Hygrothermal properties of lightweight concrete:Experiments and numerical ?tting study

a r t i c l e i n f o Article history:

Received 11August 2012

Received in revised form 26October 2012Accepted 22November 2012

Available online 20December 2012Keywords:

Lightweight concrete

Heat and moisture transfer Porous building materials Energy savings

a b s t r a c t

This paper presents an experimental research work in order to obtain the main hygrothermal properties of different mixes of lightweight concrete (LWC)produced from expanded clay.Nowadays,the current state of art assumes an exponential relationship between the moisture content and the thermal proper-ties for this kind of building material.The prime novelty of this study is the experimental determination of the actual hygrothermal properties for different LWC mixes with material densities ranging from 900to 1400kg/m 3,as well as the least squares best-?tting curves in order to obtain accurate mathematical expressions that permit us to optimize the hygrothermal behavior of new construction products made up of LWC.In this way,the experimental data set is compared with those for the Standard and a new ana-lytical solution is obtained,giving place to a new analytical solution taking into account the relationship among the heat,moisture and density.Finally,the results and conclusions reached in this work are exposed.

ó2012Elsevier Ltd.All rights reserved.

1.Introduction

In recent years,many researchers have studied the thermal and mechanical properties of different materials used in buildings,such as normal weight concrete (NWC),lightweight concrete (LWC),gypsum,plaster and clay brick [1–8].

LWC has been used in many constructions due to its signi?cant bene?ts from the structural

and thermal points of view.However,more research is necessary to understand the hygrothermal behav-ior of this porous material.In order to investigate its hygrothermal performance,it is necessary to take into account the material density and its moisture sorption capacity.LWC density typically ranges from

1000to 1800kg/m 3compared with that of 2400kg/m 3for NWC.The main advantages of the LWC are the reduction in the dead weight of the structure and good thermal insulation

0950-0618/$-see front matter ó2012Elsevier Ltd.All rights reserved.https://www.sodocs.net/doc/8a950253.html,/10.1016/j.conbuildmat.2012.11.045

Corresponding author.Tel.:+34985182042;fax:+34985182433.

E-mail address:juanjo@constru.uniovi.es (J.J.del Coz Díaz).

properties due to the cellular structure of the aggregates.The main disadvantage is the porous structure of the aggregate that implies absorption of a signi?cant quantity of the mixing water.This fact has in?uence in the thermal[7,8]and mechanical[4]properties of the LWC,causing energy losses and failure cracks,respectively.

Nowadays,the LWC porous material is an important research subject in both heat and moisture transfer points of view due to its attractive characteristics,such as its thermal and acoustic good physical properties,even at high temperatures

?ts of this research have been applied to the

ef?ciency of buildings made up of lightweight

[7,11].Furthermore,the basics of the

in porous materials are interesting and

[12–15]due to their important effects on

the climate change.However,it is possible to

cent research studies have often been

numerical investigations instead of

[13,15].

The fundamental references for this

building physics and focusing on porous

their properties with respect to the heat and

The interested reader is encouraged to

search works in this?eld such as advances

[10,11,13],property measurements[9,14]

numerical models[16,17].To motivate this

huge interest in the comprehensive study of

transfer between indoor air and hygroscopic

due to changes in the indoor humidity since

phenomenon may improve air quality and

[18].In other words,it is necessary to obtain

data to accurately quantify the heat and

hygroscopic building materials and air if the

are varied in a cyclical form.Furthermore,

are also important and a prerequisite for the

that will be used in developing new building

LWC.

The main objectives of this research work include:(1)developing a new experimental procedure to obtain the hygrothermal proper-ties of the LWC,(2)studying the thermal properties as a function of the moisture content in LWCs when its density ranges from900 to1400kg/m3,(3)carrying out different least squares best-?tting curves in order to?nd an equation that de?nes the relationship among density,moisture content and thermal conductivity,and (4)proposing a new revised conversion coef?cient of thermal con-

Nomenclature

F a conversion factor of aging,dimensionless

F T conversion factor of temperature variation,dimension-

less

F m conversion factor for the moisture content,dimension-

less

F m

i conversion factor for the moisture content of the i-th set of conditions

f u conversion coef?cient of moisture content per unit

mass,kg/kg

L thickness of the specimen across which the temperature difference exists,m

LWA lightweight aggregate

LWC lightweight concrete

LWS lightweight sand

m specimen mass at equilibrium with a relative humidity, kg

m0mass of the dry specimens,kg

n number of the observed values obtained in the actual tests or‘sample size’

NWC normal weight concrete

q heat?ux,or heat?ow rate through a surface of unit area perpendicular to the direction of heat?ow,W/m2

r2coef?cient of determination

R overall thermal resistance,m2K/W R se surface thermal resistance of the specimen in the hot-box test chamber as a function of wind velocity,m2K/W

R si surface thermal resistance of the specimen in the sur-rounding area as a function of wind velocity,m2K/W

D T temperature difference between the hot-box and the

surrounding area,K

U heat transmission coef?cient or thermal transmittance, W/m2K

u moisture content per unit mass,kg/kg

u i moisture content per unit mass of the i-th set of condi-tions,kg/kg

u50%moisture content per unit mass for/=50%,kg/kg

V volume of the specimen,m3

w moisture content in volume,kg/m3

Y i observed values obtained in the actual tests

^Y

i

modeled values obtained from the?tted curve or pre-

dicted values

Y mean of the observed data

Greek symbols

/relative humidity(%)

k thermal conductivity,W/m K

k50%thermal conductivity for/=50%,W/m K

q material density,kg/m3

1.Expanded clay aggregates used in this research:LWA(left)and LWS(right).

544J.J.del Coz Díaz et al./Construction and Building Materials40(2013)543–555

Expanded clay is an arti?cial lightweight aggregate that is produced?ring nat-ural clay in a rotary kiln at the temperature about1100°C using a process called ‘‘pyroprocessing’’,which causes the material to expand.The high proportion of semi-closed pores in LWA creates a cellular pore system that supplies to these aggregates their low-particle relative density and good thermal insulated properties.

A total of six samples of0.2m width,0.2m long and0.05m thick for different mix proportions(see Table1)are tested.First of all,the specimens are built in an 2.3.Hygroscopic test methodology

The Standard ISO12571:2000has been used in this research[22].This Standard is used in this work in order to develop a new test methodology to determine the hygroscopic sorption isotherm of the LWC construction material.

A variant of the air-conditioned room method indicated in the Standard[22]for a climatic test chamber is used in this experimental setup(see Fig.4).This layout allows that the temperature inside the test chamber remains constant (23±0.5°C)as well as an increase of the relative humidity ranging from21%to95%.

The moisture content of samples is determined by weighing until to obtain a constant mass so that the equilibrium state is reached in each test.The constant mass is achieved when the mass variation between three consecutive weightings, carried out with a time separation of at least24h,becomes less than0.1%of the to-tal mass of the sample.

The hygroscopic moisture storage is described using the sorption isotherm curves of the material,termed hygroscopic curves.These curves establish the rela-tionship between the moisture content for porous media in volume,V,or per unit mass,and the relative humidity of air in equilibrium at constant temperature,/, as follows[22]:

we/T?

me/Tàm0

V

or ue/T?

me/Tàm0

m0

?

we/T

qe1T2.4.Hygrothermal test methodology

The speci?c thermal properties determined as a function of the moisture con-tent inside the LWC specimens are:the heat transmission coef?cient or thermal transmittance,the thermal resistance and the thermal conductivity.

In this way,four samples are placed on a thermal isolated frame using low ther-mal conductivity foam,located between the test lab environment and the hot-box chamber(see Fig.5).The hot-box chamber controls the relative humidity and the temperature by means of the climatic generator set so that a dominant horizontal heat?ow is achieved.

The temperature,relative humidity and heat?ow of the specimen sides are measured to determine the thermal properties of the samples in each test at steady state conditions.For each specimen,?ve hygrothermal SHT75capacitive sensors and one HFP01heat?ux sensor are used(see Fig.5a–c).Three hygrothermal sensors are placed on the inner side of the sample(see Fig.5d),and the other two sensors on the external side(see Fig.5e).These sensors are protected with?lter caps type SF1

Table1

Mix proportions of the LWC samples.

Composition SAMPLE LWA a

(kg)

LWS a

(kg)

Silica sand

(kg)

Cement

(kg)

Water

(kg)

1A0.840.720.480.4950.36

1B0.840.720.480.4950.36

2A0.780.720.6750.540.36

2B0.780.720.6750.540.36

3A0.840 2.40.540.39

3B0.840 2.40.540.39

a Note:LWA:4–12.5mm particle diameter,and LWS:1–5mm particle diameter.

Table2

Densities of the LWC determined in this investigation during the manufacturing process.

Sample Fresh density

(kg/m3)Oven dry density

(kg/m3)

Equilibrium density

(kg/m3)

1A1027953973

1B992948971

2A1055979999

2B105810011026

3A146013531373

3B146013381362

Fig.2.Scheme of the experimental facility layout.

J.J.del Coz Díaz et al./Construction and Building Materials40(2013)543–555545

where the value used for the surface thermal resistance of the specimen inside and outside the hot-box test chamber as a function of wind velocity is0.04m2K/W.

2.5.Tests conditions

The test conditions of the experimental tests are:

Number of samples:six.

Test environment conditions tested:11. Volume of each sample:0.003m3.

Precision weighing balance’s accuracy(for hygroscopic tests):±0.1g,10kg is the maximum weight allowed.

Laboratory conditions:23±1°C of temperature and48±2.5%of relative humidity.

Experimental setup:climatic chamber described in Section2.3,based on the Standards[20–22]using the hot-box apparatus.

Test site:Moisture Laboratory at High Polytechnic Engineering College of Gijón (University of Oviedo,Principality of Asturias,Northern Spain).

Fig.3.Photographs of the climatic chamber(left)and hot-box apparatus(right).

Experimental setup(left)and specimens located inside the hot-box test chamber(right)for hygroscopic

test setup:(a)a?lter cap type SF1,(b)a hygrothermal sensor type SHT75,(c)a thermal?ux sensor type HP01,(d)specimens with side,and(e)specimens with hygrothermal and thermal?ux sensors on the external side.

3.Experimental results

The experimental results for the different mixes of LWC studied in this research work are follows as:

Hygroscopic sorption isotherm (see Eq.(1)),used to describe the equilibrium moisture content of the material at a speci?ed constant temperature [22].

Hygrothermal conductivity or thermal conductivity for different moisture contents (see Eqs.(2)–(4)).3.1.Hygroscopic sorption tests and results

The experimental setup described previously is able to test the hygroscopic properties of several specimens at the same time (see

The sorption isotherms of the samples obtained in the tests (see Figs.7–9)and the moisture content per unit mass (see Table 3)show clearly that the moisture absorption is increased in the samples if their density is decreased.3.2.Hygrothermal conductivity tests

The experimental measurement of the LWC hygrothermal prop-erties is performed by means of the same experimental device (see Fig.5d and e).Speci?cally,four specimens are located on a thermal isolated frame at the open front side of the hot-box apparatus.The temperature differences between the internal and external sides of the specimens located at the hot-box are greater than 15°C in all the tests.This value is recommended by the Standards [20,21]for these thermal tests.The results obtained for the sam-ples checked are shown in Fig.10.Additionally,Table 4shows only the experimental LWC thermal properties for a speci?c relative humidity equal to 50%.

Fig.11shows a set of thermal photographs of some specimens checked using the infrared thermographic camera ThermaCAM E300from FLYR Systems Ltd.It is interesting to observe the evolu-tion of the temperature on the cold side (outer face of the hot-box)for some samples as a function of the relative humidity inside the test chamber.In all cases,the temperature inside the hot-box is equal to 55°C.

Taking into account the results of the tests carried out,the fol-lowing ?ndings for the hygrothermal properties test of the LWC mixes are:

The hot-box test chamber provides a stable test environment in order to determine the thermal properties of building elements. The laboratory values of the thermal properties belong to the usual range for this LWC material,achieving similar results on specimens of the same type (see Table 4).

6.Data acquisition system from temperature and humidity sensors type SHT75.

Fig.7.Sorption isotherms of the LWC samples type 1.

Building Materials 40(2013)543–555547

LWC material,it is necessary to calculate the?tted curves from the previous experimental results.

In this sense,the goodness of the?tted curves compared to the observed values is performed using the coef?cient of determina-tion as a signi?cant statistic[24,25]:

r2?P n

i?1

eY ià^Y iT2

P

i?1

eY ià YT

e5T

In science and engineering it is often the case that an experi-ment produces a set of data points(x1,y1),...,(x n,y n),where the

abscissas f x k g n

k?1are distinct.One goal of numerical methods is

to determine a formula y=f(x)that relates these variables.There

are several different possibilities for the type of function that can

be https://www.sodocs.net/doc/8a950253.html,ually,a class of allowable formulas is chosen and then

the coef?cients must be determined.Often there are underlying

mathematical models,based on the physical process that will

determine the form of the function[25,26].This is our case in this

research work.

Suppose that we want to?t a nonlinear curve to data points.

The original points(x1,y1),...,(x n,y n)in the xy-plane are trans-

formed into the points(X1,Y1),...,(X n,Y n)in the XY-plane.The pro-

cess that permits to transform a nonlinear?tted curve into a linear

?tted curve applying a mathematical transformation in both sides Fig.8.Sorption isotherms of the LWC samples type2.

Fig.9.Sorption isotherms of the LWC samples type3.

Table3

Experimental results of the LWC moisture content per unit mass(kg/kg)for the relative humidity(%)points tested.

LWC type/(%)

10152235506575808595

10.01110.01340.01500.01650.01790.01940.02090.02250.02380.0251

20.01020.01270.01470.01610.01760.01950.02090.02240.02370.0250

30.00690.00860.00990.01100.01190.01310.01380.01480.01580.0166

of the equation and introducing a change of variables giving place to a linear relation is called data linearization .Finally,the least-squares line is determined minimizing the root-mean-square error,that is to say,solving a linear system known as the Gaussian normal equations .

Next,the ?tted curves of several theoretical models have been carried out according to the following steps:

1.Transformations for data linearization of the functions for sev-eral nonlinear theoretical models.Once the curve has been cho-sen,a suitable transformation of the variables must be found so that a linear relation is obtained.

2.Finding the best ?tted curve with least squares ?tting technique using the MATLAB software [26].

3.Re?nement of the previous best-?t parameters using a quasi-Newton method.A signi?cant weakness of Newton’s method for solving systems of nonlinear equations is that,for each iter-ation,a Jacobian matrix must be computed and a n ?n linear system solved that involved this matrix.In this work,a general-ization of the Secant method to systems of nonlinear equations known as Broyden’s method [25]is considered.This method replaces the Jacobian matrix in Newton’s method with an approximate matrix for each iteration.

4.1.Hygroscopic ?tted curves

In order to obtain the hygroscopic ?tted curves,the three most well-known theoretical models to represent the sorption iso-therms curves are used:

The Kunzel model [27,28]:This model is used by the WUFI moisture transport simulation software,developed at the Fraunhofer-Institut für Bauphysik of Stuttgart.Its mathematical expression is:

w e/T?w lim

eb à1Tá/e6T

where w lim and b are the coef?cients of the ?tted curve.

The Kumaran model:The catalogue of material properties pub-lished in the Annex 14of the International Energy Agency (IEA)[29,30],proposes the following function:

w e/;a ;b ;c T?

/a /2

tb /tc

e7T

where a ,b and c are the coef?cients of the ?tted curve.

The Burch model:It was developed by the United States Depart-ment of Energy for the MOIST simulation program [31,32]as follows:

w e/;A ;B T?A

1

à1 B

e8T

where A and B are the coef?cients of the ?tted curve.

In order to ?t the experimental data of hygroscopic sorption tests,the functions of the above mentioned theoretical models are used.The values of the coef?cients obtained in each of the ?t-ted curves are shown in Table 5(see Figs.12–15).

Next,the goodness of ?t in each of the curves can be observed in Fig.15.

From the results shown in Figs.12–15,it is obtained the follow-ing ?ndings:

The coef?cient of determination indicates that the ?tted curves to the theoretical models developed for the IEA (Kumaran model)and the MOIST program [31,32](Burch model)are the most appropriate to reproduce the hygroscopic behavior of the tested LWCs.Speci?cally,the ?tted function developed by Burch is a bit better than the Kumaran

model.

Fig.10.Thermal conductivity (k )versus relative humidity (/)curves for the three different mixtures of LWC.

Table 4

Experimental results of the LWC thermal properties for a relative humidity equal to 50%.Sample Density (kg/m 3)q (W/m 2)T (K)U (W/m 2K)R (m 2K/W)k (W/m K)/(%)1A 97396.35719.647 4.9040.2840.176501B 97195.83920.058 4.7780.2890.173502A 99993.31917.598 5.3030.2690.186502B 102694.53317.549 5.3870.2660.188503A 1373115.26013.0758.8150.1930.258503B

1362

114.068

13.142

8.680

0.195

0.256

50

The function developed by Kunzel for the WUFI program [27,28]is the worst-?tting curve and it does not ful?ll the requirements of the minimum required goodness.

Therefore,in the hygrothermal ?tted curves we will use the Burch model to obtain the moisture content per unit mass as a function of relative humidity for each type of LWC tested.4.2.Hygrothermal ?tted curves and response surface

The conversion of thermal values from a set of conditions ek 1Tto another set of conditions ek 2Tis carried out in accordance with the following expression [19]:

k 2?k 1áF T áF m áF a e9T

In this case,it is assumed that there is no in?uence of the aging (F a =1)and the temperature variation (F T =1).The Standard rule UNE-EN ISO 10456[19]establishes a conversion factor,F m i ;for the moisture content as a function of the moisture content per unit

mass for the i -th set of conditions,u i ,through the conversion coef-?cient,f u .In this investigation,we have determined u as a

function

Fig.11.Thermal photographs of three samples for different relative humidities:10%(left),50%(middle)and 80%(right).

Table 5

Coef?cients of the ?tted curves for the hygroscopic tests.

Kunzel model (WUFI)

Kumaran model (IEA)

Burch model (MOIST)LWC type 1w lim 23.9438a

à0.04039605A 17.6040545b à0.22b 0.0743672B

0.16239767

c 0.00134979LWC type 2w lim 24.8773a à0.03632732A 17.9412727b à0.25b 0.06867017B 0.16754437

c 0.00222107LWC type 3w lim 21.8496a à0.03991617A 15.9342307b à0.23

b 0.0769837B 0.16351604

c

0.0023988

Fig.12.Hygroscopic?tted curves for the LWC type1. Fig.13.Hygroscopic?tted curves for the LWC type2. Fig.14.Hygroscopic?tted curves for the LWC type3.

Fig.15.The goodness of?t as a function of the coef?cient of determination(r2)for the hygroscopic tests.

Fig.16.Fitted curves corresponding to the thermal conductivity as a function of the relative humidity for the LWC Type1. Fig.17.Fitted curves corresponding to the thermal conductivity as a function of the relative humidity for the LWC Type2.

of the relative humidity using the Burch model as it is indicated in the previous Section4.1,giving place to the following equation for the conversion factor[19]:

F m

i

e/T?e f ueu ie/Tàu50%Te10TUntil now,Table A.20in Annex A of the Standard rule UNE-EN ISO10456[19]takes a conversion coef?cient f u=4with a moisture content per unit mass ranging from0to0.25kg/kg,in case of that the expanded clay is used as main aggregate.

ke/T?aá/3tbá/2tcá/tde13Twhere a,b and c are the coef?cients of the?tted curve.

4.A logistic function for the conversion coef?cient f u=4(logistic

plus Standard):

ke/T?Aák50%á

1tmáeà/B

1tnáeà/

e14Twhere A and B are the coef?cients of the?tted curve.

Fig.18.Fitted curves corresponding to the thermal conductivity as a function of the relative humidity for the LWC Type3.

Fig.19.The goodness of?t as a function of the coef?cient of determination(r2)for the hygrothermal tests.

J.J.del Coz Díaz et al./Construction and Building Materials40(2013)543–555553

k eq ;/T?s eq Ták 50%eq TáF m eq ;/Tá

1tm eq Táe à/=r eq T1tn ep Táe à/=r eq T

e15T

As might be observed in Fig.20,the thermal conductivity surface grows if the relative humidity and the material density are increased according to the previous results [7,11].

Table 6shows the speci?c values of the LWC thermal conduc-tivity as a function of the most representative values of the

density with respect to the relative humidity within the range studied.5.Conclusions

Based on the experimental results and numerical ?tting study of this investigation,the following ?ndings can be

drawn:

specimens made up of the expanded clay (main aggregate)corresponding to the ?tted curve according to the Standard Table 6

Values of the LWC thermal conductivity as a function of the most representative values of the density with respect to the relative humidity.Standard +logistic q (kg/m 3)

/(%)90095010001050110011501200125013001350140000.1360.1540.1710.1850.1990.2110.2210.2300.2370.2430.24750.1370.1550.1710.1860.1990.2110.2220.2310.2380.2440.248100.1370.1550.1720.1870.2000.2120.2230.2310.2390.2440.249150.1380.1560.1720.1870.2010.2130.2230.2320.2400.2450.250200.1380.1560.1730.1880.2020.2140.2240.2330.2410.2460.251250.1390.1570.1740.1890.2030.2150.2250.2340.2420.2470.252300.1400.1580.1750.1900.2040.2160.2270.2360.2430.2490.253350.1400.1590.1760.1910.2050.2170.2280.2370.2440.2500.254400.1420.1600.1770.1930.2070.2190.2300.2390.2460.2520.256450.1430.1620.1790.1950.2090.2210.2320.2410.2480.2540.258500.1450.1640.1810.1970.2110.2240.2340.2430.2510.2560.260550.1470.1670.1840.2000.2150.2270.2380.2470.2540.2600.264600.1500.1700.1880.2050.2190.2320.2430.2510.2590.2640.268650.1550.1760.1940.2110.2260.2380.2490.2580.2650.2700.273700.1610.1830.2020.2190.2340.2470.2580.2670.2730.2780.281750.1700.1930.2130.2310.2470.2600.2700.2780.2850.2890.291800.1820.2070.2280.2470.2630.2760.2870.2950.3000.3030.304850.1980.2240.2480.2680.2850.2980.3090.3160.3210.3220.322900.2170.2460.2720.2940.3120.3260.3360.3430.3470.3470.345950.2400.2720.2990.3230.3430.3580.3690.3760.3790.3780.374100

0.263

0.298

0.329

0.355

0.377

0.394

0.406

0.413

0.415

0.414

0.408

1.A new experimental procedure for the calculation of the hygro-

scopic sorption isotherm curves based on the Standard UNE-EN ISO12571:2000[22]was developed,and it was applied to the study of the hygroscopic properties of three different LWC mixes with success.

2.We have compared the experimental results with the theoreti-

cal models developed by Kumaran,Burch and Kunzel[27–32] and we have calculated the best?tting parameters in each one of them.As a consequence,it is shown that the Burch model is the most suitable to reproduce the actual hygroscopic behav-ior of the LWCs tested.

3.A new testing methodology was built to obtain the hygrother-

mal properties based on the Standards UNE-EN ISO8990and ASTM C1363[20,21],and it was applied to the study of the hygrothermal behavior of three different LWC mixes.

4.From the hygrothermal tests,the best-?tting curves based on

analytical functions and the Standard rule UNE-EN ISO10456

[19]have been obtained.It is possible to state that the values

of the conversion coef?cients used in the Standard rule in case of expanded clay as the main aggregate of the LWC material must be updated according to our laboratory tests.

Finally,this research work proposes for all the LWC mixes,with densities between900and1400kg/m3and moisture content rang-ing from0to0.25kg/kg,a change of the Standard rule’s conversion coef?cients from4to16(see Table A.20.of the Standard[19]). Other two feasible possibilities are:

A logistic function with a conversion coef?cient f u=4.This?t-

ted curve shows a hygrothermal behavior in agreement with the laboratory tests.

A cubic function also presents a good?t from the hygrothermal

point of view according to the laboratory tests.

Acknowledgements

The authors wish to acknowledge the partial?nancial support provided by Spanish Ministry of Science and Innovation through the Research Projects BIA2008-00058,BIA2012-31609,and the support provided by the Research Project FICYT PC-10-33and the Gijon City Council research fellowship SV-12-GIJON-1.We also thank the GICONSIME Research Group,the Department of Con-struction at University of Oviedo and the WEBER-MAXIT Group. English grammar and spelling of this manuscript have been revised by a native person.

References

[1]Carmeliet J,Roels S.Determination of the moisture capacity of porous building

materials.J Build Phys2002;25:209–37.

[2]Bouchair A.Steady state theoretical model of?red clay hollow bricks for

enhanced external wall thermal insulation.Build Environ 2008;43(10):1603–18.

[3]Sandberg I.Effects of moisture on the thermal performance of insulating

materials.In:Trechsel HR,Bomberg MT,editors.Moisture control in buildings: the key factor in mold prevention.2nd ed.New York;2009.

[4]Shannag MJ.Characteristics of lightweight concrete containing mineral

admixtures.Constr Build Mater2011;25:658–62.

[5]Li LP,Wu ZG,He YL,Lauriat G,Tao WQ.Optimization of the con?guration of

290?140?90hollow clay bricks with3-D numerical simulation by?nite volume method.Energy Build2008;40(10):1790–8.

[6]Cui HZ,Yiu Lo T,Ali Memon S,Xu W.Effect of lightweight aggregates on the

mechanical properties and brittleness of lightweight aggregate concrete.

Constr Build Mater2012;35:149–58.

[7]del Coz Diaz JJ,Garcia Nieto PJ,Dominguez Hernandez J,Suarez Sanchez A.

Thermal design optimization of lightweight concrete blocks for internal one-way spanning slabs?oors by FEM.Energy Build2009;41(12):1276–87.

[8]Yasar E,Erdogan Y.Strength and thermal conductivity in lightweight building

materials.Bull Eng Geol Environ2008;67(4):513–9.

[9]Othuman MA,Wang YC.Elevated-temperature thermal properties of

lightweight foamed concrete.Constr Build Mater2011;25(2):705–16.

[10]Al-Sibahy A,Edwards R.Thermal behaviour of novel lightweight concrete at

ambient and elevated temperatures:experimental,modelling and parametric studies.Constr Build Mater2012;31:174–87.

[11]Gawin D,Kosny J,Desjarlais A.Effect of moisture on thermal performance and

energy ef?ciency of buildings with lightweight concrete walls.In:Proceedings ACEEE summer study on energy ef?ciency in buildings,vol.3;2000.pp.3149–160..

[12]Qin M,A?t-Mokhtar A,Belarbi R.Two-dimensional hygrothermal transfer in

porous building materials.Appl Therm Eng2010;30(16):2555–62.

[13]Lu X.Modelling of heat and moisture transfer in buildings I.Model program.

Energy Build2002;34:1033–43.

[14]Talukdar P,Olutmayin SO,Osanyintola OF,Simonson CJ.An experimental data

set for benchmarking1-D,transient heat and moisture transfer models of hygroscopic building materials.Part I:experimental facility and material property data.Int J Heat Mass Transfer2007;50(23–24):4527–39.

[15]Kreith F,Bohn MS.Principles of heat transfer.New York:Thomson-

Engineering;2000.

[16]Abahri K,Belarbi R,Trabelsi A.Contribution to analytical and numerical study

of combined heat and moisture transfers in porous building materials.Build Environ2011;46(7):1354–60.

[17]del Coz Díaz JJ,Lozano Martínez-Luengas A,Adam JM,Rodríguez AM.Non-

linear hygrothermal failure analysis of an external clay brick wall by FEM–a case study.Constr Build Mater2011;25(12):4454–64.

[18]dos Santos GH,Mendes N.Heat,air and moisture transfer through hollow

porous blocks.Int J Heat Mass Transfer2009;52(9–10):2390–8.

[19]UNE-EN ISO10456:1999.Building materials and products.Procedures for

determining declared and design thermal values.(ISO10456:1999).

[20]ASTM C1363-97.Standard test method for the thermal performance of

building assemblies by means of a Hot Box apparatus.

[21]UNE-EN ISO8990:1997.Thermal insulation.Determination of steady-state

thermal transmission properties.Calibrated and guarded hot-box(ISO 8990:1994).

[22]ISO12571:2000Standard.Hygrothermal performance of building materials

and products.Determination of hygroscopic sorption properties.

[23]UNE-EN ISO7345:1996.Thermal insulation.Physical quantities.(ISO

7345:1987)

[24]Fox J.Applied regression analysis and generalized linear models.London:Sage

Publications;2008.

[25]Dunesche P,Remillard B.Statistical modeling and analysis for complex data

problems.New York:Springer;2010.

[26]Chapman SJ.Essentials of MATLAB programming.Stamford(USA):CL-

Engineering;2008.

[27]Künzel HM.Simultaneous heat and moisture transport in building

components,one-and two-dimensional calculation using simple parameters.Stuttgart(Germany):PhD dissertation,IRB-Verlag Fraunhofer-Institut für,Bauphysik;1995.

[28]Krus M.Moisture transport and storage coef?cients of porous mineral building

materials.Theoretical principles and new test methods.Stuttgart(Germany).

Internal report,Fraunhofer IRB Verlag;1996.

[29]Kumaran KM.Heat,air and moisture transport in envelope parts.Final report.

Task3material properties.Leuven.Internal report,IEA.ECBCS;1996.

[30]Kumaran KM.Moisture control in buildings.In:Heinz R.ASTM Manual Series,

Trechsel editorial series;1994.

[31]Burch DM,Thomas WC,Fanney AH.Water vapor permeability measurements

of common building materials.ASHRAE Trans1992;2(98).

[32]Burch DM,Chi J.MOIST.A PC program for predicting heat and moisture

transfer in building envelopes.NIST Special Publication917.Gaithersburg, MD:National Institute of Standards and Technology;1997.

J.J.del Coz Díaz et al./Construction and Building Materials40(2013)543–555555

操作系统文件管理_答案

第六部分文件管理 1、文件系统的主要目的就是( )。 A、实现对文件的按名存取 B、实现虚拟存储 C、提供外存的读写速度 D、用于存储系统文件 2、文件系统就是指( )。 A、文件的集合 B、文件的目录集合 C、实现文件管理的一组软件 D、文件、管理文件的软件及数据结构的总体 3、文件管理实际上就是管理( )。 A、主存空间 B、辅助存储空间 C、逻辑地址空间 D、物理地址空间 4、下列文件的物理结构中,不利于文件长度动态增长的文件物理结构就是( )。 A、顺序文件 B、链接文件 C、索引文件 D、系统文件 5、下列描述不就是文件系统功能的就是( )。 A、建立文件目录 B、提供一组文件操作 C、实现对磁盘的驱动调度 D、实现从逻辑文件到物理文件间的转换 6、文件系统在创建一个文件时,为它建立一个( )。 A、文件目录 B、目录文件 C、逻辑结构 D、逻辑空间 7、索引式(随机)文件组织的一个主要优点就是( )。 A、不需要链接指针 B、能实现物理块的动态分配 C、回收实现比较简单 D、用户存取方便 8、面向用户的文件组织机构属于( )。 A、虚拟结构 B、实际结构 C、逻辑结构 D、物理结构 9、按文件用途来分,编译程序就是( )。 A、用户文件 B、档案文件 C、系统文件 D、库文件 10、将信息加工形成具有保留价值的文件就是( )。 A、库文件 B、档案文件 C、系统文件 D、临时文件 11、文件目录的主要作用就是( )。 A、按名存取 B、提高速度 C、节省空间 D、提高外存利用率 12、如果文件系统中有两个文件重名,不应采用( )。 A、一级目录结构 B、树型目录结构 C、二级目录结构 D、A与C 13、文件系统采用树型目录结构后,对于不同用户的文件,其文件名( )。 A、应该相同 B、应该不同 C、可以不同,也可以相同 D、受系统约束 14、文件系统采用二级文件目录可以( )。 A、缩短访问存储器的时间 B、实现文件共享 C、节省内存空间 D、解决不同用户间的文件命名冲突

智能化系统建设方案

精品文档 一.背景描述: 江南海岸总体规划和设计均体现了传统中国居家理想和现代生 活方式的有机融合,是依照21世纪人居标准精心打造的高级住宅小区。 整个小区无不营造一个舒适休闲的生活空间,是一所环境优雅,闹中 取静的花园式住宅小区,满足住户对高品质生活的追求。 二.工程说明: 江南海岸位于三明市列东区,由14栋高层住宅小区组成,总建 筑面积29.7627万平方米,其中包括4栋27层,6栋25层,4栋29 层,会所1间,负一层,一层。住户总数为1182户。 项目要求: 江南海岸,是集住宅、花园、会所于一体的高级住宅小区。小区智能化系统的工程建设具有投资大、工程复杂、专业性强等特点。小区要求建设成具有国内先进水平的,既具有自身特点,又具有时代潮流特色的高尚住宅楼宇。 整个工程规划、设计、实施上要求充分体现技术的先进性、系统的复杂性、严密的安防集控管理。注重整体功能强大,中心设备完善,系统配置科学合 理,真正体现高技术、高标准、高水平的现代化智能小区。 四.需求分析: 4.1分析与评估:

本方案以江南海岸小区住宅智能化管理及安全防范为设计目标为将力求建设成为高水平、高质量、高标准的信息化智能小区。我方提出以下见解,请发包方领导参考。 ①小区建设要求基于系统可靠、稳定、先进的基础上,既能满足用户住宅 的实际需求,同时又力求经济、实用、合理。 ②整个系统的结构要求清晰合理,小区实现全封闭管理,各个子系统既 相互关联又相对独立,形成一个全方位智能安防管理系统。 ③要求考虑未来系统扩展的需求,为小区以后系统功能的增加、升级,提 供良好的环境空间。 因此,考虑江南海岸属于大型的综合住宅小区,建筑规模庞大、结构复杂,小区各项功能模块齐备,因此在智能化建设方面,产品的集成度、统一化、高效管理方面尤为重要,同时,还必须考虑小区规模的不断扩大,智能化产品必须具备高度的扩展及冗余,顺应小区的发展。 我方进行多项分析与评估,结合小区建筑结构的分布特点、规模发展,以及对小区各功能模块的深层了解,建议江南海岸智能化系统工

linux下各目录作用和功能

/bin:是binary的缩写,这个目录是对Unix系统习惯的沿袭,存放着使用者最经常使用的命令。如:ls,cp,cat等。 /boot:这里存放的是启动Linux时使用的一些核心文档。 /dev:是device的缩写.这个目录下是任何Linux的外部设备,其功能类似Dos下的.sys 和Win下的.vxd。在Linux中设备和文档是用同种方法访问的。例如:/dev/hda代表第一个物理IDE硬盘。 /etc:这个目录用来存放任何的系统管理所需要的配置文档和子目录。 /home:用户主目录,比如说有个用户叫sina,那他的主目录就是/home/sina,说到这里打个岔.您现在应该明白,在我们访问一些个人网页。如:https://www.sodocs.net/doc/8a950253.html,/sina的时候,sina就是表示访问 https://www.sodocs.net/doc/8a950253.html, 站点中的用户sina的用户主目录.假如这个网站的操作系统是Linux,那就是表示/home/sina。 /lib:这个目录里存放着系统最基本的动态链接共享库,其作用类似于Windows里的.dll文档。几乎任何的应用程式都需要用到这些共享库。 /lost+found:这个目录平时是空的,当系统不正常关机后,这里就成了一些无家可归的文档的避难所。对了,有点类似于Dos下的.chk文档。 /mnt:这个目录是空的,系统提供这个目录是让用户临时挂载别的文档系统。 /proc:这个目录是个虚拟的目录,他是系统内存的映射,我们能够通过直接访问这个目录来获取系统信息。也就是说,这个目录的内容不在硬盘上而是在内存里啊。 /root:系统管理员,也叫终极权限者的用户主目录。当然系统的拥有者,总要有些特权啊。/sbin:s就是Super User的意思,也就是说这里存放的是一些系统管理员使用的系统管理程式。 /tmp:这个目录不用说,一定是用来存放一些临时文档的地方了。 /usr:这是个最庞大的目录,我们要用到的很多应用程式和文档几乎都存放在这个目录了。具体来说: /usr/X11R6:存放X-Windows的目录。 /usr/bin:存放着许多应用程式. /usr/sbin:给终极用户使用的一些管理程式就放在这. /usr/doc:这就是Linux文档的大本营. /usr/include:Linux下研发和编译应用程式需要的头文档在这里找. /usr/lib:存放一些常用的动态链接共享库和静态档案库. /usr/local:这是提供给一般用户的/usr目录,在这安装软件最适合. /usr/man:是帮助文档目录. /usr/src:Linux开放的源代码,就存在这个目录,爱好者们别放过哦! /var:这个目录中存放着那些不断在扩充着的东西,为了保持/usr的相对稳定,那些经常被修改的目录能够放在这个目录下,实际上许多系统管理员都是这样干的.顺便说一下,系统的日志文档就在/var/log目录中. /usr/local/bin 本地增加的命令 /usr/local/lib 本地增加的库根文件系统 通常情况下,根文件系统所占空间一般应该比较小,因为其中的绝大部分文件都不需要, 经常改动,而且包括严格的文件和一个小的不经常改变的文件系统不容易损坏。 除了可能的一个叫/ v m l i n u z标准的系统引导映像之外,根目录一般不含任何文件。所有其他文件在根文件系统的子目录中。

告诉你C盘里面每个文件夹是什么作用

Documents and Settings是什么文件? 答案: 是系统用户设置文件夹,包括各个用户的文档、收藏夹、上网浏览信息、配置文件等。补:这里面的东西不要随便删除,这保存着所有用户的文档和账户设置,如果删除就会重新启动不能登陆的情况,尤其是里面的default user、all users、administrator和以你当前登陆用户名的文件夹。 Favorites是什么文件? 答案: 是收藏夹,存放你喜欢的网址。可以在其中放网址快捷方式和文件夹快捷方式,可以新建类别(文件夹)。 Program Files是什么文件? 答案: 应用软件文件夹装软件的默认路径一般是这里!当然里面也有些系统自身的一些应用程序Common Files是什么文件? 答案: Common Files. 这个文件夹中包含了应用程序用来共享的文件,很重要,不能乱删除Co mmon Files这个文件是操作系统包扩系统程序和应用程序Common Files是应用程序运行库文件数据库覆盖了大约1000多个最流行的应用程序的插件,补丁等等文件夹com mon files里很多都是系统文件,不能随意删除,除非确定知道是干什么用的,没用的可以删掉。不过就算删掉了有用的东西,也没大的关系,顶多是某些软件用不了,不会造成系统崩溃。 ComPlus Applications是什么文件? 答案: ComPlus Applications:微软COM+ 组件使用的文件夹,删除后可能引起COM+ 组件不能运行 DIFX是什么文件? 答案: 不可以删除,已有的XML数据索引方法从实现思想上可分为两类:结构归纳法和节点定位法.这两种方法都存在一定的问题,结构归纳法的缺点是索引规模较大而且难以有效支持较复杂的查询,而节点定位法的主要缺点是容易形成过多的连接操作.针对这些问题,提出了一种新的动态的XML索引体系DifX,它扩展了已有的动态索引方法,采用一种动态的Bisimil arity的概念,可以根据实际查询需求以及最优化的要求动态决定索引中保存的结构信息,以实现对各种形式的查询最有效的支持.实验结果证明DifX是一种有效而且高效的XML索引方法,其可以获得比已有的XML索引方法更高的查询执行效率. Internet Explorer是什么文件? 答案: 不用说了,肯定不能删除,IE,浏览网页的! Kaspersky Lab是什么文件? 答案:卡巴斯基的文件包,这个是卡巴的报告,在C:\Documents and Settings\All Users\Application Data\Kaspersky Lab\AVP6\Report 的更新文件中有很多repor t文件很占地

智能化系统配置项目及要求

智能化系统初步配置方案 一、设计原则 1、智能化系统设计,应综合考虑项目投资额度的可控性、设备选型的灵活性、工程施工的可行性、系统功能的可扩展性、系统运行维护的便利性和物业管理 的规范性等要求。 2、智能化系统的设计应参照本要求,其配置标准不得低于”初步配置方案” 的要求,同时应有一定的升级和扩展能力,并预留相应的接口。 3、智能化系统设计除了满足国家标准与规范的相关规定,以及本标准基本配 置要求外,还应满足建筑、结构以及与智能化系统存在设计相关联的其他专业 的设计规范和要求,特别需要注意符合项目当地现行有关标准和规范的特殊要求。 4、智能化系统设计与工程项目建设地点的实际情况相适应。 5、智能化系统所采用的设备及线路材料等均应符合国家现行的规定,并具有 产品合格证、质量检验证书和产品须通过国家的CCC认证。 二、智能化系统基本配置要求 1、安全防范系统 a、安全防范系统包括闭路电视监控、防盗报警系统、门禁系统、电子巡更系统及无线对讲系统。 b、闭路电视监控系统主要设置重要出入口,如公共场所、重要房间、楼梯通道、楼层电梯通道、电梯轿厢、室外主干道及交叉路口等处,电梯轿厢安装电 梯专用监控镜头并加装抗干扰器,户外监控镜头须带有红外夜视功能。所有的 监控镜头全部采用网络彩色摄像机,采用矩阵主机切换至电视墙,录像以全天 实时高清图像质量保存至少30天(具体保存时间可按照当地派出所要求确定)。 c、防盗报警系统主要设置在财务室、档案室等重要房间,并设置手动报警开关或脚挑报警开关,要求闭路电视监控系统同时显示出报警地点画面。 d、重要设备机房、财务室、档案室等重要房间设置门禁系统。 e、电子巡更系统要求采用离线式,设置于重要机房、楼层楼梯口、电梯厅。 f、无线对讲系统要求具有可进行信道改写和信道加密功能,满足内部通讯需要。 g、各系统设备品牌须选用技术成熟,性能稳定可靠的产品。 2、通讯网络系统

文件夹的作用

All Users文件夹: 『Win9x/ME』所有用户文件夹,里面里面包括系统缺省登录时的桌面文件和开始菜单的内容。『Win2000』在Win2000的系统目录中没有这个文件夹,Win2000将用户的信息放在根目录下的Documents and Settings文件夹中,每个用户对应一个目录,包括开始菜单、桌面、收藏夹、我的文档等等。 Application Data文件夹: 『Win9x/ME』应用程序数据任务栏中的快捷方式,输入法的一些文件等等。根据你系统中使用不同的软件,该目录中的内容也有所不同。 『Win2000』在Documents and Settings文件夹中,每个用户都对应一个Application Data 文件夹,同样每个用户由于使用的软件不同,目录内容也相同。 Applog文件夹: 『Win9x/ME』应用程序逻辑文件目录。逻辑文件是用来记录应用软件在运行时,需要调用的文件、使用的地址等信息的文件。要查看这些文件,用记事本打开即可。 Catroot文件夹: 『Win9x』计算机启动测试信息目录,目录中包括的文件大多是关于计算机启动时检测的硬软件信息。 『WinME』该文件夹位于系统目录的system目录中。 『Win2000』该文件夹位于系统目录的system32目录中。 Command文件夹: 『Win9x/ME』DOS命令目录。包括很多DOS下的外部命令,虽说都是些小工具,但真的很好用,特别是对于系统崩溃时。 『Win2000』这些DOS命令位于系统目录的system32目录中。 Config文件夹: 『Win9x/ME/2000』配置文件夹,目录中包括一些MIDI乐器的定义文件。 Cookies文件夹: 『Win9x/ME』Cookies又叫小甜饼,是你在浏览某些网站时,留在你硬盘上的一些资料,包括用户名、用户资料、网址等等。 『Win2000』每个用户都有一个Cookies文件夹,位于Documents and Settings文件夹的每个用户目录中。 Cursors文件夹: 『Win9x/ME/2000』鼠标动画文件夹。目录中包括鼠标在不同状态下的动画文件。 Desktop文件夹: 『Win9x/ME』桌面文件夹。包括桌面上的一些图标。 『Win2000』这个文件夹在系统目录中也存在,同时在Documents and Settings文件夹的每个用户目录中还有“桌面”文件夹。

linux下各文件夹的结构说明及用途详细介绍解析

linux下各文件夹的结构说明及用途介绍: /bin:二进制可执行命令。 /dev:设备特殊文件。 /etc:系统管理和配置文件。 /etc/rc.d:启动的配置文件和脚本。 /home:用户主目录的基点,比如用户user的主目录就是/home/user,可以用~user 表示。 /lib:标准程序设计库,又叫动态链接共享库,作用类似windows里的.dll文件。 /sbin:系统管理命令,这里存放的是系统管理员使用的管理程序。 /tmp:公用的临时文件存储点。 /root:系统管理员的主目录。 /mnt:系统提供这个目录是让用户临时挂载其他的文件系统。 /lost+found:这个目录平时是空的,系统非正常关机而留下“无家可归”的文件就在这里。 /proc:虚拟的目录,是系统内存的映射。可直接访问这个目录来获取系统信息。 /var:某些大文件的溢出区,比方说各种服务的日志文件。 /usr:最庞大的目录,要用到的应用程序和文件几乎都在这个目录。其中包含: /usr/x11r6:存放x window的目录。 /usr/bin:众多的应用程序。

/usr/sbin:超级用户的一些管理程序。 /usr/doc:linux文档。 /usr/include:linux下开发和编译应用程序所需要的头文件。 /usr/lib:常用的动态链接库和软件包的配置文件。 /usr/man:帮助文档。 /usr/src:源代码,linux内核的源代码就放在/usr/src/linux 里。 /usr/local/bin:本地增加的命令。 /usr/local/lib:本地增加的库根文件系统。 通常情况下,根文件系统所占空间一般应该比较小,因为其中的绝大部分文件都不需要经常改动,而且包括严格的文件和一个小的不经常改变的文件系统不容易损坏。除了可能的一个叫/vmlinuz标准的系统引导映像之外,根目录一般不含任何文件。所有其他文件在根文件系统的子目录中。 1. /bin目录 /bin目录包含了引导启动所需的命令或普通用户可能用的命令(可能在引导启动后。这些命令都是二进制文件的可执行程序(bin是binary的简称,多是系统中重要的系统文件。 2. /sbin目录 /sbin目录类似/bin,也用于存储二进制文件。因为其中的大部分文件多是系统管理员使用的基本的系统程序,所以虽然普通用户必要且允许时可以使用,但一般不给普通用户使用。 3. /etc目录

让你知道C盘的每个文件夹代表什么,其作用是什么

让你知道C盘的每个文件夹代表什么,其作用是什么 C:\Program Files文件夹介绍 列出常见的几个文件夹: 1、C:\Program Files\common files Common Files (存放软件会用到的公用库文件) 安装一些软件会在里面产生文件夹 比如visual studio symentec antivirus gtk lib 等 他是一些共享资源,这里的共享是指,一个公司所出的一系列软件都需要用这里的文件 比如:vb vc 要用里面visual studio 文件夹下的文件 norton fire wall norton antivirus 等要用里面symentec shared文件夹下的文件acrobat reader photoshop 要用里面adobe 文件夹下的文件 公有文件不能删除 正常的话会有: Microsoft Shared MSSoap ODBC SpeechEngines System Direct X Common Files这个文件是操作系统包扩系统程序和应用程序 Common Files是应用程序运行库文件 数据库覆盖了大约1000多个最流行的应用程序的插件,补丁等等 文件夹common files里很多都是系统文件,不能随意删除,除非确定知道是干什么用的,没用的可以删掉。不过就算删掉了有用的东西,也没大的关系,顶多是某些软件用不了,不会造成系统崩溃。 另外也有说各种软件的注册信息也在里面。 2、C:\Program Files\ComPlus Applications ComPlus Applications:微软COM+ 组件使用的文件夹,删除后可能引起COM+ 组件不能运行 显示名称:COM+ System Application ◎微软描述:管理基于COM+ 组件的配置和跟踪。如果服务停止,大多数基于 COM+ 组件将不能正常工作。如果本服务被禁用,任何明确依赖它的服务都将不能启动。 ◎补充描述:如果 COM+ Event System 是一台车,那么 COM+ System Application 就是司机,如事件检视器内显示的 DCOM 没有启用。一些 COM+软件需要,检查你的C:\Program Files\ComPlus 3、C:\Program Files\InstallShield Installation Information 发现这个网上一些解释的很含糊,说是用来存放部分软件安装信息的文件夹。比较准确的说

系统目录WINDOWS下主要文件夹简介

> 系统目录WINDOWS下主要文件夹简介 时间:2008-08-14 12:26来源:网络作者:未知点击:599次 WINDOWS系统目录下各个核心文件夹作用及用途介绍,详细完 ├—WINDOWS │ ├—system32(存放Windows的系统文件和硬件驱动程序) │ │ ├—config(用户配置信息和密码信息) │ │ │ └—systemprofile(系统配置信息,用于恢复系统) │ │ ├—drivers(用来存放硬件驱动文件,不建议删除) │ │ ├—spool(用来存放系统打印文件。包括打印的色彩、打印预存等) │ │ ├—wbem(存放WMI测试程序,用于查看和更改公共信息模型类、实例和方法等。请勿删除) │ │ ├—IME(用来存放系统输入法文件,类似WINDOWS下的IME文件夹) │ │ ├—CatRoot(计算机启动测试信息目录,包括了计算机启动时检测的硬软件信息) │ │ ├—Com(用来存放组件服务文件) │ │ ├—ReinstallBackups(电脑中硬件的驱动程序备份) │ │ ├—DllCache(用来存放系统缓存文件。当系统文件被替换时,文件保护机制会复制这个文件夹下的文件去覆盖非系统文件) │ │ ├—GroupPolicy(组策略文件夹) │ │ │ ├—system(系统文件夹,用来存放系统虚拟设备文件) │ ├—$NtUninstall$(每给系统打一个补丁,系统就会自动创建这样的一个目录,可删除) │ ├—security(系统安全文件夹,用来存放系统重要的数据文件) │ ├—srchasst(搜索助手文件夹,用来存放系统搜索助手文件,与msagent文件

Word 目录功能

Word目录编排功能应用 录是一个文档中不可缺少的一部分,目录的内容通常都是 由各级标题及其所在页的页码组成,目的在于方便阅读者直接查询有关内容的页码。 目录编排是档案编研工作中必不可少的一项工作。如果用手工完成一个文档目录的建立,将是一件机械而容易出错的工作,因为您必须一字不错的将每个标题的内容照抄到相应的目录中,而且要将该标题所在页的页号正确无误地记录下来。当文档中的标题被修改后,您又必须手工更新目录的内容,稍有不慎,生成的目录就会题文不符。笔者在工作中使用Word目录自动编排功能,觉得方便又准确,在此介绍给同行,以供参考。 Word提供了根据文档中标题样式段落的内容自动生成目录的功能。您可以通过控制创建目录的标题级别数来控制目录的级别数。但文档中的标题一定要使用相应的标题样式,否则,Word就不能按标题样式自动创建目录。 Word共提供了9级目录格式,它们一般为“目录1”、“目录2”、“目录3”、……“目录9”。“目录1”的内容一般为“标题1”的内容,如文章的每一章的标题,参考文献、附录、索引等标题,但整个文档的大题目、目录标题的“目录”、前言的标题“前言”等不能作为“目录1”中的内容出现在目录1中。“目录2 ”的内容为“标题2”的内容,“目录3”为“标题3”的内容,以此类推。文档的目录一般只需要3级,最多不超过4级或5级。 一、目录的生成 目录的生成一般都在文档写作完成后才进行。其生成过程就是目录域的插入。要插入目录,首先要选择目录的插入点,一般都选择在

文档正文之前,并将光标定位到该插入点。具体操作步骤如下: 1、 选择?插入(I)?菜单中的〖分隔 符(B)〗命令后,屏幕上显示“分隔符” 对话框,右图所示,点击〖分页符〗中 的“下一页”选项,然后再单击?确定? 按钮。(主要功能是将目录与正文的页 码断开,即确保目录和正文的页码都分 别从“1”开始。) 2、 将光标 定位在分节符 前,选择?插入 (I)?菜单中的〖索 引和目录(D)…〗 命令后,屏幕上 显示“索引和目 录”对话框,如右 上图所示。 3、 激活〖目录(C)〗选项后,在〖格式(T)〗选项下选择合适的目录格式,并在对话框中部查看其预览效果。 4、 在〖显示级别(L)〗选项下输入不同数字以改变目录中包含的标题样式级别数目。 5、 单击?确定?按钮,就会将 目录添加到文档中。右图所示的是用 Word 自动生成的《科研成果简介)》 目录。 二、目录的更新 当对文档的标题作了修改之后, 自然需要对新文档的目录进行更新。如果用手工更新目录的话,就要

Linux下各文件夹的结构说明及用途介绍

linux下各文件夹的结构说明及用途介绍: /bin 二进制可执行命令 /dev 设备特殊文件 /etc 系统管理和配置文件 /etc/rc.d 启动的配置文件和脚本 /home 用户主目录的基点,比如用户user的主目录就是/home/user,可以用~user表示 /lib 标准程序设计库,又叫动态链接共享库,作用类似windows里的.dll文件 /sbin 系统管理命令,这里存放的是系统管理员使用的管理程序 /tmp 公用的临时文件存储点 /root 系统管理员的主目录(呵呵,特权阶级) /mnt 系统提供这个目录是让用户临时挂载其他的文件系统。 /lost+found 这个目录平时是空的,系统非正常关机而留下“无家可归”的文件(windows 下叫什么.chk)就在这里 /proc 虚拟的目录,是系统内存的映射。可直接访问这个目录来获取系统信息。 /var 某些大文件的溢出区,比方说各种服务的日志文件 /usr 最庞大的目录,要用到的应用程序和文件几乎都在这个目录。其中包含: /usr/x11r6 存放x window的目录 /usr/bin 众多的应用程序 /usr/sbin 超级用户的一些管理程序 /usr/doc linux文档 /usr/include linux下开发和编译应用程序所需要的头文件 /usr/lib 常用的动态链接库和软件包的配置文件 /usr/man 帮助文档 /usr/src 源代码,linux内核的源代码就放在/usr/src/linux里 /usr/local/bin 本地增加的命令 /usr/local/lib 本地增加的库根文件系统 通常情况下,根文件系统所占空间一般应该比较小,因为其中的绝大部分文件都不需要经常改动,而且包括严格的文件和一个小的不经常改变的文件系统不容易损坏。 除了可能的一个叫/ v m l i n u z标准的系统引导映像之外,根目录一般不含任何文件。所有其他文件在根文件系统的子目录中。 1. /bin目录 / b i n目录包含了引导启动所需的命令或普通用户可能用的命令(可能在引导启动后)。这些 命令都是二进制文件的可执行程序( b i n是b i n a r y - -二进制的简称),多是系统中重要的系统文件。 2. /sbin目录 / s b i n目录类似/bin ,也用于存储二进制文件。因为其中的大部分文件多是系统管理员使用的基本的系统程序,所以虽然普通用户必要且允许时可以使用,但一般不给普通用户使用。 3. /etc目录 / e t c目录存放着各种系统配置文件,其中包括了用户信息文件/ e t c / p a s s w d,系统初始化文件/ e t c / r c等。l i n u x正是*这些文件才得以正常地运行。 4. /root目录 /root 目录是超级用户的目录。

Windows下各个文件夹的作用分别是什么

Windows下各个文件夹的作用分别是什么 更新时间:2011-08-21 作者:来源:访问: ├—WINDOWS │├—system32(存放Windows的系统文件和硬件驱动程序) ││├—config(用户配置信息和密码信息) │││└—systemprofile(系统配置信息,用于恢复系统) ││├—drivers(用来存放硬件驱动文件,不建议删除) ││├—spool(用来存放系统打印文件。包括打印的色彩、打印预存等) ││├—wbem(存放WMI测试程序,用于查看和更改公共信息模型类、实例和方法等。请勿删除) ││├—IME(用来存放系统输入法文件,类似WINDOWS下的IME文件夹) ││├—CatRoot(计算机启动测试信息目录,包括了计算机启动时检测的硬软件信息) ││├—Com(用来存放组件服务文件) ││├—ReinstallBackups(电脑中硬件的驱动程序备份) ││├—DllCache(用来存放系统缓存文件。当系统文件被替换时,文件保护机制会复制这个文件夹下的文件去覆盖非系统文件) ││├—GroupPolicy(组策略文件夹) ││ │├—system(系统文件夹,用来存放系统虚拟设备文件) │├—$NtUninstall$(每给系统打一个补丁,系统就会自动创建这样的一个目录,可删除) │├—security(系统安全文件夹,用来存放系统重要的数据文件)

│├—srchasst(搜索助手文件夹,用来存放系统搜索助手文件,与msagent文件夹类似) │├—repair(系统修复文件夹,用来存放修复系统时所需的配置文件) │├—Downloaded Program Files(下载程序文件夹,用来存放扩展IE功能的ActiveX等插件) │├—inf(用来存放INF文件。INF文件最常见的应用是为硬件设备提供驱动程序服务,不建议删除其中文件) │├—Help(Windows帮助文件) │├—Config(系统配置文件夹,用来存放系统的一些临时配置的文件) │├—msagent(微软助手文件夹,存放动态的卡通形象,协助你更好地使用系统。若觉的没有必要,可直接删除) │├—Cursors(鼠标指针文件夹) │├—Media(声音文件夹,开关机等wav文件存放于此) │├—Mui(多语言包文件夹,用来存放多国语言文件。简体中文系统中这个文件夹默认是空的,但不建议删除此文件夹) │├—java(存放java运行的组件及其程序文件。不建议删除其中文件) │├—Web ││├—Wall*****(存放桌面壁纸的文件夹) ││ │├—addins(系统附加文件夹,用来存放系统附加功能的文件) │├—Connection Wizard(连接向导文件夹,用来存放“Internet连接向导”的相关文件) │├—Driver Cache(驱动缓存文件夹,用来存放系统已知硬件的驱动文件) ││└—i386(Windows操作系统自带的已知硬件驱动文件,可删除以节省空间)

计算机中各种文件的作用说明

----------给你一个WINDOWS 文件夹内容的介绍,看了你就明白了. ├—WINDOWS │ ├—system32(存放Windows的系统文件和硬件驱动程序) │ │ ├—config(用户配置信息和密码信息) │ │ │ └—systemprofile(系统配置信息,用于恢复系统) │ │ ├—drivers(用来存放硬件驱动文件,不建议删除) │ │ ├—spool(用来存放系统打印文件。包括打印的色彩、打印预存等) │ │ ├—wbem(存放WMI测试程序,用于查看和更改公共信息模型类、实例和方法等。请勿删除) │ │ ├—IME(用来存放系统输入法文件,类似WINDOWS下的IME文件夹) │ │ ├—CatRoot(计算机启动测试信息目录,包括了计算机启动时检测的硬软件信息) │ │ ├—Com(用来存放组件服务文件) │ │ ├—ReinstallBackups(电脑中硬件的驱动程序备份) │ │ ├—DllCache(用来存放系统缓存文件。当系统文件被替换时,文件保护机制会复制这个文件夹下的文件去覆盖非系统文件) │ │ ├—GroupPolicy(组策略文件夹) │ │ │ ├—system(系统文件夹,用来存放系统虚拟设备文件) │ ├—$NtUninstall$(每给系统打一个补丁,系统就会自动创建这样的一个目录,可删除) │ ├—security(系统安全文件夹,用来存放系统重要的数据文件) │ ├—srchasst(搜索助手文件夹,用来存放系统搜索助手文件,与msagent文件夹类似) │ ├—repair(系统修复文件夹,用来存放修复系统时所需的配置文件)

多功能厅智能化系统

多功能厅智能化系统 一、工程概况 多功能厅的智能化系统应是功能先进,设施完备,应当具有智能性、先进性、兼容性及可扩展性。该会议系统将高质量的音频、视频和诸多智能特性紧密结合在一起,通过数字信号处理、压缩编码技术和数据传输等新技术的融入,实现更多、更齐全的会议会话、视频传输、信息传输功能。方案设计要根据具体需求分析,针对性地展开设计,以满足各多功能厅的具体要求。 设计方案应集成当今世界多媒体集成系统的各种现代化设备,如使用会议同声传译发言表决系统,使会议进程具有高雅简洁的特点;大屏幕显示的应用可以提高大厅的规格档次,具有清晰明亮、色彩丰富、逼真的及动态视觉效果;选用专业化的音频处理设备,以最佳状态处理声音效果,使话音清晰均匀,演示效果明显;高清晰度及高精度云台摄像监视设备完全满足现代化监控的摄录及新闻发布的要求;所有的视听设备均可通过智能中央控制系统实现遥控操作,使系统具有完美的整体性和高度可靠性,操作平台可选用彩色液晶显触摸屏,控制涉及大厅系统的每个子系统,真正实现了智能化控制。 系统的设计思想是现代化、高起点、高质量、高可靠性、高完整性。既具备现代化大厅的各种使用功能,又可以完成高质量的视听节目播放等特殊使用要求,高度自动化的操控方式使其具备各种功能任意选用的特点。 二、系统设计依据 本项目中所指定系统之设计的依据和设计规范标准为: ●多功能厅的需求报告; ●多功能厅的相关技术图纸; ●《智能建筑设计规范》GBJ08-47-95; ●《智能建筑设计标准》GB/T 50314-2000 ; ●《30-1GHz声音和电视信号的电缆分配系统》GB6510-86; ●《建筑电气安装工程质量检验评定标准》GBJ-303-88; ●《民用建筑电气设计规范》JGJ/T16-92; ●《厅堂扩声系统声学特性指标》GYJ25-86; ●《声系统设备互连的优选配接值》GB14197-93; ●《厅堂混响时间测量规范》GBJ76-84 ●《厅堂扩声特性测量法》GB/T4959-1995; ●《客观评价厅堂语言可懂度的RASTI法》GB/T14476-93; ●《中华人民共和国国家行业标准》;

linux文件目录作用

目录树的主要部分有root(/)、/usr、/var、/home等等。下面是一个典型的linux 目录结构如下: / 根目录 /bin 存放必要的命令 /boot 存放内核以及启动所需的文件等 /dev 存放设备文件 /etc 存放系统的配置文件 /home 用户文件的主目录,用户数据存放在其主目录中 /lib 存放必要的运行库 /mnt 存放临时的映射文件系统,我们常把软驱和光驱挂装在这里的floppy和cdrom子目录下。 /proc 存放存储进程和系统信息 /root 超级用户的主目录 /sbin 存放系统管理程序 /tmp 存放临时文件的目录 /usr 包含了一般不需要修改的应用程序,命令程序文件、程序库、手册和其它文档。 /var 包含系统产生的经常变化的文件,例如打印机、邮件、新闻等假脱机目录、日志文件、格式化后的手册页以及一些应用程序的数据文件等等。建议单独的放在一个分区。[separator] 典型的/usr目录如下: /X11R6 存放X window系统 /bin 存放增加的用户程序 /dict 存放字典 /doc 存放追加的文档 /etc 存放设置文件 /games 存放游戏和教学文件 /include 存放C开发工具的头文件 /info 存放GNU信息文件 /lib 存放库文件 /local 存放本地产生的增加的应用程序 /man 存放在线帮助文件 /sbin 存放增加的管理程序 /share 存放结构独立的数据 /src 存放程序的源代码 由于/usr中的文件不和特定的计算机相关,也不会在通常使用中修改,因此可以通过网络共享这个目录(文件系统),这样,当管理员安装了新的软件之后,所有共享这一文件系统的计算机均可以使用新的软件。 Linux继承了unix操作系统结构清晰的特点。在linux下的文件结构非常有条理。但是,上述的优点只有在对linux相当熟悉时,才能体会到。现在,虫虫就把linux 下的目录结构简单介绍一下。

希尔顿酒店智能化系统配置

一、建筑概况 酒店位于广州市珠江新城猎德,酒店建筑面积50294平方米,建筑高度100m,建筑层数地上25层,地下4层,客房数约357间。 二、设计依据 1、甲方提供的建筑、结构、强电、给排水、暖通等相关专业提供的设计资料及要求。 2、希尔顿酒店管理公司《机电设计标准》(弱电系统部分) 3、国家现行的相关设计标准、规范: (1)《高层民用建筑设计防火规范》(GB50045-95)2005年版 (2)《民用建筑电气设计规范》(JGJ 16-2008) (3)《火灾自动报警系统设计规范》(GB50116-2013) (4)《智能建筑设计标准》(GB/T 50314-2006) (5)《综合布线系统工程设计规范》(GB 50311-2007) (6)《安全防范工程技术规范》(GB 50348-2004) (7)《入侵报警系统工程技术规范》(GB 50394-2007) (8)《视频安防监控系统工程技术规范》(GB 50395-2007) (9)《出入口控制系统工程技术规范》(GB 50396-2007) (10)《电子信息系统机房设计规范》(GB50174-2008) (11)《民用建筑设计通则》(GB50352-2005) (12)《低压配电设计规范》(GB50054-2011) (13)《供配电系统设计规范》(GB50052-2009) (14)《电力工程电缆设计规范》(GB50217-2007) (15)《通用用电设备配电设计规范》(GB50055-2011) (16)《建筑照明设计标准》(GB50034-2013) (17)《建筑物防雷设计规范》(GB50057-2010) (18)《建筑物电子信息系统防雷设计技术规范》(GB 50343-2012) (19)《电力装置的电测量仪表装置设计规范》(GB50063-90) (20)《公共建筑节能设计标准》(GB 50189-2005) (21)《公共建筑节能设计标准》广东省实施细则(DBJ 15-51-2007) 4、建设单位、物业管理单位对设计的意见及需求

医院智能化系统设计方案

医院项目设计方案 一、设计说明 1.设计依据 招标文件及图纸 DBJ01-615-2003《建筑智能化系统设计技术规范》 GB 50339-2003 《智能建筑工程质量验收规范》 DB21/T1341-2004 《智能建筑工程施工质量验收实施细则》 GB/T50311-2000 建筑与建筑群综合布线系统工程设计规范 GB/T50312-2000 建筑与建筑群综合布线系统工程验收规范 GB6510-86《电视和声音信号的电缆分配系统》 GBJ1200-88《工业企业共用天线电视系统设计方案》 BG7401-87《彩色电视图像质量主观评价方法》 GBJ79-85《工业企业通讯接地设计规范》 B11318.5-89 《声音和电视信号的电缆分配系统设备与部件;可靠性要求与试验方法》 GB50200-94《有线电视系统工程技术规范》 GA/T75-94《安全防范工程程序与要求》 GBJ232-82《电器装置安装工程施工及验收规范》 GB-50057-94《建筑物防雷设计规范》 GB/T 50314-2000《智能建筑设计标准》 JGJ/T 16-92《民用建筑电气设计规范》 2.设计原则 本系统设计遵循以下设计原则: 系统设计与配置强调先进适用。在技术上保持先进性,具有适应技术发展趋势及产品更新的能力。 系统设计与配置综合平衡考虑,特别强调建筑设备管理系统在节能等方面的

作用,达到国际先进水准。 系统设计与配置在体现本工程整体特色的同时,注意工程投资的经济效益。除考虑建设时的一次性投资外,还考虑系统到的运行成本,并使之最小化。 整个系统在规划时结合建筑的各功能分区进行设计。 具体如下: 以人为本:以满足使用者的需求为目标,建立良好的人机界面,中文显示、操作简单、界面友好、管理轻松、方便。 标准化:各子系统设计及其实施将按照国家和地方的有关标准进行,所选用的系统,设备,产品和软件符合工业标准或主流模式。 先进性:考虑到电子信息及软件技术的迅速发展,各子系统所采用的设备产品和软件不仅成熟而且能代表当今世界的技术水平。 实用性:集成管理系统设计将以业主需求分析着手,并以得到业主认可的需求为目标来开展工作,保证满足目前存在的各种需要。 合理性和经济性:在保证先进性的同时,以提高工作效率,节省人力和各种资源为目标进行工程设计,充分考虑系统的实用和效益,争取获得最大的投资回报率。 安全性和可靠性:安全和可靠是对智能建筑的基本要求,是弱电集成系统工程设计所追求的主要目之一。 模块化和可扩充性:具有很好的兼容性和可扩充性,既可使不同厂商的集成管理系统到一个管理平台中,又可使系统能在日后得以方便地扩充,并扩展另外厂商的系统。 方便性和舒适性:在使用和操作上将为弱电工程的拥有者、管理者及其客户提供最有效的信息服务,提供高效,舒适,便利和安全的工作环境。 灵活性:系统提供管理人员和用户灵活移动和变更设备的可能。 二、综合布线系统工程 1.产品规范和技术标准 本设计方案中所使用产品主要适用的规范标准为: TIA/EIA 568-B 北美综合布线标准 TIA/EIA 569 北美建筑通讯线路间距标准 TIA/EIA 570 北美住宅和小型商用通讯布线标准 TIA/EIA 606 北美商用建筑通讯基础结构管理规范

智能化工程设计项目施工与验收相关规范、标准、规程

智能化工程设计施工与验收 相关规范、标准、规程 一、智能化系统配置 通用办公建筑为例。 1.信息化应用系统 、公共服务系统 、智能卡应用系统 、物业管理系统 、信息设施运行管理系统 、信息安全管理系统 2.智能化集成系统 、智能化信息集成(平台)系统 、智能化信息应用系统 3.信息设施系统 、信息接入系统光纤到楼层、光纤到桌面等等。 、综合布线系统 、移动通信室内信号覆盖系统 、无线对讲系统 、信息网络系统 、有线电视系统 、公共广播系统 、会议系统 、信息导引与发布系统 、用户电话交换系统

4.建筑设备管理系统 、建筑设备监控系统 、建筑设备能效监管系统 5.公共安全系统 、火灾自动报警系统 、安全技术防范系统入侵报警系统、视频安防监控系统、出入口控制系统、电子巡查系统、访客对讲系统、停车库管理系统。 、安全防范综合管理(平台)系统 6.机房工程 、信息接入机房 、有线电视前端机房 、信息设施系统总配线机房 、智能化总控制室 、信息网络机房 、消防控制室 、安防监控中心 、智能化设备间 二、系统集成 《智能建筑设计标准》(—) 《智能建筑工程质量验收规范》(—) 《安全防范工程技术规范》(—) 三、安防工程主要规范 《安全防范工程技术规范》(—) 《智能建筑工程质量验收规范》(—) 《民用建筑电气设计规范》() 《智能建筑设计标准》(—) 《智能建筑工程质量验收规范》(—) 《安全防范工程建设与维护保养费用预算编制办法》 《安全防范系统通用图形符号》(—)

《安全防范工程程序与要求》(—) 《安全防范系统维护保养规范》() 《安全防范工程监理规范》() 《银行营业场所安全防范工程设计规范》(—) 《银行营业场所安全防范要求》() 《银行自助设备、自助银行安全防范的规定》() 《银行自助服务亭技术要求》() 《银行业务库安全防范要求》() 《文物系统博物馆安全防范工程设计规范》(—) 《文物系统博物馆风险等级和安全防护级别的规定》(—)《民用爆炸物品储存库治安防范要求》 《入侵报警系统工程设计规范》(—) 《入侵探测器通用技术条件》(—) 《超声波多普勒探测器》(—) 《微超声波多普勒探测器》(—) 《主动红外入侵探测器》(—) 《被动红外入侵探测器》(—) 《微波和被动红外复合入侵探测器》(—) 《振动入侵探测器》(—) 《磁开关入侵探测器》(—) 《防盗报警控制器通用技术条件》(—) 《视频安防监控系统工程设计规范》(—) 《安全防范视频监控摄像机通用技术要求》 《出入口控制系统工程设计规范》(—) 楼寓对讲电控防盗门通用技术条件 《电子巡查系统技术要求》(—) 《停车库(场)安全管理系统技术要求》 四、消防工程 《建筑设计防火规范》(—) 《农村防火规范》(—) 《建筑防雷设计规范》() 《爆炸危险环境电力装置设计规范》(—) 《汽车库、修车库、停车场设计防火规范》(—) 《石油库设计规范》() 《自动喷水灭火系统设计规范》(—) 《人民防空工程设计防火规范》() 《火灾自动报警系统设计规范》(—) 《建筑灭火器配置设计规范》() 《低倍数泡沫灭火系统设计规范》(—) 《小型石油库及汽车加油站设计规范》(—) 《石油化工企业设计防火规范》(—)

相关主题