move to an alternate location before the breaker command is executed.

Relay and Logic Settings Software

AC SEL ERATOR QuickSet Software simplifies settings and provides analysis support for the SEL-751A. With AC SEL ERATOR QuickSet you have several ways to create and manage relay settings:

?Develop settings off-line with an intelligent settings editor that only allows valid settings.

?Create SEL OGIC control equations with a drag-and-drop text editor.

?Configure proper settings using online help.

?Organize settings with the relay database manager.?Load and retrieve settings using a simple PC communications link.With AC SEL ERATOR QuickSet you can verify settings and

analyze events; and analyze power system events with the

integrated waveform and harmonic analysis tools.

The following features of AC SEL ERATOR QuickSet can

be used to monitor, commission, and test the SEL-751A:?The Human-Machine Interface (HMI) to monitor meter data, Relay Word bits, and output contacts

status during testing.

?The PC interface to remotely retrieve power system data.

Metering and Monitoring

The SEL-751A provides extensive metering capabilities. See Specifications on page12 for metering and power measurement accuracies.

As shown in Table2, metered quantities include phase voltages and currents; sequence voltages and currents;power, frequency, and energy; and maximum/minimum logging of selected quantities. The relay reports all metered quantities in primary quantities (current in A primary and voltage in V primary).

SEL-751A Data Sheet Schweitzer Engineering Laboratories, Inc.

Schweitzer Engineering Laboratories, Inc.SEL-751A Data Sheet

5

Load Profile

The SEL-751A feature a programmable Load Profile (LDP) recorder that records up to 17 metering quantities into nonvolatile memory at fixed time intervals. The LDP saves several days to several weeks of the most recent data depending on the LDP settings.

Event Reporting and Sequential Events Recorder (SER)

Event Reports and the SER simplify post-fault analysis and improve understanding of simple and complex pro-tective scheme operations. In response to a user-selected trigger, the voltage, current, frequency, and element status information contained in each event report confirms relay,scheme, and system performance for every fault. Decide how much detail is necessary when you request an event report (e.g., 1/4-cycle or 1/16-cycle resolution, filtered or raw analog data). The relay stores the most recent

64-cycle or 15-cycle event reports in nonvolatile memory.The relay stores the most recent five 64-cycle or twenty-two 15-cycle event reports in nonvolatile memory. The relay always appends relay settings to the bottom of each event report.

The following analog data formats are available:?1/4-cycle or 1/16-cycle resolution ?Unfiltered or filtered analog ?ASCII or Compressed ASCII The relay SER feature stores the latest 1024 entries. Use this feature to gain a broad perspective at a glance. An SER entry helps to monitor input/output change-of-state occurrences, element pickup/dropout.

The IRIG-B time-code input synchronizes the SEL-751A time to within ±5 ms of the time-source input. A convenient source for this time code is a SEL-2401 Satellite-Synchronized Clock or the SEL-2032, SEL-2030, or SEL-2020 Communications Processor (via Serial Port 2 on the SEL-751A).

Automation

Flexible Control Logic and Integration Features

The SEL-751A is equipped with up to four indepen-dently operated serial ports: one EIA-232 port on the front, one EIA-232 or EIA-485 port on the rear, and one fiber-optic port. Additionally, one EIA-232 or EIA-485port option card. The relay does not require special com-munications software. Use any system that emulates a standard terminal system. Establish communication by connecting computers; modems; protocol converters;printers; an SEL-2032, SEL-2030 or SEL-2020 Commu-nications Processor; SCADA serial port; and/or RTU for local or remote communication. Refer to Table 3 for a list of communications protocols available in the SEL-751A.

Apply an SEL communications processor as the hub of a star network, with point-to-point fiber or copper connection between the hub and the SEL-751A (Figure 4).

Figure 4Example Communication System

Table 2Metering Capabilities Quantities

Description

Currents IA, IB, IC, IN, IG Input currents, residual ground current (IG = 3I0 = IA + IB + IC)V oltages V A, VB, VC Wye-connected voltage inputs V oltages V AB, VBC, VCA Delta-connected voltage inputs

Power kW, kV AR, kV A Three-phase kilowatts, kilovars, and kilovolt-amps

Energy MWh3P, MV

ARh3P-IN, MV ARh3P-OUT, MV Ah3P Three-phase megawatt hours, megavar-hours (IN & OUT), and megavolt-amp-hours Power Factor PF3P Three-phase power factor (leading or lagging)Sequence 3I2, 3I0, 3V2, 3V0Negative- and zero-sequence currents and voltages Frequency, FREQ (Hz)

Instantaneous power system frequency

6

The communications processor supports external communications links including the public switched telephone network for engineering access to dial-out alerts and private line connections of the SCADA system.SEL manufactures a variety of standard cables for connecting this and other relays to a variety of external devices. Consult your SEL representative for more information on cable availability.

SEL-751A control logic improves integration in the following ways:

?Replaces traditional panel control switches.

Eliminate traditional panel control switches with 32

local bits. Set, clear, or pulse local bits with the

front-panel pushbuttons and display. Program the

local bits into your control scheme with SEL OGIC

control equations. Use the local bits to perform

functions such as a trip test or a breaker trip/close.?Eliminates RTU-to-relay wiring. Eliminate RTU-to-relay wiring with 32 remote bits. Set, clear, or pulse

remote bits using serial port commands. Program

the remote bits into your control scheme with

SEL OGIC control equations. Use remote bits for

SCADA-type control operations such as trip, close,

and settings group selection.

?Replaces traditional latching relays. Replace up to

32 traditional latching relays for such functions as

“remote control enable” with latch bits. Program

latch set and latch reset conditions with SEL OGIC

control equations. Set or reset the nonvolatile latch

bits using optoisolated inputs, remote bits, local

bits, or any programmable logic condition. The

latch bits retain their state when the relay loses

power.

?Replaces traditional indicating panel lights. Replace traditional indicating panel lights with 32

programmable displays. Define custom messages

(e.g., Breaker Open, Breaker Closed) to report

power system or relay conditions on the front-panel

display. Use Advanced SEL OGIC control equations

to control which messages the relay displays.

?Eliminate external timers. Eliminate external timers for custom protection or control schemes with 32

general purpose SEL OGIC control equation timers.

Each timer has independent time-delay pickup and

dropout settings. Program each timer input with any

desired element (e.g., time qualify a current

element). Assign the timer output to trip logic,

transfer trip communications, or other control

scheme logic.

?Eliminate settings changes. Selectable setting groups make the SEL-751A ideal for applications

requiring frequent setting changes and for adapting

the protection to changing system conditions.

The relay stores three setting groups. Select the active setting group by optoisolated input, command, or other programmable conditions. Use these setting groups to c ove r a w i d e r a n g e o f p r o t e c t i o n a n d c o n t r o l contingencies.

Switching setting groups switches logic and relay element settings. Program groups for different operating conditions, such as feed er paralleling, station maintenance, seasonal operations, emergency contingencies, loading, source changes, and downstream relay setting changes.

Fast SER Protocol

SEL Fast Sequential Events Recorder (SER) Protocol provides SER events to an automated data collection system. SEL Fast SER Protocol is available on any rear serial port. Devices with embedded processing capability

Table3Communications Protocols

Type Description

Simple ASCII Plain language commands for human and simple machine communications. Use for metering, setting, self-test status, event reporting, and other functions.

Compressed ASCII Comma-delimited ASCII data reports. Allows external devices to obtain relay data in an appropriate format for direct import into spreadsheets and database programs. Data are checksum protected.

Extended Fast Meter and Fast Operate Binary protocol for machine-to-machine communications.

Quickly updates SEL-2032/2030/2020 communications processors, RTUs, and other substation devices with metering information, relay element, I/O status, time-tags, open and close commands, and summary event reports. Data are checksum protected. Binary and ASCII protocols operate simultaneously over the same communications lines so control operator metering information is not lost while a technician is transferring an event report.

Fast SER Protocol Provides SER events to an automated data collection system.

Modbus Modbus with point remapping. Includes access to metering data, protection elements, contact I/O,

targets, SER, relay summary event reports, and setting groups.

IEC 61850Ethernet-based international standard for interoperability between intelligent devices in a substation.

Operates remote bits and I/O. Monitors Relay Word bits and analog quantities.

SEL-751A Data Sheet Schweitzer Engineering Laboratories, Inc.

7

can use these messages to enable and accept unsolicited binary SER messages from SEL-751A Relays.

SEL relays and communications processors have two separate data streams that share the same serial port. The normal serial interface consists of ASCII character commands and reports that are intelligible to people using a terminal or terminal emulation package. The binary data streams can interrupt the ASCII data stream to obtain information, and then allow the ASCII data stream to c o n t i n u e.T h i s m e c h a n i s m a l l ow s a s i n g l e communications channel to be used for ASCII communications (e.g., transmission of a long event report) interleaved with short bursts of binary data to support fast acquisition of metering or SER data.

Additional Features

M IRRORED B ITS Relay-to-Relay Communications

The SEL-patented M IRRORED B ITS communications tech-nology provides bidirectional relay-to-relay digital com-munications. M IRRORED B ITS can operate independently on up to two EIA-232 rear serial ports and one fiber-optic rear serial port on a single SEL-751A.

This bidirectional digital communication creates eight additional virtual outputs (transmitted M IRRORED B ITS) a n d e i g h t a d d i t i o n a l v i r t u a l i n p u t s(r e c e ive d M IRRORED B ITS) for each serial port operating in the M IRRORED B ITS mode (see Figure5). Use these M IRRORED B ITS to transmit/receive information between upstream relays and downstream recloser control (e.g., SEL-351R) to enhance coordination and achieve faster tripping for downstream faults. M IRRORED B ITS technology also helps reduce total scheme operating time by eliminating the need to assert output contacts to transmit information.

Figure5M IRRORED B ITS Transmit and Receive Bits Status and Trip Target LEDs

The SEL-751A includes 16 status and trip target LEDs on the front panel. As shipped from the factory, all LEDs are predefined and fixed in settings. You can reprogram these for specific applications. This combination of targets is explained and shown in Figure7. Some front-panel rela-beling of LEDs may be needed if you reprogram them for unique or specific applications—see Configurable Labels. Event Messenger Points

The SEL-751A, when used with the SEL-3010, has the capability to allow for ASCII to voice translation of up to 32 user-defined messages along with analog data that has been measured or calculated by the relay. This combina-tion can allow the user to receive voice messages on any phone for alerts for transition of any Relay Word bits in the relay.

Verbal notification of breaker openings, fuse failures, RTD alarms, etc. can now be sent directly to your cell phone through the use of your SEL-751A and SEL-3010 (must be connected to an analog telephone line). In addition, messages can include an analog value such as current, voltage, or power measurements made by the SEL-751A.

Configurable Labels

Use the optional configurable labels to relabel the opera-tor controls and LEDs (shown in Figure7) to suit the installation requirements. This feature includes preprinted labels (with factory default text), blank label media, and a Microsoft? Word template on CD-ROM. This allows quick, professional-looking labels for the SEL-751A. Labels may also be customized without the use of a PC by writing the new label on the blank stock provided. The ability to customize the control and indication features allows specific utility or industry procedures to be imple-mented without the need for adhesive labels. All of the figures in this data sheet show the factory default labels of the SEL-751A, including the standard model shown in Figure7.

Schweitzer Engineering Laboratories, Inc.SEL-751A Data Sheet

8

Guideform Specification

Feeder protection shall be provided by a microprocessor-based relay equipped with the following protection, moni-toring, control, automation, and reporting functions. Self-checking functions shall be included. Specific requirements are as follows.

Protection and Control

?Phase, neutral, residual, and negative-sequence overcurrent elements (50P/50N/50G/50Q)

?Phase, neutral, residual, and negative-sequence time-overcurrent elements (51P/51N/51G/51Q)

?Over- and underfrequency (81)

?Breaker/contactor failure

When voltage inputs are specified, the relay shall provide the following protection elements.

?Over- and undervoltage (59, 27)

?Power factor (55)

?V oltage-based over- and underfrequency (81)

?Loss-of-potential (60)

Temperature Inputs

Availability of up to 12 RTD inputs in an external module (SEL-2600 series) or 10 RTD inputs with an internal card, which, when included, shall have the following features:?Optical fiber transmission of RTD temperatures (using SEL-2600 series) to relay: range >400 m

?Separately field-selected RTD types: Pt100, Ni100, Ni120, or Cu10

?Noise immunity (50 Hz and higher) on RTD inputs up to 1.4 Vac peak

?One contact input (with SEL-2600 series) Automation

?32 local control logic points, 32 remote control logic points, 32 latching logic points, 32 counters,

32 math variables, 32 logic variables, and 32 timers ?SEL OGIC control equations with Boolean and math equations capability for logic and control Communications/Integration

?ASCII, Modbus RTU, DeviceNet, Telnet, F TP, Modbus TCP, and IEC 61850 protocols

?One front-panel EIA-232 port and one rear-panel EIA-232 or EIA-485 port, one optional fiber-optic

serial port, and one optional Ethernet port

?Capability for an additional rear-panel EIA-232 or EIA-485 port

?Windows?-based PC software for settings and report retrieval Front-Panel Visualization

?The front panel shall be capable of displaying measured values, calculated values, I/O status,

device status, and configuration parameters on a

front-panel LCD display.

?The display shall have a rotating capability to display custom messages and data. 32 display

messages shall be provided.

?The front panel shall also have a minimum of 6 user-programmable LEDs and 4 user-

programmable pushbutton controls with 8

programmable LEDs.

Monitoring and Reporting

?Load-profile monitoring—Provide periodic snap-shot (selectable rate from every 5 to 60 minutes) of

up to 17 selectable analog quantities

?Event summaries—

F

ault type and trip data, including time of tripping

?Event reports—15-cycle length (up to 22 reports) or 64-cycle length (up to 5 reports) with 4 or

16samples/cycle resolution

?Sequential Events Recorder (SER)—Up to 1024 time-tagged, most recent input, output, and element

transitions

?Data stored in nonvolatile, Flash memory Hardware

?Operating temperature range of –40° to +85°C

?Power supply input operating voltage range of 24–48 Vdc, 110–250 Vdc, or 110–230 Vac

?Demodulated IRIG-B time-synchronization input capability

?Optional 10 internal RTD inputs or 12 external RTD inputs

?5 A or 1 A, ac current inputs IA, IB, IC, and IN with optional 2.5 mA sensitive IN input

?300 V maximum, 3 ac voltage inputs

?Flexible, configurable I/O, including digital I/O and analog I/O

?Electromechanical or optional fast hybrid (high-speed, high-current interruption) digital outputs

?Optoisolated digital inputs

?Jumper-selectable current (up to ±20 mA range) or voltage (up to ±10 V range) analog inputs

?Jumper selectable current (up to ±20 mA range) or voltage (up to ±10 V range) analog outputs

?Relay front panel shall meet the requirements of NEMA 12/IP65

?Conformal coat of circuit boards

SEL-751A Data Sheet Schweitzer Engineering Laboratories, Inc.

9 Wiring Diagrams

Figure6Wiring Diagram SEL-751A

Schweitzer Engineering Laboratories, Inc.SEL-751A Data Sheet

SEL-751A Data Sheet Schweitzer Engineering Laboratories, Inc.

10

Panel Diagrams

Figure 7Front Panel With Default Configurable Labels

Figure 8

Fiber-Optic Serial, Ethernet, EIA-232 Communication, 4 DO/3 DI/1 AO, and Voltage Option

(A) Rear-Panel Layout

(B) Side-Panel Input and Output Designations

Schweitzer Engineering Laboratories, Inc.SEL-751A Data Sheet

11

Figure 9

Fiber-Optic Serial, Ethernet, 8 DI, RTD, and 4 AI/4 AO Option

Figure 10

Fiber-Optic Serial, DeviceNet, Fast Hybrid 4 DI/4 DO, and Voltage Option

(A) Rear-Panel Layout

(B) Side-Panel Input and Output Designations

(A) Rear-Panel Layout

SEL-751A Data Sheet Schweitzer Engineering Laboratories, Inc.

12

Relay Dimensions

Figure 11SEL-751A Dimensions for Rack- and Panel-Mount Models

Specifications

General

AC Current Input

AC Voltage Inputs

Rated Operating V oltage (U e ):100–250 Vac Rated Continuous V oltage:300 Vac

10 Second Thermal:600 Vac Rated Frequency:50/60 ±5 Hz Burden:

< 0.1 V A

Power Supply

Rated Supply V oltage:110–230 Vac; 24–48Vdc; 110–250 Vdc Input V oltage Range:85–264 Vac; 19.2–52.8Vdc; 85–275 Vdc Frequency:50/60 ±5 Hz Power Consumption:< 40 V A (ac)

< 15 W (dc)

Interruptions:

50 ms @ 120 Vac/Vdc 100 ms @ 250 Vac/Vdc

Phase and Neutral Currents I NOM

= 5 A

= 1 A

= 2.5 mA

Rated Range (X/R = 40):0.1–96.0 A

0.02–19.20 A 0.125–12.5 mA Continuous Thermal Rating:

15 A 3 A 7.5 mA 1 Second Thermal:500 A 100 A —

Rated Frequency:50/60 ±5 Hz 50/60 ±5 Hz

50/60 ±5 Hz Burden (per phase):

<0.1 V A

< 0.01 V A

<0.1 mV A

NOTE: I NOM = 1 A, 5 A, or 2.5 mA (high sensitivity) secondary depending on model.

Output Contacts

General

OUT103 is Form C Trip Output, all other outputs are Form A.Dielectric Test V oltage:2000 Vac Impulse Withstand V oltage (U imp ):4000 V

Mechanical Durability:10,000 no load operations

Pickup/Dropout Time:≤5 ms (coil energization to contact closure)

DC Output Ratings

Rated Operational V oltage:250 Vdc Rated V oltage Range:19.2–275 Vdc Rated Insulation V oltage:300 Vdc

Make:

30 A @ 250 Vdc per IEEE C37.90Continuous Carry: 6 A @ 70°C 4 A @ 85°C Thermal:

50 A for 1 s

Contact Protection:

360 Vdc, 40 J MOV protection across open contacts Breaking Capacity (10,000 operations) per IEC 60255-0-20:1974:24 Vdc 0.75 A L/R = 40 ms 48 Vdc 0.50 A L/R = 40 ms 125 Vdc 0.30 A L/R = 40 ms 250 Vdc 0.20 A L/R = 40 ms Cyclic (2.5 cycles/second) per IEC 60255-0-20:1974:

24 Vdc 0.75 A L/R = 40 ms 48 Vdc 0.50 A L/R = 40 ms 125 Vdc 0.30 A L/R = 40 ms 250 Vdc 0.20 A L/R = 40 ms

Schweitzer Engineering Laboratories, Inc.SEL-751A Data Sheet

13

AC Output Ratings Maximum Operational V oltage (U e ) Rating:240 Vac

Insulation V oltage (U i ) Rating (excluding EN 61010-1):300 Vac

Utilization Category:AC-15 (control of electromagnetic loads >72V A)Contact Rating Designation:

B300 (B = 5 A, 300 = rated insulation voltage)

V oltage Protection Across Open Contacts:270 Vac, 40 J Rated Operational Current (I e ):

3 A @ 120 Vac 1.5 A @ 240 Vac

Conventional Enclosed Thermal Current (I the ) Rating: 5 A Rated Frequency:

50/60 ±5 Hz

Electrical Durability Make V A Rating:3600 V A, Electrical Durability Break V A Rating:360 V A, Fast Hybrid (high-speed, high-current interrupting)Make:30 A

Carry: 6 A continuous carry at 70°C 4 A continuous carry at 85°C 1 s Rating:

50 A

MOV Protection

(maximum voltage):250 Vac/330 Vdc Pickup Time:< 50 μs, resistive load Dropout Time:8 ms, resistive load

Break Capacity (10000 operations):

48 Vdc

10.0 A L/R = 40 ms 125 Vdc 10.0 A L/R = 40 ms 250 Vdc

10.0 A

L/R = 20 ms

Cyclic Capacity (4 cycles in 1 second, followed by 2 minutes idle for thermal dissipation):48 Vdc 10.0 A L/R = 40 ms 125 Vdc 10.0 A L/R = 40 ms 250 Vdc

10.0 A

L/R = 20 ms

NOTE: Per IEC 60255-23:1994, using the simplified method of assessment.NOTE: Make rating per IEEE C37.90-1989.

Optoisolated Control Inputs

When used with dc control signals 250 V:ON for 200–275 Vdc OFF below 150 Vdc 220 V:ON for 176–242 Vdc OFF below 132 Vdc 125 V:ON for 100–135.5 Vdc OFF below 75 Vdc 110 V:

ON for 88–121 Vdc OFF below 66 Vdc

φcos 0.3=φcos 0.3

=UL/CSA Digital Output Contact Temperature Derating for Operating at Elevated Temperatures

Digital Output (D)

Cards Installed Operating Ambient Maximum Value of Current (I the )Duty Factor 1–3less than or equal to 60°C 5.0 A Continuous 1–3

between 60°C and 70°C

2.5 A

Continuous

48 V:ON for 38.4–52.8 Vdc OFF below 28.8 Vdc 24 V:

ON for 15–30 Vdc OFF for <5 Vdc

When used with ac control signals

250 V:ON for 170.6–300 Vac OFF below 106 Vac 220 V:ON for 150.2–264 Vac OFF below 93.3 Vac 125 V:ON for 85–150 Vac OFF below 53 Vac 110 V:ON for 75.1–132 Vac OFF below 46.6 Vac 48 V:ON for 32.8–60 Vac OFF below 20.3 Vac 24 V:

ON for 14–27 Vac OFF below 5Vac

Current draw at nominal dc voltage:2mA (at 220–250V)4mA (at 48–125V)

10mA (at 24V)Rated Impulse Withstand V oltage (U imp ):4000 V

Analog Output (Optional)

1A0

4A0Current:4–20mA ±20mA V oltage:—±10V Load at 1 mA:—0–15k ΩLoad at 20 mA:0–300Ω0–750ΩLoad at 10 V:—>2000Ω

Refresh Rate:100 ms

Error:< ±0.55%, Full Scale, at 25°C Select From:

Analog quantities available in the relay

Analog Inputs (Optional)

Maximum Input Range:

±20mA ±10V

Operational range set by user Input Impedance:200Ω (current mode)>10k Ω (voltage mode)

Accuracy at 25°C:With user calibration:

0.050% of ±20mA (current mode)0.025% of ±10V (voltage mode)

Without user calibration:0.050% of ±20mA (current mode)

0.25% of ±10V (voltage mode)Accuracy Variation With Temperature:

±0.015% per °C of full-scale (±20 mA or ±10 V)

Frequency and Phase Rotation

System Frequency:50, 60 Hz Phase Rotation:ABC, ACB Frequency Tracking:

20–70 Hz

Time-Code Input

Format:Demodulated IRIG-B On (1) State:V ih ≥2.2 V Off (0) State:V il ≤0.8 V Input Impedance: 2 k Ω

Accuracy:

±3 milliseconds

14

Communications Ports

Standard EIA-232 (2 ports)

Location:Front Panel

Rear Panel

Data Speed:300–38400 bps

10/100BASE-T Ethernet port (copper)

Multimode fiber-optic

Laser/LED:Class 1 LED

Complies with IEC60825-1:1993 +A1:1997

+ A2:2001

Optional Communications Cards

Option 1:Modbus RTU Protocol or ASCII Protocol

over EIA-232 or EIA-485

Option 2: DeviceNet Protocol Communications Protocols

SEL, Modbus, FTP, TCP/IP, Telnet, IEC 61850, M IRRORED B ITS

Communications, EVMSG, and DeviceNet.

Operating Temperature

IEC Performance Rating:

(per IEC/EN 60068-2-1

& 60068-2-2)–40° to +85°C (–40° to +185°F)

UL/CSA Safety Rating:+70°C (158°F) maximum

DeviceNet

Communications

Card Rating:+60°C (140°F) maximum

Operating Environment

Pollution Degree:2

Overvoltage Category:II

Atmospheric Pressure:80–110 kPa

Relative Humidity:5–95%, noncondensing

Maximum Altitude:2000 m

Dimensions

144.0 mm (5.67 in.) x 192.0 mm (7.56 in.) x 147.4 mm (5.80 in.) Weight

2.0 kg (4.4 lbs)

Terminal Connections

Current Inputs Terminal Block Tightening Torque

Minimum:0.9 Nm (8 in-lb)

Maximum: 1.4 Nm (12 in-lb)

Compression Plug Tightening Torque

Minimum:0.5 Nm (4.4 in-lb)

Maximum: 1.0 Nm (8.8 in-lb)Type Tests

Environmental Tests

Enclosure Protection:IEC 60529:2001

IP65 enclosed in panel

IP20 for terminals

Vibration Resistance:IEC 60068-2-6:1995

3 G, 10–150 Hz

IEC 60255-21-1:1988, Class 1

IEC 60255-21-3:1993, Class 2

Shock Resistance:IEC 60255-21-2:1988, Class 1

Cold:IEC 60068-2-1:1990

–40°C, 16 hours

Damp Heat, Steady State:IEC 60068-2-78:2001

40°C, 93% relative humidity, 4 days Damp Heat, Cyclic:IEC 60068-2-30:1980

25–55°C, 6 cycles, 95% relative humidity Dry Heat:IEC 60068-2-2:1993

85°C, 16 hours

Dielectric Strength and Impulse Tests

Dielectric (HIPOT):IEC 60255-5:2000

IEEE C37.90-1989

2.5 kVac on current inputs

2.0 kVac on ac voltage inputs,

contact I/O

1.0 kVac on analog output

2.83 kVdc on power supply

Impulse:IEC 60255-5:2000

0.5 J, 4.7 kV on power supply, contact

I/O, ac current and voltage inputs

0.5 J, 530 V on analog output

RFI and Interference Tests

EMC Immunity

Electrostatic Discharge

Immunity:IEC 61000-4-2:2001

Severity Level 4

8 kV contact discharge

15 kV air discharge

Radiated RF Immunity:

IEC 61000-4-3:2002, 10 V/m

IEEE C37.90.2-1995, 35 V/m

Fast Transient, Burst

Immunity:IEC 61000-4-4:2001

4 kV @ 2.

5 kHz

2 kV @ 5.0 kHz for comm. ports

Surge Immunity:

IEC 61000-4-5:2001

2 kV line-to-line

4 kV line-to-earth

Surge Withstand Capability

Immunity:IEC 60255-22-1:1988

2.5 kV common mode

2.5 kV differential mode

1 kV common mode on comm. ports

IEEE C37.90.1-2002

2.5 kV oscillatory

4 kV fast transient

Conducted RF Immunity:IEC 61000-4-6:2003, 10 Vrms

Magnetic Field Immunity:

IEC 61000-4-8:2001

1000 A/m for 3 seconds

100 A/m for 1 minute

SEL-751A Data Sheet Schweitzer Engineering Laboratories, Inc.

15

EMC Emissions

Conducted Emissions:EN 55011:1998, Class A

Radiated Emissions:EN 55011:1998, Class A

Electromagnetic Compatibility

Product Specific:EN 50263:1999

Certifications

ISO: Relay is designed and manufactured using

ISO 9001:2000 certified quality program.

UL/CSA:UL 61010-1 and C22.2 No. 61010-1

CE: CE

Mark–EMC

Directive

Low V oltage Directive

EN 61010-1:2001

EN 60947-1

EN 60947-4-1

EN 60947-5-1

Processing Specifications

AC V oltage and

Current Inputs:16 samples per power system cycle

Frequency Tracking Range:20–70 Hz

Digital Filtering:One-cycle cosine after low-pass analog

filtering. Net filtering (analog plus digital)

rejects dc and all harmonics greater than

the fundamental.

Protection and Control Processing:4 times per power system cycle

(except for math variables and analog quantities, which are processed every 100 ms)

Relay Elements

Instantaneous/Definite-Time Overcurrent (50P, 50G, 50N, 50Q) Pickup Setting Range, A secondary:

5 A models:0.50–96.00 A, 0.01 A steps

1 A models:0.10–19.20 A, 0.01 A steps

2.5 mA models:0.13–12.50 mA, 0.01 mA steps Accuracy:±5% of setting ±0.02 ? I NOM A secondary

(Steady State pickup)

Time Delay:0.00–5.00 seconds, 0.01 seconds steps Inverse Time Overcurrent (51P, 51G, 51N, 51Q)

Pickup Setting Range, A secondary:

5 A models:0.50–16.00 A, 0.01 A steps

1 A models:0.10–3.20 A, 0.01 A steps

2.5 mA models:0.13–2.00 mA, 0.01 mA steps Accuracy:±5% of setting ±0.02 ? I NOM A secondary

(Steady State pickup)

Time Dial:

US:0.50–15.00, 0.01 steps

IEC:0.05–1.00, 0.01 steps

Accuracy:±5 cycles, ±5% between 2 and 30 multiples

of pickup (within rated range of current) Undervoltage (27)

Setting Range:Off, 0.60–1.00 ? VNOM

Accuracy:±5% of setting ±2 V

NOTE: VNOM is a setting.

Overvoltage (59)

Setting Range:Off, 1.00–1.20 ? VNOM

Accuracy:±5% of setting ±2 V

Power Factor (55)

Setting Range:Off, 0.05–0.99

Accuracy:±5% of full scale for current≥0.5?INOM Frequency (81)

Setting Range:Off, 20.0–70.0

Accuracy:±0.1 Hz

Timers

Setting Range:See SEL-751A Settings Sheets

Accuracy:±0.5% of setting ±1/4 cycle

RTD Protection

Setting Range:Off, 1–250°C

Accuracy:±2°C

Metering

Accuracies are specified at 20°C, nominal frequency, ac currents within

(0.2–20.0) ? I NOM A secondary, and ac voltages within 50–250 V

secondary unless otherwise noted.

Phase Currents:±2% of reading, ±2°

3-Phase Average Current:±2% of reading

Current Imbalance (%):±2% of reading

IG (Residual Current):±3% of reading, ±2°

IN (Neutral Current):±2% of reading, ±1°

3I2 Negative-Sequence

Current:±3% of reading

System Frequency:±0.1 Hz of reading for frequencies

within20–70 Hz

Line-to-Line V oltages:±2% of reading, ±1° for voltages

within 24-264V

3-Phase Average Line-to-

Line V oltage:±2% of reading for voltages

within24–264V

Line-to-Ground V oltages:±2% of reading, ±1° for voltages

within24–264 V

3-Phase Average Line-to-

Ground V oltages:±2% of reading for voltages within24–264V V oltage Imbalance (%):±2% of reading for voltages within24–264V 3V2 Negative-Sequence

V oltage:±2% of reading for voltages within24–264V Real 3-Phase Power(kW):±5% of reading for 0.10

Power(kV AR):±5% of reading for 0.00

Power(kV A):±2% of reading

Power Factor:±2% of reading

RTD Temperatures:±2°C

Schweitzer Engineering Laboratories, Inc.SEL-751A Data Sheet

16

? 2007–2008 by Schweitzer Engineering Laboratories, Inc. All rights reserved.

All brand or product names appearing in this document are the trademark or registered trade-mark of their respective holders. No SEL trademarks may be used without written permission. SEL products appearing in this document may be covered by US and Foreign patents. Schweitzer Engineering Laboratories, Inc. reserves all rights and benefits afforded under fed-

eral and international copyright and patent laws in its products, including without limitation software, firmware, and documentation.

The information in this document is provided for informational use only and is subject to change without notice. S chweitzer Engineering Laboratories, Inc. has approved only the English language document.

This product is covered by the standard S EL 10-year warranty. For warranty details, visit https://www.sodocs.net/doc/7a13209498.html, or contact your customer service representative.

*PDS751A-01* SCHWEITZER ENGINEERING LABORATORIES 2350 NE Hopkins Court ? Pullman, WA 99163-5603 USA

Phone: +1.509.332.1890 ? Fax: +1.509.332.7990

Internet: https://www.sodocs.net/doc/7a13209498.html, ? E-mail: info@https://www.sodocs.net/doc/7a13209498.html,

SEL-751A Data Sheet Date Code 20080121 Notes

互联网管理制度

互联网管理制度 GZ/SZQ03.02-2012 1 目的和适用范围 1.1目的:规范网络内互联网使用的管理控制,在支持公司业务需求的同时提高信息化工作效率, 切实保障的信息安全。 1.2适用范围:本规定适用于全公司内所有部门和单位。 2引用 2.1《中华人民共和国计算机信息网络互联网管理暂行规定》 2.2《中华人民共和国计算机信息网络际联网管理暂行规定实施办法》 3术语 3.1 互联网:全球各种公共计算机网络连接而成的全球性网络; 3.2 各互联网应用单位:公司内各部门和单位。 4职责 4.1IT管理员职责 4.1.1负责互联网通道的建设与维护; 4.1.2负责对互联网应用情况的检查、监督; 4.1.3负责维护(开通、取消、更改)互联网应用权限; 4.1.4负责定期整理互联网开通用户信息列表并提交给公司领导审核。 4.2各互联网应用单位领导的职责 4.2.1各互联网应用单位的领导严格按本制度的规定,对本单位的互联网的应用申请进行符合性把 关; 4.2.2各互联网应用单位的领导对本单位获准使用的互联网应用管理和监督。 4.3涉及本制度的个人职责 4.3.1互联网用户,必须遵守网络安全管理和企业商密保护的相关制度规定、以及国家关于互联网 应用的法律法规; 4.3.2互联网内部应检查自身使用计算机的防病毒软件、防火墙的有效性;保证登录密码的安全 可靠,不得泄露给他人。 5管理活动的内容与办法: 5.1对互联网使用权限的管控规定 5.1.1对互联网应用需求的支持原则

5.1.1.1确保公司各种涉外业务信息系统的应用需要; 5.1.1.2充分满足企业对外联系的电子邮件通信需要; 5.1.1.3重点支持财务及营销业务的对外网上交互需要; 5.1.1.4适度满足信息查询需求,并控制总体应用规模,以减轻企业网承载的外部网络安全压力。 5.1.2互联网应用权限管理的分类规定 5.1.2.1对互联网应用权限的管控,落实至具体用户及其计算机; 5.1.2.2根据不同用户群体的岗位业务对互联网应用的不同需求,根据下表赋予相应级别的互联网资源使用权限; 5.1.2.3对的互联网资源各类应用人员,按照本制度各相关章节要求进行权限和应用管理。 5.1.3人员权限变更管理 5.1.3.1 IT管理员每季度将互联网使用者名单送人力及行政专员进行岗位符合性核对。岗位变动者如需继续使用互联网,必须重新申请; 5.1.3.2接替有上网权限岗位的员工,不能继承已有权限,必须重新申请上网权限。 5.2对互联网应用的管理规定

计算机管理使用办法

计算机管理使用办法 1、公司购买的台式计算机和便携式计算机属固定资产(办公设备)由综合办公室统一管理。 2、公司各部门按计划和需求提出使用申请,申请表由部门经理填写;如需购买由综合办公室报主管行政副总经理批准。部门计算机领用见流程图。 3、公司固定资产(办公设备)的采购由商务部负责。 4、计算机的使用申请、采购、验机、入库、付款必须按操作流程办理,操作流程如下:批准综合办公室申请商务部采购行政副总经理不批准技术开发部验机综合办公室入库财务部付款 5、公司各职能部门人员、开发部人员配备台式机;市场部、工程部配备相应的便携机或台式机(市场部各大区可根据情况配一台笔记本计算机)。 6、各部门内部根据工作需要可以进行计算机调配,调配后必须到综合办公室办理变更登记手续。 7、公司计算机的统一调配由综合办公室负责,在需要整体调配时,各部门负责人应积极配合综合办公室的工作。 8、计算机在使用过程中如发生故障,应及时通知开发部维修人员,不得擅自处理。

9、如发现计算机损坏应及时通知综合办公室,其损坏程度和是否需要外修,由开发部维修人员确定;如需外修,在综合办公室填写维修申请表按相应程序办理。 10、使用人必须按操作规程进行操作使用,并妥善保管。对计算机在使用或携带中的任何损坏和丢失盗抢,使用人负有直接责任,并将负责全部或部分赔偿。1 1、因保管不当发生丢失盗抢情况的,使用人需及时向公安机关报案,并由公安机关出据证明及使用人写明情况汇报;如不能破案返还的,使用人将按该计算机折旧价格赔偿,折旧价格由财务部依照有关规定出据;如返还后出现损坏的,按人为损坏处理。 12、因保管或使用不当致使计算机损坏,视情节分人为损坏和使用中损坏。凡人为损坏的(如磕、碰、摔和非规范操作),使用人按维修费赔偿。凡使用中损坏的可分为保修期内和保修期外。保修期内损坏的公司以教育为主,不做赔偿处理;保修期外损坏的,按计算机购买年限进行赔偿。购买一年以内的(减去保修期、含一年),按维修费的50%赔偿;购买一年以上两年以下的(减去保修期、含两年),按维修费的40%赔偿;购买两年以上三年以下的(减去保修期、含三年),按维修费的30%赔偿;购买三年以上五年以下的(减去保修期、含五年),按维修费的20%赔偿;购买五年以上年以下的(减去保修期、含年),按维修费的15%赔偿。

【精品】校企合作方案

深化校企合作工作攻坚方案 (讨论稿) 为落实《国家中长期教育改革和发展规划纲要(2010—2020年)》文件中关于“大力推行职业教育实行工学结合、校企合作、顶岗实习的人才培养模式”的精神,依据教育部《中等职业教育改革创新行动计划(2010-2012年)》之教产合作与校企一体办学推进计划,围绕职业教育服务区域经济发展的要求和河南省产业发展的新形势,我校在现有校企合作基础上,将全方位、深层次地推进校企合作,并以此为契机,深化改革,充实内涵,着力提升学校招生就业、专业教学、行业培训等方面工作水平,实现学校与企业“合作多赢"的目标,特制订如下校企合作工作攻坚方案: 一、校企合作的指导思想 以科学发展观统领工作全局,围绕中原经济区建设,面向电子信息产业、先进制造业和现代服务业领域,按照“以服务为宗旨,以就业为导向,走产学结合发展道路”的办学要求,以专业及课程建设、建立实训基地、开展技能培训与鉴定、打造“双师型”队伍、加强订单培养、优化招生就业体系等为载体,畅通校企沟通渠道,搭建校企合作平台,努力实现学校各专业与产业、企业、岗位对接,专业课程内容与职业标准对接,教学过程与生产过程对接,学历证书与职业资格证书对接,为学校人才培养提供全方位有效服务,促进学校办学水平不断提升。

二、校企合作的基本思路 立足学校现有的校企合作项目,立足中原经济区建设需求,以我校强项专业为基础,面向本省、珠三角及港澳等地区拓展定单式培养的校企合作关系;以信息产业、行业和省内知名企业为依托,坚持资源共享、优势互补、共同培养、互利共赢的原则,瞄准新设备、新工艺、新技术、新材料,选择生产设备先进、核心技术处于同行业领先水平的企业作为合作对象,创建校内外实训实习基地;积极寻求企业在资金、设备和师资的投入,积极拓展企业在职职工的培训,变招工为招生,把学校办成大企(行)业的技能型人才培养基地;积极拓展学校办学模式创新,加大引企入校、引校入企的工作力度,逐步由人才输出到产品输出,建立起校企紧密型战略合作关系。 三、校企合作的主要内容 1、人才培养模式的合作:根据企业需求,校企双方共同拟定人才培养计划和方案,并制定切实可行的教学计划和理论、实践教学大纲,学校在遵循基本教育规律的前提下,按企业的要求订单式培养人才,企业为人才培养“埋单”。 其表现形式包括:“订单式”人才培养模式、“2+1”人才培养模式、“学工交替”人才培养模式以及以产品项目为基础的全方位合作教育模式等.学校“汉恩班"、“中兴班”便是成功的例子,其特点在于

计算机和互联网使用管理制度(修订)

计算机与互联网使用管理制度 第一章总则 第一条为了全面规范公司计算机与计算机网络的管理,确保计算机与计算机网络资源的安全运行与高效运用,特制订本制度。 第二条公司计算机以及计算机网络资源的使用应限制在工作以及与工作相关的业务学习范围以内。 第三条严格遵守《计算机信息网络国际互联网安全保护管理办法》和《公众计算机信息网络安全管理规范》,不得利用互联网从事危害国家安全,泄露国家秘密等违法犯罪活动。 第四条严格遵守公司保密、公文处理、计算机与计算机网络管理等方面的各项规章制度,杜绝各种故意妨碍计算机与计算机网络安全运行与高效运用的行为。 第二章计算机与网络设备的保管 第五条公司为各部门及员工配置的计算机或计算机网络设备、计算机驱动程序等软件、外接设备、辅助设备等,由使用部门与使用人负责妥善保管,并做好防尘、防潮、防火、防雷、防盗等工作。 第六条要定期清洁电脑主机、显示器、键盘、鼠标以及相关的外接设备打印机、扫描仪等,随时清除设备周边的杂物,为设备安全、正常运行提供良好的环境,防止各种意外事故的发生。 第七条计算机原则上由专人负责操作与维护。 未经计算机使用或管理人员准许,任何人不得使用他人的计算机。财务、科研等重要岗位计算机使用人员必须设置开机密码。保密文件不得提供共享,必要时还应设置密码,并妥善保管密码,防止密码泄漏、遗失、遗忘或被他人破解。 工作人员仅限于使用自己的帐号、密码及权限,不得窃取他人帐号及密码越权访问。

第八条做好重要文件的备份。需要使用光盘备份文件时,可向公司人力行政部申请领取光盘进行刻录,刻录后的光盘由文件保管人员妥善保管,不得遗失、损毁。 第九条未经公司领导同意,本公司的软件或光盘不得随意外借,不得为外单位人员拷贝软件;外来人员不得随意使用本公司的计算机及网络设备。 第十条公司为各部门及工作人员配置的计算机或计算机网络设备、计算机驱动程序等软件、外接设备、辅助设备,以及计算机、光盘、移动硬盘等各类储存介质内的与公司有关的所有资料,均归公司所有。工作人员离职、转岗时,必须保证上述硬件、软件与资料的完好,并全部交回公司。 第十一条下班或外出超过两小时,不使用计算机时,应按照规定程序及时关闭计算机,切断电源。 第十二条对计算机及网络设备因保管不善发生损毁、应追究部门负责人与使用人的相应的责任;归个人保管的设备丢失,按相关规定予以赔偿。 第三章计算机与网络的使用 第十三条使用计算机的工作人员应具备计算机操作基本知识与基本技能。公司员工应加强计算机知识的学习,不断提高操作熟练程度。 第十四条为员工配置计算机时,人资行政部应向员工明确应用软件安装范围;严禁员工在计算机内安装游戏、购物、炒股及与办公、学习无关的软件。 第十五条公司员工使用互联网行为规范: 1、上班时间,仅限于网络办公平台以及与公司有关的信息网页,不得浏览与工 作无关的网页。 2、不得利用公司的网络办公平台发布违背事实,对公司和其它员工造成损失及 伤害的语言信息。 3、上班时间,未经许可不得使用QQ、MSN等工具从事与工作无关的聊天等活 动。 4、上班时间,不得利用公司提供的互联网从事以下活动: (1)、下载观看影视作品;

机关计算机使用管理办法

机关计算机使用管理办法 一、计算机设备及软件管理 1、计算机相关耗材管理 集团机关各部室日常计算机使用耗材,包括:墨盒、光盘等方面的购置,需先填写《购买计算机、打印机等设备及耗材申报单》交办公室,由办公室根据不同机型配置及集团整体网络系统需要提出意见,报集团领导批准后,办公室出办理通知单,由保卫物业部负责购置。 2、计算机硬件配置。 机关各部门使用计算机显示器、主机、键盘、鼠标等各类硬件需要升级或购置,需由使用部室提交购置、升级申请报办公室,由办公室根据集团整体网络需求和业务工作需要,结合计算机自身配置情况,与技术维护单位共同提出意见,报集团主管领导批准后,办公室出办理通知单,进行相应硬件设备调整或由保卫物业部购置。 3、计算机日常维修 各部门计算机、打印机等设备,维修前需填写《计算机维修申报单》交办公室,由办公室与计算机维护单位共同提出解决方案。在送修前相关部室应将硬盘中的重要数据或文件清除,确保无涉密信息。在维修过程中需更换、添加或减少硬件,经请示集团主管领导批准后,由办公室出办理通知单,计算机维护单位协助办理。 4、集团计算机、打印机、复印机等设备的财产管理统一由保卫行政部负责。各部室要配合保卫行政部做好财产确认,以及日常维护管理工作。 二、计算机病毒防治 1、在使用他人计算机软盘、光盘、移动存储等信息存储设备前,必须先进行病毒检查,确信无病毒后,方可使用。

2、集团所有计算机的软、硬件资源必须用于与集团有关的业务范围,除通过办公室找有关技术部门给各部门安装的软件、硬件,及本部门工作专业软件外,未经主管领导许可,不得加载安装任何与工作无关的软件,不得擅自改变机器的配置与系统设施。 3、严禁在集团计算机上玩电子游戏。 4、每周各部门对所使用计算机最少进行一次病毒检查,如发现计算机病毒,及时清除。 5、各部门现存笔记本电脑,需到办公室统一安装网络版杀毒软件。各部门需设一人负责本部门笔记本电脑的保管及使用,同时负责每周通过集团局域网对笔记本电脑进行杀毒及杀毒软件升级。当使用笔记本电脑上局域网时,必须先杀毒后上网。 三、计算机数据备份制度 1、在计算机数据备份前,必须对存放备份数据的物理介质(包括软盘、硬盘、光盘等)进行计算机病毒检查,确保无病毒后,方可使用。 2、为防止供电系统不可预见的断电事故,各部门必须定期把更新的计算机数据进行备份。 3、集团财务审计部、人力资源部,因其所用久其系统、网上银行系统不属集团整体网络工程范围内,故以上两个部门属电脑软件维护事宜由其部门自行解决,属硬件故障问题由办公室负责解决。 4、为确保集团办公区及华龙街饭庄安全,集团在华龙街装修时安装了视频监控系统。该系统对整个大楼13个点进行24小时监控。办公室将以月为周期向保卫物业部征求有无需保存录像事宜,如没有,该数据将删除。 四、计算机网络安全管理

公司治理和提名委员会职权范围

公司名称认证认证之认可证书编号(CC)状态暂停/撤销日期上海英达宝塑料有限公司ISO 9001:2008UKAS3234撤销14/9/2018 东莞丽适内衣有限公司SA8000:2014SAAS5845撤销8/9/2018 东莞市源康毛绒玩具有限公司SA8000:2014SAAS6229撤销26/4/2018 东莞雅隽纸品有限公司SA8000:2014SAAS6349暂停29/11/2018 中交一航局第五工程有限公司ISO 9001:2008HKCAS,UKAS6035撤销24/5/2018 中交一航局第五工程有限公司QSPSC:2014UKAS6035撤销24/5/2018 中国电信股份有限公司TL-V 6.0/5.0CNAS2861撤销28/3/2019 中国移动通信集团四川有限公司ISO 9001:20085969撤销29/4/2018 中国移动通信集团广东有限公司TL-V 5.5/5.0CNAS3117撤销1/1/2018 中国移动通信集团福建有限公司厦门分公司ISO 14001:2004CNAS3810撤销24/2/2018 中山市海荣金属制品有限公司ISO 9001:2008UKAS3312撤销20/6/2018 伟信(天津)工程咨询有限公司ISO 9001:2008CNAS5110撤销14/9/2018 佛山市高明南越钢结构制造有限公司ISO 9001:2008HKCAS6238撤销7/1/2018 佳达电子塑胶(深圳)有限公司ISO 9001:2008CNAS,HKCAS,UKAS3474撤销14/9/2018 南京智达康无线通信科技股份有限公司TL-HS 5.5/5.0CNAS5203撤销14/9/2018 厦门华润燃气有限公司OHSAS18001:20076059撤销15/2/2019 嘉实多(深圳)有限公司ISO 9001:2008CNAS,UKAS1506撤销29/6/2018 嘉实多(深圳)有限公司ISO 14001:2004CNAS,UKAS2168撤销29/6/2018 嘉实多(深圳)有限公司ISO 9001:20085982撤销29/6/2018 天津美罗钢格板有限公司ISO 9001:2015CNAS,HKCAS,UKAS5577撤销9/7/2018 奥仕达电器(深圳)有限公司ISO 14001:2004CNAS,HKCAS5518撤销14/9/2018 广东中奥物业管理有限公司ISO 9001:20085972撤销27/5/2018 广东中奥物业管理有限公司ISO 14001:20045973撤销27/5/2018 广东中奥物业管理有限公司OHSAS18001:20075974撤销27/5/2018 广东恒泰钢结构有限公司ISO 9001:2008HKCAS,UKAS6135撤销18/3/2018 广州同略信息科技有限公司SA8000:2014SAAS6092撤销17/8/2018 广州哲品家居用品有限公司SA8000:2014SAAS6547撤销22/2/2019 广州方盈珠宝首饰有限公司第一分厂SA8000:2014SAAS6329撤销10/3/2018 广州美罗钢格板有限公司ISO 9001:2008CNAS,HKCAS,UKAS1583撤销27/8/2018 广州莱佛士物业服务有限公司ISO 9001:2008CNAS,HKCAS,UKAS3845撤销29/3/2018 广州誉川兴业鞋业有限公司SA8000:2014SAAS6109撤销20/4/2018 张家港保税区舒尔玆金属贸易有限公司ISO 9001:2008UKAS5471撤销4/1/2018 惠州宏丰手袋实业有限公司SA8000:2014SAAS5278撤销4/3/2019 无锡德思普科技有限公司SA8000:2014SAAS6108撤销31/3/2019 正东钢铁结构(深圳)有限公司ISO 9001:2015CNAS,HKCAS,UKAS2531撤销28/8/2018 比优特(苏州)塑胶科技有限公司SA8000:2014SAAS6093撤销28/2/2019

互联网信息服务管理办法

互联网信息服务管理办法 (2000年9月20日国务院第31次常务会议通过,中华人民共和国国务院令第292号公布,自公布之日起施行) 第一条为了规范互联网信息服务活动,促进互联网信息服务健康有序发展,制定本办法。 第二条在中华人民共和国境内从事互联网信息服务活动,必须遵守本办法。 本办法所称互联网信息服务,是指通过互联网向上网用户提供信息的服务活动。 第三条互联网信息服务分为经营性和非经营性两类。 经营性互联网信息服务,是指通过互联网向上网用户有偿提供信息或者网页制作等服务活动。 非经营性互联网信息服务,是指通过互联网向上网用户无偿提供具有公开性、共享性信息的服务活动。 第四条国家对经营性互联网信息服务实行许可制度;对非经营性互联网信息服务实行备案制度。 未取得许可或者未履行备案手续的,不得从事互联网信息服务。 第五条从事新闻、出版、教育、医疗保健、药品和医疗器械等互联网信息服务,依照法律、行政法规以及国家有关规定须经有关主管部门审核同意的,在申请经营许可或者履行备案手续前,应当依法经有关主管部门审核同意。 第六条从事经营性互联网信息服务,除应当符合《中华人民共和国电信条例》规定的要求外,还应当具备下列条件: (一)有业务发展计划及相关技术方案; (二)有健全的网络与信息安全保障措施,包括网站安全保障措施、信息安全保密管理制度、用户信息安全管理制度; (三)服务项目属于本办法第五条规定范围的,已取得有关主管部门同意的文件。 第七条从事经营性互联网信息服务,应当向省、自治区、直辖市电信管理机构或者国务院信息产业主管部门申请办理互联网信息服务增值电信业务经营许可证(以下简称经营许可证)。 省、自治区、直辖市电信管理机构或者国务院信息产业主管部门应当自收到申请之

IInterlib区域图书馆集群管理系统用户手册

I n t e r l i b图书馆集群 管理系统 用户手册 广州图创计算机软件开发有限公司

目录 前言 ?图书馆集群管理系统Interlib的出现 ?为什幺需要区域图书馆群的联合服务 ?阅读对象 ?本手册包括的内容 ?本手册阅读指导 ?相关参考手册 ?本书约定 ?更多信息 图书馆集群管理系统Interlib的出现 传统的图书馆管理方式下,区域内各图书馆作为一个独立存在的实体,数字化文献资源信息无法做到共享,达到为全区域服务的目的,各自的独立发展将使自己成为今后数字化信息时代的一座孤岛。 从图书馆自动化系统发展历程来看,经历过单机、终端/主机阶段,局域网下客户机/服务器(C/S)阶段。C/S模式在90年代中期作为图书馆自动化系统架构的主流,一直到今天,将图书馆自动化的发展带入了新境界。C/S模式是基于局域网技术发展起来的,在Internet技术发展到今天的地步,C/S模式在伸缩性、可管理、资源共享、联合服务等方面有技术上先天的缺陷,难以实现数字资源和传统业务紧密结合以及海量数字资源的分布处理。 图书馆集群管理系统Interlib是新一代的图书馆自动化软件,采用开放的多层结构体系,基于Internet实现传统业务与海量数字资源管理的结合。Interlib作为资源共建共享的新的载体形式,打破了图书馆各自分离的局面,将区域内图书馆群作为一个整体进行管理,从而达到资源共建共享、合理配置和图书馆之间互相合作的目的。 Interlib通过Internet网络或城域网络将区域内各图书馆联合起来,组成一个区域性的虚拟图书馆群,建立一个区域图书馆群的电子化、数字化、网络化的信息空间,同时通过开放的多层结构达到与国内外其它图书馆的资源共享与协作,从真正意义上实现图书馆群的资源管理和业务协作。 Interlib系统的主要功能特点: ?100%纯Java开发产品,跨平台设计,与Internet紧密结合。 ?B/S模式多层体系结构,MVC架构。 ?Browser端完全采用XML,解决HTML的局限性,适应更新的技术发展。 ?Unicode标准,真正解决多语种混合编码问题。

公司计算机系统使用管理办法(2010-014)

计算机系统使用管理办法 为规范公司计算机和网络的管理,确保计算机以及计算机网络资源高效安全地用于工作,特制定本管理办法。 第一章硬件管理 第一条行政部是公司计算机设备的管理部门。为了更有效地管理及应用公司的计算机,行政部对公司内的所有计算机及其相关设备登记注册,其中包含每台机的配置、使用人、用途等。任何人不得私自调换以及更改计算机配置。 第二条各部门如需申请IT设备(包括:电脑、打印机、扫描仪),由申请人填写《IT事宜处理单》,经审批通过后,交IT管理员根据公司《各岗位计算机配置及分配办法》填写配置说明,行政部统一进行IT设备的划拨;如需采购,则由行政部依请购流程办理请购手续。人员离职后其使用的计算机设备应返还给行政部,设备归还前需由IT管理员对设备完好情况进行确认,行政部须对设备使用的变动情况予以登记。若人员离职后未将其计算机设备交付给行政部,行政部有权将其收回。 第三条公司员工不得滥用计算机设备,使用者有义务对其使用的计算机设备负责;对计算机硬件设备的丢失、被盗等情况,必须及时通知行政部,并依情形追究责任。 第四条公司计算机设备及相关的附属设备(如打印机、扫描仪、网络设备等)的故障须报IT管理员处理。设备使用中遇到非正常情况或困难时,由设备使用部门填写《IT事宜处理单》,注明机器编号及故障现象,通知IT管理员排查和处理,经确认需外发维修时,由IT管理员办理。除IT管理员以外其他人员不得自行拆装、修理IT设备。 第五条公司的所有计算机及相关的附属设备(如打印机、扫描仪、网络设备等)的报废由行政部填写《设备报废申请单》提出申请,经IT管理员确认后报批。 第二章软件管理 第六条公司使用的各种计算机系统及应用软件程序由IT管理员统一发布、更新和管理。系统软件的使用统一由IT管理员进行安装;应用软件的使用由需求人员于公司局域网上自行下载、安装,IT管理

华为企业人力资源研究

标杆企业人力资源研究提纲 (供参考,根据你能够收集到信息整理) 1.企业概况 1.1企业概况华为技术有限公司,简称华为,是中国一家生产销售通信设备的民营公 司,总部位于广东省深圳市。华为于1987年注册成立,产品主要涉及通信网络中的交换网络、传输网络、无线及有线固定接入网络和数据通信网络及无线终端产品,为世界各地通信运营商及专业网络拥有者提供硬件设备、软件、服务和解决方案。 华为技术有限公司是一家总部位于中国广东深圳市的生产销售电信设备的员工持股的民营科技公司,总裁任正非,董事长孙亚芳。它1988年成立的时候,是个只有两万元注册资本、20个员工,唯一的资源是人的头脑的默默无名的小公司。20世纪末,旋风一样席卷了国内市场,研发投入与回报间的漫长周期带来了巨大的风险,但他每次都能披荆斩棘,昂首阔步的走下去。可是行业的冬天给这位领军者造成了巨大的伤害,但他没有倒下去,押上命运的决心,把上亿资金、上千人员投入了新的项目。2002年,它拥有员工22000多人,2003年销售额达到317亿元。到今天,它是行业内的领军者,在国内市场占领了巨大的份额,并已经展开国际发展的征程。这个时候,世界第一的思科已紧张地盯着它的主要竞争对手。 1.2发展历程、阶段 1988年成立于深圳的华为公司是一家通讯设备供应商。其营业范围包括交换、传输、无线和数据通信类电信产品。在通讯设备领域为世界各地的客户提供网络设备、服务和解决方案。 1988-1997年,“农村包围城市”零起步的华为无论是资金还是竞争实力都无法与对手在大、中城市参与竞争。但华为公司的创始人看到:县城以及农村更广阔的市场是国外厂商尚未涉足的领域,这为华为带来了机会。华为认为:以农村为突破口有两个非常明显的好处:首先,小县城和农村发展通讯设备行业门槛低,承受风险小。其次,农村对于产品的技术和质量要求不高,也不是很关注品牌,而是更加注重实用。 1989 自主开发PBX。1992年,华为开始研发并推出农村数字交换解决方案。农村包围城市的战役正式打响。很快,华为培养起一支精良的营销队伍,成长起来一个研发团队。在1995年,公司销售额达15亿人民币。随着自有资金实力不断增强,华为发动城市战的资本逐渐积累完成。至此华为正式将市场目标转移到中国主要城市。1994 推出C&C08 数字程控交换机。 1995 成立知识产权部。成立北京研发中心。 1996 推出综合业务接入网和光网络SDH设备。与香港和记黄埔签订合同,为其提供固定网络解决方案。成立上海研发中心。

互联网使用管理办法

互联网使用管理办法 为加强我单位互联网的使用管理,防止在使用互联网过程中发生违规和泄密事件,确保信息安全,根据上级有关互联网管理的要求制定本办法。 一、计算机上互联网必须履行报批手续。 二、互联网计算机必须专机专用,严格按批准的用途使用,不得将互联网计算机作为日常办公机器使用。 三、互联网计算机必须按批准的方式接入互联网,不得私自接入路由器和无线网卡。 四、禁止在互联网计算机上处理内部敏感信息。 五、凡向互联网上提供或者发布信息,必须经单位主要领导签批同意,严格执行信息上网发布审核制度。 六、禁止一台计算机既接入互联网又接入局域网。 七、禁止将互联网的网络设备连接到局域网的网络设备上。 八、禁止互联网计算机及移动介质与局域网计算机及移动介质交叉使用。 九、互联网计算机操作人员要相对固定,人员离开时,必须关闭计算机。

十、互联网计算机应安装防病毒软件和漏洞修补工具,并及时更新。 十一、按照国家相关法规,对所有上网记录保留60天。 十二、上网不得从事以下行为: 1、禁止上班时间访问游戏、娱乐类网站,禁止玩网络游戏,禁止上班炒股; 2、禁止下载MP3,WMA,MPEG等与工作无关,占用网络带宽的音乐、电影文件; 3、禁止使用p2p、p2p streaming(网络电视)类工具 4、禁止直接下载exe、com、bat等有风险的程序,禁止访问有恶意代码的病毒网站; 5、禁止使用聊天工具、电子邮件、bbs等传递违反法律的内容; 6、利用单位互联网资源进行侵害国家安全以及谋取私利的行为; 7、浏览娱乐网站、带有色情和反动倾向的网站以及进行网上游戏; 8、故意制作或者传播计算机病毒以及其他破坏性程序的; 9、非法侵入计算机信息系统或者破坏计算机信息系统功能、数据和应用程序。 十三、违反本办法规定的纳入日常考核。

图书管理系统(结构化方法)

摘要 本文采用自顶向下的结构化的系统分析方法,阐述了一个功能全面的图书管理系统的开发过程、操作流程及其一些核心的技术。本文首先进行了项目概述,简单介绍了分析了企业的组织结构,系统开发的背景、系统开发的目的和系统开发的必要性;接下来是系统规划阶段,通过实际的业务流程调研,具体完成了图书管理系统的需求分析、可行性分析、现行业务流程分析,并通过对现行业务流程的优化,得出了系统的业务流程;之后是系统分析,具体完成了数据流分析和数据字典;系统设计阶段主要完成了功能模块的划分、数据库的设计和系统界面设计。该阶段对各个模块的功能进行了详细设计,形成了本系统的功能模块图,在此基础上选择了合适的开发模式;数据库的设计先进行了概念结构设计,之后进行了逻辑结构设计,最后完成了数据库表的设计。 根据前几个阶段的分析和设计,本系统使用C#技术进行基本页面的设计与功能实现,后台数据库选用SQL Server 2005数据库,系统在设计上采用C/S模式。本系统为图书管理提供了良好的基础。 关键词:图书管理系统结构化分析 C#

The Information System and Management of AnShan Library Abstract:In this paper, the top-down structured systems analysis methods, described the development process of a full-featured library management system, operational procedures, and some of its core technology. This article first overview of the project, a brief background of the organizational structure of the business, project development, the significance of the purpose of the project development and project development; followed by the system planning stage, through the actual process of business research, to complete a book management systems requirements analysis, feasibility analysis, analysis of existing business processes, and through optimization of existing business processes, and obtained the business processes of the system; followed by a systematic analysis of the specific data flow analysis and data dictionary; the system design phase completed the division of functional modules, database design and system interface design. Detailed design stage of the function of each module, forming a functional block diagram of this system on this basis, select the appropriate development model; database design is the first concept of structural design, followed by a logical structure design, and finally completed the design of the database table. The first few stages of analysis and design of the system using C # basic page design and function to achieve the back-end database selected SQL Server 2005 database, the system design using C / S mode. This system provides a good foundation for the library management. Keywords: Library Management system, structured analysis, C#

公司电脑安全使用管理办法

公司电脑安全使用管理办法 为提高现代化办公实效,规范公司电脑的使用管理,确保电脑以及网络资源高效安全的用于工作,特制本规定 一、公司电脑及网络资源仅为公司所配置,员工不得从事无关使用。 1.公司电脑只供本公司人员使用。 2.每天下班前应检查主机和显示器电源是否关好,下班将桌面重要资料储存至非系 统盘,严禁频繁开关或重启电脑,非特殊情况不要强行关机。 3.严禁上网浏览反动、色情、暴力以及宣传不良言行的网站,不准在任何网站散布、 发表对公司不利的言论、不得下载网络未被公认的文件,防止病毒和木马的入侵。 4.定期对电脑进行病毒扫描,以免感染病毒。 5.任何时间,在公司禁止使用BT、电驴等占用网络带宽过多的P2P软件下载文件, 禁止使用在线听歌,在线视频的软件,严禁下载与工作无关的影视文件,以免影响整体网速。 6.在平时的工作中,应养成将文件分门别类地存放在相应文件夹中的习惯,避免出 现急需某个文件时遍寻不获的情况。不要把有用的文件存放在系统盘(一般为C 盘)、“我的文档”和“桌面”。 7.员工使用网络时,必须使用分配的IP,严禁擅自修改,如有IP冲突,请与IT联 系 二、公司内部有专人负责电脑的维护、维修等各项工作,公司员工对所使用的电脑有 管理、维护责任与义务。 1.员工入职领用电脑需到IT处登记备案,IT根据其岗位性质发配合适的电脑

2.在职期间,员工未经允许,不得更改系统配置,严禁私自拆卸和装接各种硬件设 施 3.当电脑出现故障时应立即报告IT 4.员工离职,需请IT 检查,确认后方可正常离职,如有问题需追加其责任,并做 相应的赔偿 5.每周至少对电脑进行一次清理。对本机资料进行分类及整理、删除多余文件、案 例,保证硬盘容量和运行速度。 6.员工应该保持电脑周围环境的清洁,键盘、鼠标、机箱、显示器等不应堆积灰尘, 应该每日清理 三、公司电脑已全部建档立案,并进行了合理的使用定位,任何部门和个人不得私自 挪用、调换、外借和移动电脑 四、出于维护公司商业利益的需要,公司电脑中的文件未经允许禁止复制或者传送给 超出公司业务范围的人员。 五、违反电脑使用规定的个人,第一次警告并记录,第二次罚款200元,经多次屡教 不改的公司有权开除,该部门负责人负连带责任,并处罚款100元/人/次,以上罚款从当月工资中扣除。 六、对于监督有功者,经公司核实后,奖励100元/次,以奖金形式在当月工资中体 现。 七、 八、 九、(资料素材和资料部分来自网络,供参考。可复制、编制,期待你的好评与关注) 十、 十一、 十二、

H3C

华为 华为技术有限公司 Huawei Technologies Co., Ltd. 公司 类型 民营企业 成立1987年 代表人物总裁:任正非董事长:孙亚芳 总部中国深圳市龙岗区坂田华为基地 邮政 编码 518129 电话 号码 +86 755 2878-0808 标语口号丰富人们的沟通与生活(Enrich life through communication) 业务 地区 全球 产业无线电,微电子,通讯 产品接入设备,骨干路由器,无线基站和交换设备,语音视频设备 服务企业网,国家级骨干网,光纤网络设计,建设 年营 业额 ▲284亿美元(2010年)

税后 盈余 ▲36.8亿美元(2010年) 员工 人数 110,000(2010年12月) 主要部门移动、宽带、IP、光网络、电信增值业务和终端 网址https://www.sodocs.net/doc/7a13209498.html,

华为研发大楼(深圳)

大学里的H3C无线网络硬件

华为朗新科技有限责任公司(下面简称:合资公司),总部所在地北京,由朗新董事长徐长军任合资公司的董事长。合资公司立足原朗新在中国电信、中国联通市场的现有产品和应用经验,结合华为的销售与服务网络及资金优势,加大投入,进一步为中国电信和中国联通客户提供更优质的解决方案和服务,构建有竞争力的全业务融合运营支撑系统。 [编辑]员工待遇 华为员工等级分23级,一般技术工从13级开始,13级以下一般是秘书等岗位。待遇包括基本工资+奖金,部分优秀员有配股,可分红。对新人建立了导师制度,使新员工能尽快适应公司。对老员工还有在职培训。龙岗基地有可容纳3000人的百草园员工公寓群。基地内部外部都有接送巴士。 [编辑]争议 2003年时,思科控告华为窃取其路由器程式码,华为同意从市场上撤回路由器并修改程式码后,思科随后便取消控告。 2004年芝加哥贸易展上,一位华为员工因拍摄竞争对手的产品而被捕。 2007年秋,华为鼓励7000多名工作满8年的老员工辞职后再竞聘上岗,外界普遍认为是为了规避即将于2008年施行的《劳动合同法》,而华为内部人士表示这是为了企业的活力。[2] 2008年,摩托罗拉控告五位离职员工,指称他们携带商业机密,投效与华为订有经销协议的Lemko Corp.。2010年,摩托罗拉提出修正控告,向美国联邦芝加哥地方法院控告华为自2001年开始透过摩托罗拉内部员工窃取商业机密。但华为董事长任正非声明这项指控毫无根据。 2011年3月4日,华盛顿以国家安全为由阻止华为收购3Leaf公司,理由如下[3]: 1.华为总裁任正非参加中国共产党超过3分之1个世纪。 2.任正非为长期活跃的中国共产党重量级成员。 3.任正非以上校军衔离开解放军立即创建华为,资金来源不明。 4.华为创业早期合约全部为解放军控制的中资驻港企业,政府背景明显。 5.中国军方长期无偿向华为提供关键技术,华为与解放军签署多项现存长期合作项目,军方背景明显。 6.华为长期策划及从事与盗取知识产权相关的商业犯罪,商业道德败坏。 7.华为有向包括萨达姆侯赛因、伊朗、塔利班提供服务的长期历史。 8.华为在收购3Leaf以前曾经策划及参与盗取3Leaf知识产权的商业犯罪。 9.中国多家国家银行在华为成立后的24年当中向华为提供“无限制的融资”,政府背景明显。

互联网管理制度

河北..制药有限公司标准文件起草:…日期:2003/02/10 文件名称:互联网管理规定审核:.. 日期:2003/03/01 文件编码:ZR/GB/1900500批准:.. 日期:2003/03/ 主管部门:计算机中心执行日期:2003/03/ 适用范围:适用于公司计算机互联网管理。 目的:规范公司互联网用户的建设、接入、管理及使用。 责任:计算机中心、各使用部门和人员。 规定: 1互联网建设项目立项、论证。 1.1根据公司信息化建设的要求,需要建立专线、配置服务器、路由器等相关设备接入互联网,由计算机中心起草项目建议书,报技术部组织论证。 2互联网建设项目调研。 2.1经论证通过报公司总经理办公会批准的互联网建设项目由计算机中心负责项目的建设及管理。 2.2计算机中心负责工程项目的小组筹建、人员分工、工作计划、考核办法制定等工作,涉及到的部门应给予配合及支持。 2.3计算机中心负责组织项目组有关人员对建设单位进行调研、考察,组织招标确定项目建设单位工作。3合同审批及签订。 3.1在确定工程实施单位后,计算机中心负责编写合同文件,报公司主管工程项目建设副总经理、总经理审批。 3.2合同经审批后由计算机中心与建设单位签订合同,开始进行项目实施。 4互联网建设项目实施。 4.1计算机中心按照公司工程建设项目管理规定组织实施,定期向主管领导汇报项目进度。 4.2计算机中心按项目进度负责工程款的申报工作。 4.3计算机中心负责项目建设的监督、测试、技术资料收集等工作。 5互联网建设项目验收。 5.1项目建设完成后,由计算机中心报技术部组织验收。 5.2技术部组织相关部门和人员,按照合同条款和项目要求对工程项目进行验收。 5.3验收报告由参加验收工作的部门和人员填写,验收报告由技术部交公司档案室保存。 5.4工程项目建设完成后,应附有完备的技术资料和技术文档,如:系统软、硬件技术资料、软件安装盘、系统使用说明书、接线图、系统维护手册等。 5.5以上文档及资料,经验收后交由公司档案室保存或备案,资料的复印件由计算机中心保存,软盘、光盘等软件由计算机中心保存并报公司档案室备案。 6计算机网络资产办理。 6.1工程项目通过验收后计算机中心负责到有关部门办理固定资产手续。 7接入互联网申报程序。 7.1业务部门根据工作要求,需要接入互联网,须向计算机中心提交《接入互联网申请表》(见附件一),由计算机中心进行审核。 7.2符合申报条件、接入互联网不需资金投入的,由计算机中心报公司主管领导审批。 7.3公司主管领导审批同意后,计算机中心安排网络管理员直接解决,文件由计算机中心存档。 7.4业务部门接入互联网投入资金较少的(少于一万元),走网络维护费;投入资金超过一万元的,计算机中心起草项目建议书,报技术部组织论证。 8申请接入互联网(Internet网络)的部门及人员必须具备下列条件。 8.1申请接入互联网的部门及人员工作上确实需要经常从互联网上查阅、下载与工作有关的信息。

图书馆利用情况调查分析报告

XXXX校区图书馆利用情况 调查报告 1.引言 高校图书馆作为高校信息资源中心,是校园文化建设不可或缺的部分,具有文化导向、文化宣传、文化教育等重要功能。高校图书馆因其特殊地位和存在意义以及功能而成为大学综合素质测评的重要指标之一。 1.1调查背景 武汉理工大学图书馆是由原武汉工业大学图书馆、武汉交通科技大学图书馆和武汉汽车工业大学图书馆于2000年合并组建而成,是国家CALIS成员馆、CASHL成员馆、湖北省“研究级文献收藏单位”、湖北省“优秀级图书馆”,设立有教育部部级科技查新工作站。 图书馆现有工作人员179人。其中:博硕研究生20人,本科94人,大专45人,其他20人;高级职称45人,中级职称72人,其他62人。图书馆现有馆舍面积3.86万平方米,阅览座位3305个图书馆系统建立了印本文献、电子文献和网络文献“三位一体”的文献资源保障格局,形成了以材料科学与工程、船舶与海洋结构工程等一级重点学科、专业为主体的馆藏学科体系。在全国文献资源调查中,图书馆收藏的材料科学与工程、非金属采矿与选矿、汽车工程、船舶工程、航运工程、管理工程等15个学科的文献被评为研究级藏书。图书馆系统现有印本文献370余万册、电子图书160余万册、各类中外文数据库160余个,数据库包含中外文全文电子期刊3万余种。

经过“十?五”和“211工程”数字图书馆项目的建设,图书馆系统在网络硬件环境建设方面取得了重大进展。图书馆系统拥有服务器和网络设备80余台,存储容量达到50余TB,各类联网计算机800余台,建立了多校区总馆与各分馆组成的图书馆系统的千兆级光纤互联,实现了图书馆与网络中心互为容灾备份。 图书馆采用INTERLIB图书馆集成管理系统搭建我校图书馆系统统一的内部业务系统平台,实现了图书馆、学院分馆日常办公、文献信息资源建设、管理和服务的全面自动化和网络化,从而真正实现了全校文献资源的共知和共享。 图书馆在服务空间、时间和功能上不断拓展、延伸和完善。实行藏、借、阅、参、网一体化的服务管理模式,周开放时间达到92小时以上。除提供书刊借阅服务以外,还提供参考咨询、网络数据库检索、文献传递、课题检索、科技查新、定题服务、虚拟咨询等深层次和个性化服务。数字图书馆能全年365×24小时为读者提供多元化高质量的文献信息服务。 图书馆十分注重学术研究和人才队伍建设。设有湖北高校图工委主办的《高校图书情报论坛》杂志编辑部,负责该刊和《理工图苑》馆刊的编辑、出版和发行工作。图书馆系统每两年组织一次的武汉理工大学图书情报学术研讨会,编辑出版会议论文集,加强学术交流与合作。同时,图书馆十分重视人才队伍建设,加大职工业务培训力度,提高职工综合素质和服务水平。

相关主题