搜档网
当前位置:搜档网 › NACE SP0107-2007

NACE SP0107-2007

NACE SP0107-2007
NACE SP0107-2007

Standard Practice

Electrochemical Realkalization and Chloride Extraction

for Reinforced Concrete

This NACE International standard represents a consensus of those individual members who have reviewed this document, its scope, and provisions. Its acceptance does not in any respect preclude anyone, whether he or she has adopted the standard or not, from manufacturing, marketing, purchasing, or using products, processes, or procedures not in conformance with this standard. Nothing contained in this NACE International standard is to be construed as granting any right, by implication or otherwise, to manufacture, sell, or use in connection with any method, apparatus, or product covered by Letters Patent, or as indemnifying or protecting anyone against liability for infringement of Letters Patent. This standard represents minimum requirements and should in no way be interpreted as a restriction on the use of better procedures or materials. Neither is this standard intended to apply in all cases relating to the subject. Unpredictable circumstances may negate the usefulness of this standard in specific instances. NACE International assumes no responsibility for the interpretation or use of this standard by other parties and accepts responsibility for only those official NACE International interpretations issued by NACE International in accordance with its governing procedures and policies, which preclude the issuance of interpretations by individual volunteers.

Users of this NACE International standard are responsible for reviewing appropriate health, safety, environmental, and regulatory documents and for determining their applicability in relation to this standard prior to its use. This NACE International standard may not necessarily address all potential health and safety problems or environmental hazards associated with the use of materials, equipment, and/or operations detailed or referred to within this standard. Users of this NACE International standard are also responsible for establishing appropriate health, safety, and environmental protection practices, in consultation with appropriate regulatory authorities if necessary, to achieve compliance with any existing applicable regulatory requirements prior to the use of this standard.

CAUTIONARY NOTICE: NACE International standards are subject to periodic review, and may be revised or withdrawn at any time in accordance with NACE technical committee procedures. NACE International requires that action be taken to reaffirm, revise, or withdraw this standard no later than five years from the date of initial publication. The user is cautioned to obtain the latest edition. Purchasers of NACE International standards may receive current information on all standards and other NACE International publications by contacting the NACE International FirstService Department, 1440 South Creek Dr., Houston, Texas 77084-4906 (telephone +1[281]228-6200).

Approved 2007-03-10 NACE International 1440 South Creek Drive Houston, Texas 77084-4906

+1 281/228-6200

ISBN 1-57590-210-9 ? 2007, NACE International

NACE SP0107-2007

Item No. 21113

SP0107-2007

________________________________________________________________________

Foreword

This NACE standard practice presents the requirements for electrochemical chloride extraction and

electrochemical realkalization of reinforcing steel in atmospherically exposed concrete structures.

The standard provides the design engineer and contractor with the requirements for control of

corrosion of conventional reinforcing steel in Portland cement concrete structures through the

application of chloride extraction or realkalization. This standard is aimed at owners, engineers,

architects, contractors, and all those concerned with rehabilitation of corrosion-damaged reinforced

concrete structures.

These electrochemical techniques are related to the use of impressed current cathodic protection

of steel in concrete as described in NACE SP0290.1 State-of-the-art reports on the techniques

were previously published by the task group and are available from NACE.2,3 For more information

on design, maintenance, and rehabilitation of reinforcing steel in concrete, refer to NACE Standard

RP01874 and NACE Standard RP0390.5

To provide for the necessary expertise on all aspects of the subject and to provide input from all

interested parties, Task Group (TG) 054 is composed of corrosion consultants, consulting

engineers, architect engineers, cathodic protection engineers, researchers, structure owners, and

representatives from both industry and government.

The provisions of this standard should be applied under the direction of a registered Professional

Engineer or a person certified by NACE International as a Corrosion Specialist or Cathodic

Protection Specialist. His or her professional experience should include suitable experience in

corrosion control of reinforced concrete structures.

This standard was prepared in 2007 by NACE TG 054, a component of Specific Technology Group

(STG) 01 on Reinforced Concrete, and is published under the auspices of STG 01.

In NACE standards, the terms shall, must, should, and may are used in accordance with the

definitions of these terms in the NACE Publications Style Manual, 4th ed., Paragraph 7.4.1.9. Shall

and must are used to state mandatory requirements. The term should is used to state something

good and is recommended but is not mandatory. The term may is used to state something

considered optional.

________________________________________________________________________

SP0107-2007

________________________________________________________________________

NACE International

Standard

Practice

Electrochemical Realkalization and Chloride Extraction for

Reinforced Concrete

Contents

1. General (1)

2. Electrochemical Chloride Extraction (2)

3. Electrochemical Realkalization (6)

References (10)

Bibliography (11)

________________________________________________________________________

SP0107-2007 ________________________________________________________________________

Section 1: General

1.1 Background

1.1.1 Following this General section, this standard is

divided into two stand-alone sections, the first on electrochemical chloride extraction and the second on

electrochemical realkalization. This will help the user by ensuring that all the relevant provisions are in one place.

1.1.2 Reinforcing steel is compatible with concrete

because of similar coefficients of thermal expansion and because concrete normally provides the steel with

excellent corrosion protection. The corrosion protection

is the result of the formation of a highly alkaline passive

oxide film on the surface of the reinforcement by Portland cement contained in the concrete. This passive oxide film is compromised by (1) excessive amounts of chloride or other aggressive ions and gases

such as carbon dioxide, or (2) the concrete not fully encasing the steel.

1.1.3 Corrosion occurs as a result of the formation of

an electrochemical cell. An electrochemical cell consists of four components: an anode, where oxidation occurs; a cathode, where reduction occurs; a

metallic path, where the electrons flow; and an electrolyte (concrete), where the ions flow. The anodic

and cathodic areas occur as a result of coupling of dissimilar metals, exposure to differential environmental

conditions, or both. If any one of the four elements of

the electrochemical cell is eliminated, corrosion can be

prevented.

1.1.4 Corrosion of reinforcing steel in concrete is a

serious problem in certain environments throughout the

world. This corrosion is directly attributable to the presence of significant amounts of aggressive substances at the steel surface. Parking structures, bridges and roadways, buildings, sanitary and water facilities, marine structures, concrete pipe, storage facilities, and other reinforced concrete structures are being damaged by corrosion. Corrosion of the reinforcing steel can weaken or destroy a structure.

Corrosion of the reinforcing steel in concrete and the resulting cracking and spalling of concrete costs billions

of dollars/euros, etc., each year. These losses can be

reduced if proper corrosion control factors are considered during rehabilitation and maintenance repair of reinforced concrete structures.

1.1.5 Carbonation of concrete is a major cause of

reinforcement corrosion. Carbonation is a process by

which atmospheric carbon dioxide reacts with the alkalis in the pore water of the concrete. A carbonation

front proceeds through the cover concrete to the reinforcement, where it leads to the breakdown of the passive oxide layer, allowing corrosion to proceed.

Electrochemical realkalization can be used to reverse

this process and restore the alkaline environment to the

reinforcement, preventing further corrosion.

1.1.6 Chloride-induced corrosion is the other major

cause of reinforcement corrosion. It has been shown

that chloride ion content as low as approximately 0.2

percent by weight of cement (or approximately 0.6

kg/m3 [1 lb/yd3] of concrete, depending on the cement

content of the mix) at the steel depth can initiate the

corrosion process. Electrochemical realkalization can

be used to move chloride ions away from the steel

surface and reestablish the protective passive oxide

layer.

1.2 Electrochemical Treatments

1.2.1 Electrochemical treatments for reinforced

concrete include cathodic protection (CP), electrochemical chloride extraction (ECE), and electrochemical realkalization (ER). ECE and ER are

short-term treatments with a temporary installation that

is removed after treatment. Treatment is intended to

remove the cause of corrosion. On the other hand, CP

is a permanent installation.

CP of atmospherically exposed steel in concrete is

described in NACE SP0290.1 Many of the practices

described in SP0290 are relevant to ECE and ER in

terms of preparation of the structure, testing, and

wiring.

1.3 Scope and Limitations

1.3.1 The provisions of this standard shall be applied

under the direction of a registered Professional

Engineer or a person certified by NACE International

as a Corrosion Specialist or certified as a Cathodic

Protection Specialist. The person’s professional

experience shall include suitable experience in CP,

ECE, and ER.

1.3.2 The requirements presented here are limited to

impressed current ECE and ER systems for new or

existing atmospherically exposed reinforced concrete

elements; they are not applicable to prestressed

concrete.

1.3.3 Normal reinforcement in post-tensioned

elements with the post-tensioning strands fully protected in ducts can be treated as long as adequate

precautions are taken to ensure that the prestressed

steel is not susceptible to hydrogen embrittlement and

that it is protected such that the potential of the steel

does not rise above the hydrogen evolution potential.

SP0107-2007

________________________________________________________________________

Section 2: Electrochemical Chloride Extraction

2.1 Suitability for Treatment

A structure shall be suitable for ECE if:

2.1.1 There is sufficient chloride contamination to

warrant generalized or localized treatment to retard further chloride attack.

2.1.2 Water ingress can be controlled during treatment

so that the current density to the steel can be maintained and accurately monitored, especially in marine conditions. ECE is not suitable for application

to the elements of structures in splash and tidal zones.

2.1.3 There is no prestressed steel susceptible to

hydrogen embrittlement in the area to be treated. Any

prestressed steel shall be monitored to ensure that its

potential does not go more negative than -1,100 mV vs.

a copper/copper sulfate reference electrode.

2.1.4 Any susceptibility to alkali silica reaction (ASR) is

addressed by analysis of the risk of further ASR expansion and, if necessary, by the use of a suitable

electrolyte as discussed in Paragraph 2.3.2.

2.2 End Point Criteria

2.2.1 The criteria in this section have been found to

achieve corrosion control for reinforcing steel embedded in atmospherically exposed concrete after the application of ECE. Compliance with these criteria

is dependent on analysis of representative data in each

situation. The number and locations of measurements

made during data collection shall be commensurate with the complexity of the structure being protected.

Sampling plans shall be in accordance with ASTM(1)

E105.6 Sample size shall be determined in accordance

with ANSI(2)/ASQ(3)Z1.47 with the unit of product typically being 0.836 m2 (1.00 yd2) of protected metal

surface area. For structures in which ECE or ER systems are divided into discrete zones, testing inspection lots shall be defined. Acceptable quality and

confidence levels shall also be defined. Potentials of

reinforcing steel or other embedments measured against portable reference electrodes shall be obtained

in accordance with the techniques described in ASTM

C876.8 Sign conventions for potential and current density as well as conventions for graphical presentation of data shall be in accordance with ASTM

G3-89.9

2.2.2 NACE TG 054 developed these criteria through

evaluation of data obtained from successfully operated ECE systems. NOTE: Those using this standard shall review data made available after this standard’s publication to determine whether more effective criteria have been established. It is not intended that those responsible for corrosion control be limited to these criteria if it can be demonstrated by other means that adequate corrosion control can be achieved. A combination of criteria can be used on a single structure.

2.2.3 In all cases, the current density shall not exceed 4 A/m2 (0.4 A/ft2) of steel surface area, and the voltage shall be in the range of 30 to 50 V direct current (DC).

2.2.4 Electrochemical Chloride Extraction Criteria —At least one of criterion A, B, or C below (Paragraphs 2.2.4.1, 2.2.4.2, and 2.2.4.3) shall be used:

2.2.4.1 Criterion A—Chloride content within the

concrete: Treatment shall be continued until the

chloride content within the concrete in the vicinity

of the reinforcing steel is reduced to a predetermined level.

A suitable test method for chloride determination is

ASTM C1152/C1152M-04e1.10Treatment is halted when the target chloride value is reached.

Samples are collected carefully to prevent contamination and are located relative to the location of the rebar. Because of the inhomogeneous nature of embedded concrete, samples are statistically analyzed to account for

natural variations in chloride content.

NOTE: Typical target values used for these measurements are acid-soluble chloride content of

less than 0.2 to 0.4% by weight of cement (when

corrected for background levels of chloride permanently bound in aggregates, if appropriate)

within 25 mm (1.0 in.) or one diameter of the

reinforcing steel.

2.2.4.2 Criterion B—Amp hours (A-h) per square

meter (per square foot): This criterion ensures a

minimum treatment of charge density per unit area

of steel. NOTE: 600 A-h/m2 (56 A-h/ft2) is a typical

minimum target. 1,500 A-h/m2 (140 A-h/ft2) is a

very conservative value and should not be exceeded for most applications. There are some

structures for which it might not be practical to

achieve a given accumulated charge.

___________________________

(1) ASTM International (ASTM), 100 Barr Harbor Dr., West Conshohocken, PA 19428-2959.

(2) American National Standards Institute (ANSI), 11 W. 42nd St., New York, NY 10036.

(3) American Society for Quality (ASQ), 611 East Wisconsin Ave., Milwaukee, WI 53201-3005.

SP0107-2007

2.2.4.3 Criterion C—Chloride/hydroxyl ratio: Using

this criterion, the chloride/hydroxyl ratio in the

vicinity of the reinforcing steel is reduced to less

than 0.6. A suitable method for measuring the

chloride content is ASTM C1152/C1152M-04e1. A

suitable method for measuring the pH of pore

water and chloride/hydroxyl ratio of pore water is

given in Cáseres, et. al.11

NOTE: Half-cell potentials and corrosion rate

monitoring before and after ECE treatment have

been used in some cases, but these

measurements have limitations because of the

polarization of the reinforcing steel and the time

required for depolarization. Potential or rate

measurements are typically taken approximately

six months after treatment to allow for

depolarization. A suitable method for measuring

half cell potentials is ASTM C876.8 One criterion

is to reduce the potential difference to less than

150 mV across the treated zone.

2.3 Design

2.3.1 Anode Systems

2.3.1.1 Anode systems shall be mild steel or

catalyzed titanium.

2.3.1.2 Mild steel anodes shall be welded wire

fabric. Mild steel anodes are suitable for

structures when some staining of the concrete

surface is not a concern, when the possible

evolution of small amounts of chlorine cannot be

tolerated, and when treatment time is short.

NOTE: A suitable steel mesh is 3.0 to 4.0 mm

(0.12 to 0.16 in.) diameter on a 50 x 50 or 100 x

100 mm (2 x 2 in. or 4 x 4 in.) mesh size.

Mild steel anodes shall be fixed apart from the

concrete surface so that the steel does not come

in direct contact with the concrete surface.

Electrical anode wires shall be attached to cleaned

surfaces of the steel anodes by a firm mechanical

bond, and the connections shall be sealed to

prevent corrosion during treatment. If staining of

the concrete surface occurs, discoloration shall be

removed, if desired, by a light abrasive blast

following treatment.

2.3.1.3 Catalyzed titanium anodes shall be used

when staining of the concrete is unacceptable and

when pH of the electrolyte can be carefully

monitored to prevent acidification and possible

chlorine evolution.

Catalyzed titanium anodes shall be in the form of a

flexible, highly expanded mesh that conforms easily to concrete surfaces.

Catalyzed titanium anodes shall, as a minimum,

meet the requirements of NACE Standard TM0294.12

Anode wires shall be attached to an ASTM B26513

Grade 1 titanium current distributor bar outside the

electrolyte. The current distributor bar shall distribute current to the catalyzed titanium anode

by resistance-welded connections extending the

length of the anode.

When catalyzed titanium anodes are used, the

electrolyte shall be buffered, or alkali shall be

periodically added to the electrolyte to prevent the

electrolyte from dropping below pH 7.

2.3.2 Electrolytes

2.3.2.1 Potable water is a suitable electrolyte and

ensures that the current carries the maximum amount of chloride with minimal competition from

other ions. However, water is liable to acidify and

may promote the evolution of chlorine gas on

mixed metal oxide coated titanium anodes.

2.3.2.1.1 Regular electrolyte replacement

may be required to maintain the pH above 6,

and control of evolved chlorine gas may be

required in confined areas. NOTE: Certain

fixtures and fittings to structures such as

window frames, light fittings, and railings may

be subject to attack from alkaline or acidified

electrolytes and may require additional

protection against electrolyte leakage.

2.3.2.2 Alkaline electrolytes minimize acidification

of the electrolyte and minimize chlorine gas evolution on inert anodes. The following alkaline

solutions are suitable:

2.3.2.2.1 Saturated calcium hydroxide with

an excess of solid material to maintain the

saturation.

2.3.2.2.2 Lithium borate is suitable where

there is concern about ASR in the concrete.

NOTE: A 0.2M lithium borate solution can be

prepared by mixing 14.4 g LiOH and 12 g

H3BO3 per liter of water (0.12 lb LiOH and 0.1

lb H3BO3 per gallon). The volume required to

neutralize the acid generated by an inert

anode for a charge Q is given by Equation (1):

SP0107-2007

V = 6 x 10-7QA (1) Where:

V = Volume (liters)

Q = Charge (A-h/m2)

A = Area of steel to be treated (m2)

2.3.2.2.3 Lithium borate electrolytes must be

mixed, handled, and disposed of according to

national and local health and safety

regulations.

2.3.3 Anode and Electrolyte Containment

2.3.3.1 For all systems, provision shall be made

for electrolyte replenishment, topping, and

circulation as required.

The electrolyte solution shall be protected against

climatic changes (sun, rain, wind, frost, etc.).

2.3.3.2 Sprayed cellulose fiber (shredded paper)

shall be sprayed onto an anode mesh fixed onto

wooden battens at suitable separations. The

electrolyte is sprayed onto the anode

simultaneously with the cellulose fiber.

2.3.3.3 Felt cloth or matting is suitable for decks

or vertical surfaces. The anode is sandwiched

between layers of suitable geotextiles and

continuously wetted with the electrolyte. A

waterproofing layer shall be applied to the external

surface to prevent electrolyte evaporation or

dilution by rainwater.

2.3.3.4 Tanks with built-in anode mesh are

suitable anodes. These shall be tailored to the

structure with suitable seals to prevent electrolyte

loss.

2.3.3.5 A ponding system is suitable for decks

that are flat and level over the required anode

area. Protection shall be applied to prevent

electrolyte evaporation or dilution by rainwater.

2.3.3.6 Other water-retaining systems may be

used.

2.3.3.7 Ion exchange resins may be used to

control the concentration of chloride ions in the

electrolyte.

2.3.4 Power Supply and Control System

2.3.4.1 The power supply shall be an alternating

current (AC) input transformer-rectifier with an

isolating transformer or other suitable regulated

power supply. 2.3.4.2 The power supply shall meet national electrical code or other relevant authority codes, shall be fully protected against short circuit, and shall be suitable for continuous operation in the environment in which it is intended to operate.

2.3.4.3 In the event that AC power from the electrical grid/domestic supply is not available, an electrical generator is a suitable power supply input.

2.3.4.4 DC output terminals shall be clearly marked anode (+) and reinforcement (-). All anode cables (+) shall be colored red, and all reinforcement cables (-) shall be colored black or as required by the national electrical code.

2.3.4.5 All cables shall be insulated and shall be properly sized based on current, length of cable, expected temperature range, and exposure condition.

2.3.4.6 The output of the power supply shall have constant current control with a maximum voltage limit of 40 V DC. There shall be an indicator light for AC power-on, and there shall be suitable methods for measuring DC voltage and current for each anode zone or group of subzones.

2.4 Installation

2.4.1 Much of the preparation for ECE installation is

similar to impressed current CP (see NACE SP02901).

2.4.2 Electrical continuity: The electrical continuity

between all the steel reinforcement and other metal embedments intended to be treated shall be tested at a representative number of locations. A minimum of two connections per ECE treatment zone is usually required for redundancy.

2.4.3 Each ECE treatment zone shall be provided with

multiple connection points to the reinforcement steel.

2.4.4 Performance Monitoring

2.4.4.1 Each anode zone to be treated shall be

provided with the means necessary to monitor the

total charge in A-h and duration of the treatment.

2.4.4.2 Installations in an enclosed area shall

include means of monitoring, controlling, and

extracting the evolved hydrogen, oxygen, and

chlorine gas.

2.4.5 Installation of Anode System

2.4.5.1 The concrete surfaces shall be free of

electrically insulating contaminants before the

anode system is installed.

SP0107-2007

2.4.5.2 Particular care shall be taken to avoid

short circuits between the anodes and any metallic

items at the surface of the concrete.

2.4.5.3 The anode in each zone to be treated

shall be provided with multiple anode connections.

2.4.5.4 Installation work shall be in accordance

with applicable national electrical codes and safety

standards.

2.4.6 Preliminary Testing and Documentation

2.4.6.1 Prior to commissioning the installation, the

following preliminary testing shall be carried out

and the results documented.

2.4.6.1.1 Polarity checks on all circuits.

2.4.6.1.2 Electrical continuity shall be

checked by measuring the resistances of all

anode connections and all cathode

connections within each treatment zone.

2.4.6.1.3 Electrical insulation checks shall be

carried out on all circuits to ensure the

electrical insulation of the DC positive side

from the DC negative side and from any

metallic items on or adjacent to the concrete

surface (e.g., scaffolding).

2.4.6.1.4 After applying the electrolyte

solution, anode/cathode resistance and

potential shall be measured for each zone to

further check for short circuits, which shall be

corrected prior to energizing the system.

2.4.6.1.5 Any gas monitoring and extraction

system shall be checked prior to energizing

the ECE system.

2.5 Energizing and System Adjustment

2.5.1 This portion presents recommended procedures

for the energizing and adjustment of the ECE processes.

2.5.2 Component Installation Inspection and Testing

Prior to Energizing

2.5.2.1 The AC service system shall be inspected

for compliance with the national electrical code

and such local codes and ordinances that are

applicable or in force. It shall be verified that the

AC service voltage, phase, and wiring sizes are

suitable for the calculated expected load from the

system. In the event that the system is run with a

temporary supply, the system still shall comply

with the national electrical code and local codes

and ordinances.

2.5.2.2 The rectifier/DC power supply shall be

inspected. The integrity of all AC input and DC

output connections shall be verified. All

mechanical fasteners shall be inspected and

tightened or replaced if appropriate.

2.5.2.3 The anodes, including feed circuitry, shall

be visually inspected for proper installation. It shall

be established that no short circuits exist between

any anode material (including electrolyte) and any

metal embedments.

2.5.2.4 The electrical continuity between all the

steel reinforcement and other metal embedments

intended to be treated shall be tested at

representative locations.

2.5.2.5 Electrical isolation of metal mounted on,

in, or adjacent to the protected concrete structure

and not designed to be treated and within the ECE

electric field shall also be tested.

2.5.2.6 All monitoring devices and attendant

hardware shall be inspected for proper installation

and operation in accordance with the manufacturer’s instructions and design specifications.

2.5.2.7 Additional equipment and associated

components shall be inspected for proper

installation and operation in accordance with the

manufacturer’s instructions and design specifications.

2.5.3 System Energizing and Adjustment

2.5.

3.1 The ECE system shall be energized after

completion and acceptance of the component

installation inspection.

2.5.

3.2 Each rectifier shall be turned on and

operated at a low current, typically not more than

1,100 mA/m2 (100 mA/ft2) of the steel surface

area.

2.5.

3.2.1 Proper circuit polarity shall be

verified.

2.5.

3.2.2 The rectifier shall be tested for

proper operation. The accuracy of all rectifier

meters shall be verified with a calibrated

portable meter.

2.5.

3.2.3 Current distribution to all individual

anode feed circuits shall be determined.

NOTE: If panel boards for such testing were

not included in the system design, clamp-on

DC ammeters or other techniques shall be

used.

SP0107-2007

2.5.

3.3 After completion of the system energizing

inspection, the system shall be adjusted to the

required current or voltage. The system shall not

need further adjustment for the duration of the

treatment except under exceptional conditions.

2.5.

3.4 Tests shall be conducted to verify that

electrically isolated metal is not adversely affected

by stray current from the operation of the system.

NOTE: This may be done by measurement of the

potential shift, which should not exceed a

predetermined amount, e.g., 20 mV positive of the

rest potential.

2.6 Records

2.6.1 Records of the ECE process shall be maintained

at a minimum twice daily during the operation to ensure that accurate records of A-h are recorded. This provides reference to previously obtained data in the event that changes occur, troubleshooting is required, or modifications or additions are made to the system.

These records shall include all the physical, design, and test data accumulated on the installation.

2.6.2 The following information, collected during the

installation, shall be made an integral part of the record.

2.6.2.1 Results of chloride in concrete tests and

other chemical and physical tests and analyses.

2.6.2.2 Delamination survey data.

2.6.2.3 Depth-of-cover data.

2.6.2.4 Extent and location of concrete repair.

2.6.2.5 Steel surface area vs. concrete surface

area.

2.6.2.6 Electrical continuity and electrical isolating

data.

2.6.2.7 Current requirement data.

2.6.3 During installation of the system, certain tests shall be performed to ensure a quality installation. The following data shall be part of the records:

2.6.

3.1 Electrical continuity verification.

2.6.

3.2 Tests for electrical shorts.

2.6.

3.3 Tests for electrical isolation.

2.6.4 The following additional information, if available, shall be included in the permanent records of the system.

2.6.4.1 Tests conducted to determine that all

components are in working order prior to energizing.

2.6.4.2 Criterion compliance data.

2.6.4.3 Final rectifier data including voltage and

current outputs, mode of control including limits,

rectifier serial number, and AC and DC capacity.

2.6.4.4 Current density and distribution data.

2.6.5 Detailed as-built drawings and data shall be incorporated into the permanent records.

2.6.6 The operation and maintenance manual shall become a part of the permanent records for the system.

________________________________________________________________________

Section 3: Electrochemical Realkalization

3.1 Suitability for Treatment

A structure shall be suitable for ER if:

3.1.1 There is carbonation down to and approaching

reinforcement depth in sufficient locations to warrant

generalized treatment to retard further carbonation attack.

3.1.2 Water ingress can be controlled during treatment

so that the current density to the steel can be maintained and accurately monitored, especially in marine conditions. Realkalization is not suitable for

application to structural elements in splash and tidal

zones.

3.1.3 The area to be treated has no prestressed steel

susceptible to hydrogen embrittlement. Any

prestressed steel shall be monitored to ensure that its

potential does not go more negative than -1,100 mV vs.

a copper/copper sulfate reference electrode.

3.2 End Point Criteria

3.2.1 The criteria in this portion have been found to

achieve corrosion control for reinforcing steel embedded in atmospherically exposed concrete after the application of ER. Compliance with these criteria is

dependent on analysis of representative data in each

situation. The number and locations of measurements

made during data collection shall be commensurate with the complexity of the structure being protected.

Sampling plans shall be in accordance with ASTM E105.6 Sample size shall be determined in accordance

with ANSI/ASQ Z1.47 with the unit of product typically

being 0.836 m2 (1.00 yd2) of protected metal surface

SP0107-2007 area. For structures in which ER systems are divided

into discrete zones, testing inspection lots shall be

defined.

Acceptable quality and confidence levels shall also be

defined. Potentials of reinforcing steel or other embedments measured against portable reference electrodes shall be obtained in accordance with the techniques described in ASTM C876.8 Sign conventions for potential and current density as well as

conventions for graphical presentation of data shall be

in accordance with ASTM G3-89.9

3.2.2 NACE TG 054 developed these criteria through

evaluation of data obtained from successfully operated

ER systems. NOTE: Those using this standard shall review data made available after this standard’s publication to determine whether more effective criteria

have been established. It is not intended that those responsible for corrosion control be limited to these criteria if it can be demonstrated by other means that adequate corrosion control can be achieved. A combination of criteria may be used on a single structure.

3.2.3 In all cases, the current density shall not exceed

4 A/m2 (0.37 A/ft2) of steel surface area.

3.2.4 The voltage in the range 30 to 50 V DC.

3.2.5 Electrochemical Realkalization Criteria – At

least one of criteria A or B below (Paragraphs 3.2.5.1

and 3.2.5.2) shall be used subject to Paragraphs 3.2.3

and 3.2.4 above.

3.2.5.1 Criterion A—Amp hours per square meter

(per square foot): This criterion ensures a

minimum treatment of charge density per unit area

of steel. NOTE: A treatment of 200 A?h/m2 (19 A-

h/ft2) delivered to the steel surface is a suitable

minimum target.

3.2.5.2 Criterion B—pH Level: The effectiveness

of the ER process is demonstrated by pH testing

using phenolphthalein solution in each anode zone

with the extent of ER indicated by pink coloration

surrounding the reinforcement to a minimum of 10

mm (0.4 in.) or the bar diameter, whichever is

greater. NOTE: BSEN 14630,14 is a suitable

method for preparing the phenolphthalein solution

and measuring carbonation depth.

3.3 Design

3.3.1 Anode Systems

3.3.1.1 Anode systems shall be mild steel or

catalyzed titanium.

3.3.1.2 Mild steel anodes are suitable for

structures when staining of the concrete surface is

not a concern.

Mild steel anodes shall be welded wire fabric.

NOTE: A suitable steel mesh is 8 to 10 diameter (3

to 4 mm [0.12 to 0.16 in.]) wire on a 50 x 50 or 100

x 100 mm (2 x 2 in. or 4 x 4 in.) mesh size.

3.3.1.3 Mild steel anodes shall be fixed away from

the concrete surface so that the steel does not

come in direct contact with the concrete surface.

Electrical anode wires shall be attached to cleaned

surfaces of the steel anodes by a firm mechanical

bond, and the connections shall be sealed to

prevent corrosion during treatment. NOTE: If

staining of the concrete surface occurs, a suitable

method for removing discoloration is by a light

abrasive blast following treatment.

3.3.1.4 Catalyzed titanium anodes shall be used

when staining of the concrete is a concern, and

when pH of the electrolyte can be carefully

monitored to prevent acidification and possible

chlorine evolution.

3.3.1.

4.1 The anodes shall be in the form

of a flexible, highly expanded mesh that

conforms easily to concrete surfaces.

3.3.1.

4.2 The anodes shall, as a

minimum, comply with the requirements of

NACE TM0294.12

3.3.1.

4.3 Anode wires shall be attached

to an ASTM B26513 Grade 1 titanium

current distributor bar outside the

electrolyte. The current distributor bar

shall in turn distribute current to the

catalyzed titanium anode by resistance-

welded connections extending the length

of the anode.

3.3.1.

4.4 When catalyzed titanium

anodes are used, the electrolyte shall be

buffered, or alkali shall be periodically

added to the electrolyte to prevent the

electrolyte from dropping below pH 7.

3.3.2 Electrolytes

3.3.2.1 Alkaline electrolytes are generally

beneficial to the performance of the system, to

minimize the risk of etching of the concrete surface

and to minimize chlorine gas evolution on inert

anodes. The following alkaline solutions are

suitable. NOTE: certain fixtures and fittings to

structures such as window frames, light fittings,

and railings may be subject to attack from alkaline

or acidified electrolytes and may require additional

protection against electrolyte leakage.

SP0107-2007

3.3.2.1.1 Potassium carbonate is a

suitable electrolyte for ER. A 1M solution

is suitable and is made from 107 g of

Na2CO3 per liter (0.89 lb/gal) of water.

3.3.2.1.2 The volume required to

neutralize the acid generated by an inert

anode for a charge Q is given by Equation

(2):

V = 1.2 x 10-7QA (2) Where:

V = volume (liters)

Q = Charge (A-h/m2)

A = Area of steel to be treated (m2)

3.3.3 Anode and Electrolyte Containment

3.3.3.1 For all systems, provision shall be made

for electrolyte replenishment, topping, and circulation as required.

3.3.3.2 The electrolyte solution shall be protected

against climatic changes (sun, rain, wind, frost,

etc.).

3.3.3.3 Sprayed cellulose fiber (shredded paper)

shall be sprayed onto an anode mesh fixed onto

wooden battens as suitable separations. The

electrolyte is sprayed onto the anode simultaneously with the cellulose fiber.

3.3.3.4 Felt cloth or matting is suitable for decks

or vertical surfaces. The anode shall be

sandwiched between layers of suitable geotextiles

and continuously wetted with the electrolyte. A

waterproofing layer shall be applied to the surface

to prevent electrolyte evaporation or dilution by

rainwater.

3.3.3.5 Tanks with built-in anode mesh are

suitable systems. These shall be tailored to the

structure with suitable seals to prevent electrolyte

loss.

3.3.3.6 A ponding system is suitable for decks

that are flat and level over the required anode

area. Protection shall be applied to prevent

electrolyte evaporation or dilution by rainwater.

3.3.4 Power Supply and Control System

3.3.

4.1 The power supply shall be an AC input

transformer-rectifier with an isolating transformer

or other suitable regulated DC power supply.

3.3.

4.2 The power supply shall meet national

electrical code and other relevant authority codes,

shall be fully protected against short circuits, and

shall be suitable for continuous operation in the

environment in which it is intended to operate.

3.3.

4.3 In the event that AC power from the

electrical grid/domestic supply is not available, a

suitable power supply input is an electrical

generator. DC output terminals shall be clearly

marked anode (+) and reinforcement (-).

3.3.

4.4 All anode cables (+) shall be colored red,

and all reinforcement cables (-) shall be colored

black. All cables shall be insulated and shall be

properly sized based on current, length of cable,

and expected temperature range.

3.3.

4.5 The output of the power supply shall have

constant current control with a maximum voltage

limit of 40 V DC. There shall be an indicator light

for AC power-on, and there shall be meters for DC

voltage and current for each anode zone or group

of subzones.

3.4 Installation

3.4.1 Much of the preparation for ER is the same as

for impressed current CP (see NACE SP02901).

3.4.2 Electrical continuity: The electrical continuity of

reinforcement shall be tested at a minimum of two locations per zone before applying realkalization treatment.

3.4.3 Each zone to be treated with ER shall be

provided with multiple connection points to the reinforcement steel.

3.4.4 Performance Monitoring

3.4.4.1 Each anode zone to be treated shall be

provided with the means necessary to monitor the

total charge in A-h and duration of the treatment.

3.4.4.2 Installation in an enclosed area shall

include means of monitoring, controlling, and

extracting any evolved hydrogen, oxygen, or other

evolved gas.

3.4.5 Installation of Anode System

3.4.5.1 The concrete surfaces shall be free of

electrically insulating contaminants before the

anode system is installed.

3.4.5.2 Particular care shall be taken to avoid

short circuits between the anodes and any metallic

items at the surface of the concrete.

3.4.5.3 The anode in each zone to be treated

shall be provided with multiple anode connections.

SP0107-2007

3.4.5.4 Installation work shall be undertaken in

accordance with applicable national electrical

codes and safety standards.

3.4.6 Preliminary testing and documentation

3.4.6.1 Prior to commissioning the installation,

the following preliminary testing shall be carried

out and the results documented.

3.4.6.2 Electrical continuity shall be checked by

measuring resistances of all anode connections

and all cathode connections within each

treatment zone.

3.4.6.3 Electrical insulation checks shall be

carried out on all circuits to ensure the electrical

insulation of the DC positive side from the DC

negative side and from any metallic items on or

adjacent to the concrete surface (e.g.,

scaffolding).

3.4.6.4 After applying the electrolyte solution,

anode/cathode resistance and potential shall be

measured for each zone to further check for short

circuits, which shall be corrected prior to

energizing the system.

3.4.6.5 Any gas monitoring and extraction

system shall be checked prior to monitoring the

ER system.

3.5 Energizing and System Adjustment

3.5.1 This portion presents recommended procedures

for the energizing and adjustment of the ER processes.

3.5.2 Component Installation Inspection and Testing

Prior to Energizing

3.5.2.1 The AC service to the system shall be

inspected for compliance with the national

electrical code and such local codes and

ordinances that are applicable or in force. It shall

be verified that the AC service voltage, phase,

and wiring sizes are suitable for the calculated

expected load from the system. In the event that

the system is run with a temporary supply, the

system still shall comply with the national

electrical code and all codes and ordinances.

3.5.2.2 The rectifier/power supply shall be

inspected. The integrity of all AC input and DC

output connections shall be verified. All

mechanical fasteners shall be inspected and

tightened or replaced, if appropriate.

3.5.2.3 The anodes, including feed circuitry, shall

be visually inspected for proper installation. It

shall be established that no short circuits exist

between any anode material (including

electrolyte) and any metal embedments.

3.5.2.4 The electrical continuity between steel

reinforcement and other metal embedments

intended to be treated shall be tested at

representative locations.

3.5.2.5 Electrical isolation of metal mounted on,

in, or adjacent to the protected concrete structure

and not designed to be treated and within the

electrical field shall also be tested.

3.5.2.6 All monitoring devices and attendant

hardware shall be inspected for proper

installation and operation in accordance with the

manufacturer’s instructions and design specifications.

3.5.2.7 Additional equipment and associated

components shall be inspected for proper

installation and operation in accordance with the

manufacturer’s instructions and design specifications.

3.5.3 System Energizing and Adjustment

3.5.3.1 The ER system shall be energized after

completion of the component installation

inspection. Each rectifier shall be turned on and

operated at a low current, typically not more than

1,100 mA/m2 (100 mA/ft2) of the steel surface

area. During this initial energizing period, all

circuits shall be tested.

3.5.3.1.1 Proper circuit polarity shall be

verified.

3.5.3.1.2 The rectifier shall be tested for

proper operation. The accuracy of all

rectifier meters shall be verified with a

calibrated portable meter.

3.5.3.1.3 Current distribution to all individual

anode feed circuits shall be determined. If

panel boards for such testing were not

included in the system design, clamp-on DC

ammeters or other techniques shall be used.

3.5.3.2 Tests shall be conducted to verify that

electrically isolated metal is not adversely

affected by stray current from the operation of the

system. NOTE: This may be done by

measurement of the potential shift, which should

not exceed a predetermined amount, e.g., 20 mV

positive of the rest potential.

3.5.3.3 After completion of the system energizing

inspection, the system shall be adjusted to the

required current or voltage. The system shall not

SP0107-2007

need further adjustment for the duration of the

treatment except under unusual conditions.

3.6 Records

3.6.1 Records of the ER process shall be maintained

at a minimum twice daily during the operation to ensure

that accurate records of A-h are recorded. This

provides reference to previously obtained data in the

event that changes occur, troubleshooting is required,

or modifications or additions are made to the system.

These records shall include all the physical, design,

and test data accumulated on the installation.

3.6.2 The following information, collected during the

installation, shall be made an integral part of the record.

3.6.2.1 Results of chloride in concrete tests and

other chemical and physical analyses.

3.6.2.2 Delamination survey data.

3.6.2.3 Depth-of-cover data.

3.6.2.4 Extent and location of concrete repair.

3.6.2.5 Steel surface area vs. concrete surface

area.

3.6.2.6 Electrical continuity and electrical

isolating data.

3.6.2.7 Current requirement data. 3.6.3 During installation of the system, certain tests shall be performed to ensure a quality installation. The following data shall be part of the records:

3.6.3.1 Electrical continuity verification.

3.6.3.2 Tests for electrical shorts.

3.6.3.3 Tests for electrical isolation.

3.6.4 The following additional information, if available, shall be included in the permanent records of the system:

3.6.

4.1 Tests conducted to determine that all

components are in working order prior to

energizing.

3.6.

4.2 Criterion compliance data.

3.6.

4.3 Final rectifier data including voltage and

current outputs, mode of control including limits,

rectifier serial number, and AC and DC capacity.

3.6.

4.4 Current density and distribution data.

3.6.5 Detailed as-built drawings and data shall be incorporated into the permanent records.

3.6.6 The operation and maintenance manual shall become a part of the permanent records for the system.

________________________________________________________________________

References

1. NACE SP0290 (latest revision), “Impressed Current Cathodic Protection of Reinforcing Steel in Atmospherically Exposed Concrete Structures” (Houston, TX: NACE).

2. NACE Publication 01101 (latest revision), “Electrochemical Chloride Extraction form Steel Reinforced ConcreteA State-of-the-Art Report” (Houston, TX: NACE).

3. NACE Publication 01104 (latest revision), “Electrochemical Realkalization of Steel Reinforced Concrete—A State-of-the-Art Report” (Houston, TX: NACE).

4. NACE Standard RP0187 (latest revision), “Design Considerations for Corrosion Control of Reinforcing Steel in Concrete” (Houston, TX: NACE).

5. NACE Standard RP0390 (latest revision), “Maintenance and Rehabilitation Considerations for Corrosion Control of Atmospherically Exposed Existing Steel Reinforced Concrete Structures” (Houston, TX: NACE).

6. ASTM E105 (latest revision), “Standard Practice for Probability Sampling of Materials” (West Conshohocken, PA: ASTM).

7. ANSI/ASQ Z1.4 (latest revision), “Sampling Procedures and Tables for Inspection by Attributes” (New York, NY: ANSI).

8. ASTM C876 (latest revision), “Standard Test Method for Half-Cell Potentials of Uncoated Reinforcing Steel in Concrete” (West Conshohocken, PA: ASTM).

9. ASTM G3-89 (latest revision), “Standard Practice for Conventions Applicable to Electrochemical Measurements

in Corrosion Testing” (West Conshohocken, PA: ASTM).

10. ASTM C1152/C1152M-04e1 (latest revision), “Standard Test Method for Acid-Soluble Chloride in Mortar and Concrete” (West Conshohocken, PA: ASTM).

11. L. Cáseres, A.A. Sagüés; S.C. Kranc: and R.E. Weyers. “In Situ Leaching Method for Determination of

SP0107-2007

Chloride in Pore Water.” Cement and Concrete Research 36 (2006): pp. 492 to 503.

12. NACE Standard Test Method TM0294 (latest revision), “Testing of Embeddable Impressed Current Anodes for Use in Cathodic Protection of Atmospherically Exposed Steel-Reinforced Concrete” (Houston, TX: NACE). 13. ASTM B265 (latest revision), “Standard Specification for Titanium and Titanium Alloy Strip, Sheet, and Plate” (West Conshohocken, PA: ASTM).

14. BSEN 14630 (latest version), “Determination of Carbonation Depth in Hardened Concrete” (London, UK: British Standards Institute).

_______________________________________________________________________________

Bibliography

Banfill, P.F.G. “Features of the Mechanism of Realkalisation and Desalination Treatments for Reinforced Concrete.” Corrosion and Corrosion Protection of Steel in Concrete, R.N. Swamy ed.,

Sheffield Academic Press, Vol. 2, 1994, pp. 1489-1498. Bennett, J.E., and T.J. Schue. Chloride Removal Implementation Guide. Strategic Highway Research

Program Report SHRP-S-347, 1993, National Research Council, Washington, DC.

Broomfield, J.P., and N.R. Buenfeld. Effect of Electrochemical Chloride Extraction on Concrete Properties: Investigation of Field Concrete.

Transportation Research Record, No 1597, 1997, pp.

77-81.

Broomfield, J.P., and N.R. Buenfeld. Electrochemical Chloride Extraction For Reinforced Concrete Structures

- Advantages and Limitations. Australasian Corrosion

Association Conference Proceedings, 1998.

Buenfeld, N.R., and J.P. Broomfield. Effect of Chloride Removal on Rebar Bond Strength and Concrete

Properties. Corrosion and Corrosion Protection of

Steel in Concrete, Vol. 2, Ed. R.N. Swamy, London,

UK, Sheffield Academic Press, 1994, pp. 1438-1450. Buenfeld, N.R., and J.P. Broomfield. Influence of Electrochemical Chloride Extraction on the Bond

between Steel and Concrete. Magazine of Concrete

Research 52, 2 (2000): pp. 79-91. Glass, G.K., A.C. Roberts, and N. Davison. “Achieving High Chloride Threshold Levels on Steel in Concrete.”

CORROSION/2004, paper no 332. Houston, TX: NACE, 2003.

Glass, G.K., and N.R. Buenfeld. The Inhibitive Effects of Electrochemical Treatment Applied to Steel in Concrete. Corrosion Science 42, 6 (2000): pp. 923-

927.

Glass, G.K., J. Taylor, A. Roberts, and N. Davison. “The Protective Effects of Electrochemical Treatment in Reinforced Concrete.” CORROSION/2003, paper no.

291. Houston, TX: NACE, 2003.

Hassanein, A.M., G.K. Glass G.K., and N.R. Buenfeld. “A Mathematical Model for Electrochemical Removal of

Chloride from Concrete Structures.” Corrosion 54, 4

(1998).

Mietz, J. Electrochemical Rehabilitation Methods for Reinforced Concrete Structures - A state-of-the-art-

report. Frankfurt, Germany. European Federation of

Corrosion/Institute of Materials, publication no. 24, 1998.

Miller, J.B. The Perception of the ASR Problem with Particular Reference to Electrochemical Treatments of

Reinforced Concrete. Corrosion of Reinforcement in

Concrete - Monitoring, Prevention and Rehabilitation.;

Frankfurt, Germany. European Federation of Corrosion, publication no. 25: 1997, pp. 141 to 149.

SP0107-2007

相关主题