FWK-F型失步振荡解列装置原理及使用说明书

FWK-F型失步振荡解列装置原理及使用说明书
FWK-F型失步振荡解列装置原理及使用说明书

目录

第一部分FWK-F失步解列柜 .................................................................................. 3

一、概述 ................................................................................................................ 3

二、用途与功能 ...................................................................................................... 41UFV-2F型装置主要功能..................................................................................... 42其他功能........................................................................................................... 4三、装置输入的模拟量及电气量测量方法.................................................................. 51装置输入的模拟量 ............................................................................................. 52电气量测量方法................................................................................................. 5四、主要技术参数 ................................................................................................... 51额定参数........................................................................................................... 62过载能力........................................................................................................... 63整屏功率消耗.................................................................................................... 64整定围 .............................................................................................................. 65动作时间........................................................................................................... 66返回系数........................................................................................................... 67测量精度........................................................................................................... 68事件记录及数据记录.......................................................................................... 79装置输入量 ....................................................................................................... 710装置输出量 .................................................................................................... 711介质强度和绝缘电阻 ....................................................................................... 812抗干扰性能 .................................................................................................... 813使用环境条件 ................................................................................................. 8第二部分UFV-2F型失步振荡解列装置.................................................................... 9

一、用途及主要功能................................................................................................ 9

二、失步解列的判别方法(工作原理) ................................................................. 101概述 ............................................................................................................. 102系统失步振荡过程中相位角的变化规律 ........................................................... 103相位角失步振荡判据...................................................................................... 154保护区围的判断及选择性配合......................................................................... 175装置启动判据:相位角启动或功率突变量启动 ................................................. 18

6闭锁判据 ...................................................................................................... 197事故前潮流方向判据..................................................................................... 198相位角判据的优点 ......................................................................................... 209失步解列判别框图 ......................................................................................... 20三、装置的硬件配置............................................................................................ 231装置的硬件框图............................................................................................. 232装置的结构及正面布置................................................................................... 233输出中间板(SZ) ......................................................................................... 244出口继电器板(CKZ) ................................................................................... 265打印接口板(DYK) ...................................................................................... 276装置的背板配线图 ......................................................................................... 27四、装置的显示菜单............................................................................................ 281装置的软件结构............................................................................................. 282主菜单 .......................................................................................................... 283当前状态显示菜单 ......................................................................................... 294定值设置菜单................................................................................................ 305事件记录显示 ............................................................................................... 326数据记录显示 ............................................................................................... 337装置动作后的显示(事故屏幕) ..................................................................... 348打印选择菜单(召唤打印)............................................................................ 349时钟设置菜单................................................................................................ 3510装置的整组试验菜单 ................................................................................... 3511“关于本装置”菜单...................................................................................... 36五、防止误动作的闭锁措施(装置的回路自检).................................................... 37第三部分现场安装调试、运行与维护.................................................................. 39

一、现场安装调试 ............................................................................................... 39

二、现场运行与维护............................................................................................ 40第四部分附图:接线原理图 ......................................... E RROR!B OOKMARK NOT DEFINED.

第一部分

FWK-F 失步解列柜 一、概述

该装置所适用的厂站系统接线图

当变电站/电厂与主系统失去同步,发生失步振荡时,系统在失步过程中某些地区,尤其是振荡中心附近的电压、频率将大幅度变化,对用电负荷的安全威胁很大,甚至引起大面积停电事故。因此应安装一面FWK-F 失步解列柜,要求系统发生振荡事故时解列线路(旁代运行时解列旁路)。

母联

Ⅰ母

Ⅱ母 主变 旁路

主变

二、用途与功能

1 UFV-2F型装置主要功能

装置的单元处理机1DCJ、2DCJ分别测量线路、旁路的三相电压、三相电流、有功功率和相位角。正常情况下,用线路电气量判失步;投上旁代压板时,装置自动转用旁路电气量判失步。当系统失去同步,发生振荡时,若振荡中心落在预定的动作围,装置根据相位角振荡判据,振荡周期次数,有选择地切除联络线本侧或旁路开关,并另输出接点闭锁重合闸。另外预留六对备用出口。

2 其他功能

2.1 UFV-2F装置能自动记录两次事故过程中电压、电流、功率、相位角的变化(事故记录和数据记录),便于事故分析和掌握事故时的动态过程。记录容在断电后不会消失。

2.2 屏上配一个带汉字库的打印机,事故后自动打印出事故记录和数据记录。

2.3 UFV-2F装置带有RS-485串行通讯口,可将有关信息上送监控系统。

2.4 UFV-2F装置具有GPS脉冲自动对时功能,可保证时钟回路计时准确,避免累计误差。

2.5 采用3U0、3I0、失压等多种闭锁措施,以防止由于短路故障、PT断线、CT断线或电压异常情况可能引起的误动作,并发中央告警信号。

2.6 具有完善的自检措施及整组自试功能,使现场运行维护更为简单、方便。正常运行自检发现异常后会闭锁出口并发中央告警信号,保证了装置的安全性。

2.7 主机板上具有滤除高次谐波的二阶带通滤波器,可有效防止冲击负荷、电气化铁路等谐波源的影响。

2.8 装置的电压电流定值、功率定值及时间定值均连续可调。此外,定值显示及设定修改方便、准确、直观,定值存放在E2PROM,断电后定值不会消失。面板上设有定值允许设置开关,只有该开关拨在“允许”位置时才能写进新的定值;定值设置开关在“允许”位置时,装置不进行事故判断,定值修改完毕后必须及时将该开关拨回“禁止”位置;并且仅在设置开关拨回“禁止”位置时方可返回主菜单。

2.9 装置面板上的信号灯可准确反映出装置的运行、启动、动作、异常等情况。

2.10通过装置面板上的9个按键,可以选择各种显示菜单、修改整定值、设定日期时间、召唤打印、结束打印、进行整组检查试验及动作信号的复归。

2.11 通过装置面板上的液晶显示屏以菜单方式显示时间、正常运行测量值、整定值、事件记录及数据记录等。自检发现异常或装置动作后,均会立即发出中央告警信号,并在当前显示菜单屏幕上显示异常的容,或自动停止显示当前菜单,改为显示动作的容。UFV-2F装置采用汉字显示方式。

三、装置输入的模拟量及电气量测量方法

1 装置输入的模拟量

UFV-2F 型装置测量线路的三相电压(U A 、U B 、U C 、U N )、三相电流(I A 、I B 、I C 、I N )、旁路的三相电压(PU A 、PU B 、PU C 、PU N )、三相电流(PI A 、PI B 、PI C 、PI N )、有功功率和相位角。

直流电源通过屏后抗干扰端子后,再引入装置。抗干扰端子部装有一个电容(C=0.1μf ,耐压3kV ),用以滤去高频干扰,防止电压、电流回路的干扰电压侵入微机装置部。

交直流电压通过空气开关1ZK ~3ZK 再和装置相连。ZK 是具有高分断能力的空气开关,具有过流反时限脱扣性能和短路瞬时脱扣性能,用以防止短路事故损坏装置、外部PT 或直流电源设备。

2 电气量测量方法

2.1 电压、电流、功率的测量方法

装置的微机部分对输入的交流电压U A 、U B 、U C 及交流电流I A 、I B 、I C 的瞬时值进行采样,采样周期为1.667ms (20ms 采样12点),然后按以下算法计算出电压、电流有效值、有功功率值。

U AK =

∑=1212121u k AK kV 3U0=∑=++121

k )(2121u u u CK BK AK kV (相当3U0=U A +U B +U C )

I AK =

∑=1212121i k AK A 3I0=∑=++121k )(2121i i i CK BK AK

A (相当=I A +I

B +I

C ) P =∑++=12

1K )i u i u i u (121C C B B A A k MW

(三相对称时,P =3U AK I AK Cos φ)

2.2 相位角φ的测量方法

2F 装置相位角的测量方法:先计算出有功功率P 及无功Q ,再用以下公式求出φ。这一测量方法具有良好的连续性及抗扰动性。

相位角φ:tg φ = Q / P

四、主要技术参数

1 额定参数

a.交流电流:5A/1A。CT变比在定值设置时,只需将CT一次侧额定电流值I N输入即可。

b. 交流电压:相电压100/3V。PT变比在定值设置时,只需将PT一次侧额定相电压值U N输入即可。

变比正确设定后,装置显示的电压、电流、功率值为实际系统的一次值。

c. 频率:50Hz。

d. 直流电源电压:220V/110V。

2 过载能力

a. 交流电流回路:2倍额定电流,连续工作;

10倍额定电流,允许10秒;

40倍额定电流,允许1秒。

b. 交流电压回路:1.2倍额定电压,连续工作。

c. 直流电源回路:80%~120%额定电压,连续工作。

3 整屏功率消耗

a. 交流电流回路:额定电流时,每相不大于1VA。

b. 交流电压回路:额定相电压时,每相不大于1VA。

c. 直流电源回路:正常工作时,不大于30W;

出口动作时,不大于50W。

4 整定围

a. 电压整定围:20~100%U N。

b. 电流整定围:20~120%I N。

c. 功率定值整定围:5~100%P N。

5 动作时间

失步振荡判出时间:相位角原理判据一般需0.66~0.7个振荡周期,解列出口的延时以振荡周期次数N进行整定,一般整定Ns=3~4。失步解列出口接点在振荡平息后(即解列后)延时6秒返回。

6 返回系数

a. 电压返回系数:不大于1.05。

b. 电流返回系数:不小于0.89。

7 测量精度

a. 电压有效值测量相对误差小于±1%。

(电压20~120% U N,频率49~51 Hz)

b. 电流有效值测量相对误差小于±2%。

(电流0.2~1.2 I N,频率49~51 Hz)

c. 有功功率测量相对误差小于2%

(电压20~120% U N,电流0.2~1.2 I N,频率49~51 Hz)

d. 相位角测量误差小于2度

e. 动作延时时间误差小于0.02 秒(0.1~99.9秒围)

8 事件记录及数据记录

装置具有事件记录和数据记录功能,可存贮两次记录容,该记录容在断电后不丢失。8.1 装置可连续记录两次事件(当前事件记录和上次事件记录),容包括发生的动作事件及发生时间。

8.2 装置可连续记录两次事件的数据(当前数据记录和上次数据记录),记录时间长度为启动前-0.2秒至启动后50秒钟。数据记录在存中步长为0.02秒一点,但在打印或阅读液晶屏的数据记录时,可在定值菜单中“数据阅读间隔”一项选择所需的时间间隔变化倍数,共有1、2、5、10四档,即数据记录有0.02秒、0.04秒、0.1秒、0.2秒四种间隔供选择。

9 装置输入量

9.1 模拟量见附图1、附图2及“三、装置输入的模拟量及电气量测量方法”的说明。

9.2 输入开关量(见附图3)

开入1:供接入自动对时GPS脉冲信号用,使用DC24V光隔端子,用以隔离装置部电源和外施GPS信号电源之间的联系。

开入2:屏面上失步解列功能投退压板1SLP。使用失步解列功能时应投入压板。

开入3:信号复归开关量,即装于屏面上手动复归按钮的常开接点,用来复归装置部自保持信号继电器及动作后液晶屏所显示的动作容。

开入4:屏面上旁代功能投退压板2SLP。线路正常运行时,应退出压板2SLP;当线路由旁路代送时,应投上压板2SLP。

10 装置输出量

10.1中央信号输出接点(见附图4)

2F装置输出动作信号(XJ2)、PT断线信号(PTJ2)、异常信号(YJ2)、直流电源消失(DY)各一对接点,另外输出一对动作信号接点(XJ1)供遥信用。动作信号(XJ1、XJ2)由运行人员手动复归,其余信号在该状态消除后自动复归。Ⅰ~Ⅴ功能输出信号指示灯和

出口继电器板的出口指示灯均为动作自保持指示灯,亦由运行人员手动复归。

10.2出口继电器及输出接点(见附图5)

UFV-2F装置有2×4个出口继电器。本柜出厂时,将继电器1CKJ~4CKJ接于Ⅰ轮、5CKJ~8CKJ接于Ⅱ轮。即装置判出线路失步动作出口时,装置输出Ⅰ轮,1CKJ~4CKJ动作闭合;判出旁路失步动作出口时,装置输出Ⅱ轮,5CKJ~8CKJ动作闭合。

每个出口继电器输出两对接点,一对接点作用于线路的跳闸,另一对接点供该线路的重合闸装置放电用。

出口跳闸接点及重合闸放电接点均允许接通5A。由于出口跳闸接点配置有电流自保持继电器,所以出口跳闸接点可以经保护装置的操作箱回路作用于断路器跳闸线圈,也可直接作用于断路器跳闸线圈。

由于中央信号继电器输出接点断弧容量只有10W,故要求现场中央信号灯应为节能光字牌。若为大功率白炽灯,需增加重动继电器扩大断弧容量。

11 介质强度和绝缘电阻

屏的直流电源输入端子,交流电压、电流输入端子、输出接点端子之间,以及上述所有端子与地(即对屏柜外壳)之间,应能承受2000V(有效值)50Hz的交流电压历时1分钟试验并且无绝缘闪络或击穿现象。上述各部分之间用1000V兆欧表测量的绝缘电阻应不小于10MΩ。

试验时应将屏上抗干扰端子的接地线拆去,以使其部的抗干扰电容和地端断开。另外,开入1(GPS对时信号)及串行接口系弱电回路,耐压试验电压不应超过500V,为防止损坏装置的弱电部分,现场不需测试。

12 抗干扰性能

抗干扰性能符合GB6162《静态继电器及保护装置的电气干扰试验》的有关要求,并符合IEC255-22及国家标准的有关要求。

13 使用环境条件

环境温度-10℃~+50℃

相对湿度≤95%

大气压力80~110 kPa

海拔高度≤2kM

RCS 一993型失步解列装置运行规程

RCS 一993型失步解列装置运行规程本规程根据厂家提供的图纸和说明书,并依据国家相关的规程规定编写,适用于南煤龙川发电有限公司的失步解列保护。 14.1 设备简介 RCS-993型失步解列装置作为电力系统失步时的跳闸启动装置,当电力系统失步时,做出相应的处理:解列、切机、切负荷或启动其它使系统再同期的控制措施。 14.2 保护装置介绍 14.2.1 装置指示灯 “运行”灯为绿色,装置正常运行时点亮; “TV断线”灯为黄色,当发生电压回路断线时点亮; “TA断线”灯为黄色,当发生电流回路断线时点亮; “装置异常”灯为黄色,当装置异常时点亮; “跳闸”灯为红色,当保护动作出口点亮,在“信号复归”后熄灭。 14.2.2 按钮和开关 14.2.2.1 装置前面的按钮 保护复归按钮(1FA)用于复归RCS-993A保护信号。 打印按钮(1YA)用于RCS-993A保护装置动作后打印信息。 14.2.2.2 装置背后的开关 装置电源开关:用于给装置供电的,装置启动前投入此开关。 220KVPT开关:220KV电压互感器来的电压信号开关,保护投入前投入此开关。 14.2.3 装置保护压板 “检修状态”:投入此压板时,保护装置动作时不发出告警和动作信号。 “投211线路失步解列”:投入此压板时,失步解列保护投入。 “RCS-993跳201开关出口Ⅰ”:投入此压板时,保护装置动作时跳RCS-993跳201开关跳闸线圈Ⅰ。 “RCS-993跳201开关出口Ⅱ”:投入此压板时,保护装置动作时跳RCS-993跳201开关跳闸线圈Ⅱ。 “RCS-993跳202开关出口Ⅰ”:投入此压板时,保护装置动作时跳RCS-993跳202

机械原理练习题定稿版

机械原理练习题 HUA system office room 【HUA16H-TTMS2A-HUAS8Q8-HUAH1688】

八、(13分)已知某机械一个稳定运动循环内的等效阻力矩r M 如图所示,等效驱 动力矩d M 为常数,等效构件的最大及最小角速度分别为:rad/s 200max =ω及 rad/s 180min =ω。试求: (1)等效驱动力矩M d 的大小; (2)运转的速度不均匀系数δ; (3)当要求δ在0.05范围内,并不计其余构件的转动惯量时,应装在等效构件 上的飞轮的转动惯量J F 。

八、13分。(1)3分;(2)3分;(3)3分;(4)4分 (1)22d r 00 d d M M ππφφ=?? ?d 1 71000100212.5244M πππ??=?+?= ??? N ?m (2)()()1901802002 121min max m =+=+=ωωω rad/s (3)() max 7212.5100618.501054W π?=-= J (4)J W F max m 2 ...==?=?ωδ6185190005 034272 kg ?m 2

八、(13分)一机械系统,当取其主轴为等效构件时,在一个稳定运动循环中,其等效阻力矩M 如图所示。已知等效驱动力矩为常数,机械主轴的平均转速为 r 1000r/min。若不计 其余构件的转动惯量,试问: =? 的飞 (1)当要求运转的速度不均匀系数δ≤005 .时,应在主轴上安装一个J F 轮; (2)如不计摩擦损失,驱动此机器的原动机需要多大的功率N (kW ) ?

9612A_04842故障解列装置说明书

RCS-9612A_04842故障解列保护装置 2007-06-05(V3.35.7) 1基本配置及规格 1.1基本配置 RCS-9612A_04842是适用于110KV以下电压等级的负荷侧或小电源侧的故障解列装置,可在开关柜就地安装。当使用该装置低压解列功能时,要特别注意PT断线的判别,具体见2.3.6。 保护方面的主要功能有: 1)二段零序过压解列保护; 2)二段低压解列保护; 3)二段低周解列; 4)二段母线过压解列保护; 5)二段高周解列; 6)独立的操作回路(使用无源接点,取消了事故总和控制回路断线报警)及故障录波。 测控方面的主要功能有: 1)4路遥信开入采集、装置遥信变位、事故遥信; 2)正常断路器遥控分合; 3)U AB、U BC、U CA、U0、I A、I C、F、P、Q、COSф等模拟量的遥测; 4)开关事故分合次数统计及事件SOE等; 5)提供“保护动作信号”虚遥信,装置保护动作后置1,信号复归后清0 1.2 技术数据 1.2.1额定数据 直流电源: 220V,110V 允许偏差 +15%,-20% 交流电压: 100/3V,100V 交流电流: 5A,1A 频率: 50Hz 1.2.2 功耗: 交流电压: < 0.5VA/相 交流电流: < 1VA/相 (In =5A) < 0.5VA/相 (In =1A) 直流回路:正常 < 15W 跳闸 < 25W 1.2.3主要技术指标 ③低周解列 低周定值:45Hz~50Hz 低压闭锁:10V~90V df/dt闭锁:0.3Hz/s~10Hz/s 定值误差:< 5% 其中频率误差:< 0.01Hz ④遥测量计量等级:电流 0.2级 其他: 0.5级 ⑤遥信分辨率: <2ms 信号输入方式:无源接点

机械原理设计说明书

课程设计说明书 设计题目:工件间歇输送机构 专业:机械设计制造及其自动化 班级: 设计人: 指导老师: 2011 年 7 月 6 日 课程设计说明书 学院专业班级

一、课程设计题目:工件间歇输送机构 二、课程设计主要参考资料 [1] 课程设计指导书 [2] 安子军机械原理[M].7版. 国防工业,2009 [5] 成大先. 机械设计手册[M].化学工业 2010 三、课程设计应解决主要问题 (1)通过机构设计满足间歇输送工件的运动要求 (2)优化结构设计,提高可行性以及机构工作的稳定性 四、成员分工 方案一: 方案二: 方案三: 四、课程设计相关附件(如:图纸、软件等) (1)A2构件图 (2)课程设计说明书一份 (3)方案构件图三份 3D仿真图三

目录 1 课程设计任务 (3) 1.1设计题目 (3) 1.2设计要求 (3) 2机械系统运动功能系统图 (4) 2.1机器的功能和设计要求 (4) 2.2工作原理和工艺动作分解 (4) 2.3根据工艺动作顺序和协调要求拟定运动循环图 4 2.4 机构选型 5 2.5机械运动方案的选择和判定 5 3系统方案拟定与比较 (4) 3.1方案一 (5) 3.2方案二 (8) 3.3方案三 (13) 3.4方案比较 (16) 3.5方案选择 17 4心得 17

1 课程设计任务 1.1设计题目 工件间歇输送机构 1.2设计要求 输送机主要由动力机构、间歇机构、传动机构组成。如图一所示,电动机输入动力,带动传动机构,通过间歇机构实现工件的间歇输送。 图1 间歇输送机构工作示意图

2机械系统运动功能系统图 2.1机器的功能和设计要求 由于机器加工的与产品的流水线效率的需要,间歇式传动显得必不可少!本设计旨在针对需间歇式传动的机构而设计的步长为840mm的各种方案,为其他机械提供基础。 设计要求:步长为840mm的间歇式传动 2.2工作原理和工艺动作分解 若需完成840mm间歇式传动,必须要经过的三个步骤 1. 四级电动机n=1500r|min的输出机构 2. 将高转速的电机速度通过合理的减速机构,使之达到需求的转速 3. 低转速的输出机构,并使物体能够840mm间歇式移动 2.3根据工艺动作顺序和协调要求拟定运动循环图

故障解列装置

第一节 故障解列装置 在多电源网络中,根据网络电源和负荷分布,还可以在适当的地方装设故障解列装置。在网络有故障时电网解列成几个独立电网继续运行,保证重要负荷的安全运行。 在宜宾电网主网和地方小电源的联络线上就装设了故障解列装置。例如吊黄楼变电站解列吊纸线517,对端纸厂有小电源,正常运行时与主网联结,增加供电可靠性。如图5.8 当吊黄楼母线故障,或出线故障而未能即使切除故障线路时,母线电压降低,或者零序电压升高,满足装置的动作判据时,解列装置动作跳开吊纸线517,纸厂电源E 2与纸厂负荷F 2,主网电源E 1与主网负荷F 1各自构成电网独立运行。 刚解列的电网也要考虑各自的稳定性。对于主网,是否会因此丢掉大负荷,丢失大负荷后是否会出现电网振荡,对于小电网,是否会突然增加大负荷,增加大负荷是否会出现低周现象,出现低周是否会有合适的减载装置等。 可见,故障解列与低周减载的概念是完全不同的,在电网中的作用也不同。 另外在宜宾电网中还有一个故障解列起的作用与前面讲的不同,那就是用户昌宏化工厂内部安装的故障解列装置。如图5.9 当巡昌线发生故障,巡场175开关跳闸并重合,但是由于昌宏化工的负荷几乎是大的炉变,几台变压器的负荷以及变压器的励磁涌流之和会远远大于175开关的后加速定值,所以 175开关无法合上,这样,就只有在昌宏变电站安装解列装置,解列掉几台炉变(例如1#、2#开关),让剩下的负荷(3#、4#开关)不至于把175开关冲跳。等175开关运行稳定后再逐步投入解列掉的几台炉变。 (说明,一般方式下,巡昌线的负荷不经过巡场175,而是龙头站龙巡西线直接经巡场旁母上巡昌线,只是为了这里解释方便采用是巡场供电方式。) 第二节 备用电源自投装置 备自投装置用于多电源点的变电站,当主供电源断开时自动将备用电源投入,保证供电 图5.8 吊黄楼 主网负荷F 1 E 2 F 2 1#炉变 2#炉变 3#炉变 4#炉变 昌宏

机械原理课程设计说明书——椭圆漫步机

机械原理 课程设计说明书 设计题目椭圆漫步机 机械工程学院机械设计及其自动化专业 设计者 指导教师 2009年12月28日

目录 一、设计题目 ···································································- 3 - 1.椭圆漫步机背景 (3) 2.设计要求 (3) 二、机构选型及评价 ........................................................- 4 - 方案1 .. (4) 方案2 (5) 方案3 (6) 方案4 (7) 三、机构设计 ···································································- 7 - 四、运动分析及仿真 ······················································- 10 - 1.踏点轨迹与标准椭圆比较图 (10) 2.踏点位置与标准椭圆比较表 (11) 3.位移、速度、加速度分析 (14) 4.运动仿真 (17) 五、结果分析 ·································································- 18 - 六、个人体会 ·································································- 19 - 七、参考资料 ·································································- 20 - 八、分工·········································································- 21 -

机械手机械原理课程设计说明书

(2)水平面内转30度,手臂自转90度,前进50mm。

机械手的夹持器还有夹紧和放松动作; 机械手工作频率:20/min; 升降 0.3kw,摆动 0.1kw,伸缩 0.1kw,夹持 0.2kw。2执行机构的选择与比较 §2-1 转角机构(实现平面转角0 30功能) 方案一 实现平面转角0 30的过程:电机带动不完全 齿轮运动,不完全齿轮带动全齿轮运动,与全 齿轮固结的四杆机构,使滚子在预先设计好形 状的槽内运动,左右运动的极限位置恰好是30 度。 机构评价: 优点:因为槽的形状固定,所以能保证在一个 行程内,机构的平面转角就是30度。 不完全齿轮的使用,为机械手在抓放物 体时留下了工作时间。 缺点:由于四杆机构的运动被槽限制住,最短杆 无法做周转运动,导致机构的回程要求齿 轮的翻转,必须在前面加入变速箱改变速 度方向。 方案二 实现平面转角0 30的过程:皮带轮传动给蜗 轮蜗杆从而使不完全齿轮,有间歇地带动完全齿 轮转动,齿轮通过杆拉动齿条,由齿轮来回往复 地带动固接杆转动0 30 机构评价: 优点:同样具有结构简单,传力较小运 动灵活,造价低准确地实现转角0 30的 要求,可以控制间歇实现循环功能。 缺点:磨损较严重,效率较低,齿轮尺 寸过大加工难。 方案三 30的过程:使用槽 实现平面转角0 轮实现平面转角30度,只要计算好槽轮 的槽数,就能在主动圆盘转360度时, 使从动轮转30度。机构评价: 优点:结构简单,外形尺寸小,机械效

率高,并能平稳的间歇地进行转位。 缺点:传动存在柔性冲击,且是单向的间歇运动,同样要求变速箱改变运动方向。 方案的选择与比较: 只有第二个方案能较好的实现对传动系统的功能要求在平面转动上能准确地控制在30度,制造简单方便。 §2-2 上升机构(实现上升100功能要求) 方案一 实现上升的过程:皮带轮传动,使蜗杆带动蜗轮,蜗轮和齿条配合。通过控 制蜗杆的半径,使转动一周后,使齿条上升100. 机构评价: 优点:蜗杆的轮齿是连续的螺旋尺,故传动平 稳,啮合冲击小。 缺点:啮合齿轮间的相对滑动速度较大,摩擦 磨损较大,传动效率较低,易出现发热 现象,常用耐磨材料制作,成本高。 方案二 实现上升的过程:皮带轮传动给蜗轮蜗杆 从而使凸轮转动,凸轮通过顶杆推动滑块滑 动,从而使工作杆上升100mm。 机构评价: 优点:结构简单,传力较小,凸轮不用太大就 可以达到所需要的高度。 缺点:效率过低,滑块容易磨损且一旦磨断严重影响上升高度,寿命不高。

智能变电站失步解列装置通用技术规范(范本)

智能变电站失步解列装置通用技术规范(范本)

本规范对应的专用技术规范目录 序号名称编号 1 智能变电站失步解列装置专用技术规范2803002-0000-b1

智能变电站失步解列装置采购标准 技术规范(范本)使用说明 1、本标准技术规范(范本)分为通用部分、专用部分。 2、项目单位根据需求选择所需设备的技术规范(范本),通用技术规范(范本)部分条款及专用技术规范(范本)部分固化的参数原则上不能更改。 3、项目单位应按实际要求填写“项目需求部分”。如确实需要改动以下部分,项目单位应填写专用部分“项目单位技术差异表”并加盖该网、省公司物资部(招投标管理中心)公章,与辅助说明文件随招标计划一起提交至招标文件审查会: ①改动通用部分条款及专用部分固化的参数; ②项目单位要求值超出标准技术参数值; ③需要修正污秽、温度、海拔等条件。 经标书审查会同意后,对专用部分的修改形成“项目单位技术差异表”,放入专用部分中,随招标文件同时发出并视为有效,否则将视为无差异。 4、对扩建工程,项目单位应在专用部分提出与原工程相适应的一次、二次及土建的接口要求。 5、技术规范(范本)的页面、标题、标准参数值等均为统一格式,不得随意更改。 6、投标人逐项响应专用技术规范(范本)部分中“1 标准技术参数表”、“2 项目需求部分”和“3 投标人响应部分”三部分相应内容。填写投标人响应部分,应严格按招标文件专用技术规范(范本)部分的“招标人要求值”一栏填写相应的招标文件投标人响应部分的表格。投标人填写技术参数和性能要求响应表时,如有偏差除填写“技术偏差表”外,必要时应提供相应试验报告。 7、一次设备的型式、电气主接线和一次系统情况对二次设备的配置和功能要求影响较大,应在专用部分中详细说明。

机械原理游戏机 ()

机械原理课程设计题目:____游戏机_______ 姓名:____朱建杰_______ 班级:12级机械设计制造及其自动化(1)班 学号: 指导教师:_刘凌__ 2014年6月26日 任务书 题目:游戏机同组成员:赵磊、王鹏指导教师:刘凌 某游乐场欲添设一新的游乐项目,该项目是在一暗室中,让一画有景物的屏幕(观众可以看见屏幕上的景物),由静止逐渐开始左右晃动,由于观众在暗室中仅能看见屏幕上的景物,根据相对运动原理,观众将产生一个错觉,他不认为是屏幕在晃动,反而认为是自己在晃动,这是一个有惊无险的游乐项目。 现要求设计一机械传动装置,使屏幕能实现上述运动规律。要求:屏幕摆动角度为70度;主动件的摆动角度为60度;屏幕的摆动速度为0.5rad/s,屏幕的重量为20N。 设定任务:1.设计传动系统中各机构的运动尺寸,绘制游戏机的机构运动见 图; 2.计算主动件的运动速度及驱动力; 3.编写课程设计说明书。 成绩评定表

目录 第1章设计要求及数据..................................... 1.1设计题目 .............................................. 2.2设计目的 .............................................. 1.3原始数据和设计要求 .................................... 第2章设计方案的选取.....................................

第3章设计步骤........................................... 3.1工作原理 .............................................. 3.2机构设计说明 .......................................... 3.2.1蜗轮蜗杆机构 (8) (9) 第4章心得体会........................................... 第5章参考文献........................................... 第1章设计要求及数据 1.1设计题目 游戏机 某游乐场欲添设一新的游乐项目,该项目是在一暗室中,让一画有景物的屏幕(观众可以看见屏幕上的景物),由静止逐渐开始左右晃动,由于观众在暗室中仅能看见屏幕上的景物,根据相对运动原理,观众将产生一个错觉,他不认为是屏幕在晃动,反而认为是自己在晃动,这是一个有惊无险的游乐项目。 现要求设计一机械传动装置,使屏幕能实现上述运动规律。要求:屏幕摆动角度为70度;主动件的摆动角度为60度;屏幕的摆动速度为0.5rad/s,屏幕的重量为20N。 设定任务:1.设计传动系统中各机构的运动尺寸,绘制游戏机的机构运动见 图; 2.计算主动件的运动速度及驱动力; 2.2设计目的 机械原理课程设计是培养学生掌握机械系统运动方案设计能力的技术基础课程,它是机械原理课程学习过程中的一个重要实践环节。其目的是以机械原理课程的学习为基础,进一步巩固和加深所学的基本理论、基本概念和基本知识,培养学生分析和解决与本课程有关的具体机械所涉及的实际问题的能力,使学生熟悉机械系统设计的步骤及方法,其中包括选型、运动方案的确定、运动学和动力学的分析和整体设计等,并进一步提高计算、分析,计算机辅助设计、绘图以及查阅和使用文献的综合能力。 此课程要求我们熟练掌握和运用机械原理知识,设计一个游戏机,通过电机带动,实现屏幕的左右晃动,主动件的摆角为60度,屏幕摆角70度。 1.3原始数据和设计要求

机械原理课程设计说明书

机械原理课程设计说明书设计题目:压床机构设计 自动化院(系)机械制造专业 班级机制0901 学号20092811022 设计者罗昭硕 指导老师赵燕 完成日期2011 年1 月4日

一、压床机构设计要求 1 .压床机构简介及设计数据 1.1压床机构简介 图9—6所示为压床机构简图。其中,六杆机构ABCDEF为其主体机构,电动机经联轴器带动减速器的三对齿轮z1-z2、z3-z4、z5-z6将转速降低,然后带动曲柄1转动,六杆机构使滑块5克服阻力Fr而运动。为了减小主轴的速度波动,在曲轴A上装有飞轮,在曲柄轴的另一端装有供润滑连杆机构各运动副用的油泵凸轮。 1.2设计数据

1.1机构的设计及运动分折 已知:中心距x1、x2、y, 构件3的上下极限角,滑块的冲程H,比值CE /CD、EF/DE,各构件质心S的位置,曲柄转速n1。 要求:设计连杆机构, 作机构运动简图、机构1~2个位置的速度多边形和加速度多边形、滑块的运动线图。以上内容与后面的动态静力分析一起画在l号图纸上。 1.2机构的动态静力分析 已知:各构件的重量G及其对质心轴的转动惯量Js(曲柄1和连杆4的重力和转动惯量(略去不计),阻力线图(图9—7)以及连杆机构设计和运动分析中所得的结果。 要求:确定机构一个位置的各运动副中的反作用力及加于曲柄上的平衡力矩。作图部分亦画在运动分析的图样上。 1.3飞轮设计 已知:机器运转的速度不均匀系数δ.由两态静力分析中所得的平衡力矩Mb;驱动力矩Ma为常数,飞轮安装在曲柄轴A上。 要求:确定飞轮转动惯量J。以上内容作在2号图纸上。 1.4凸轮机构构设计 已知:从动件冲 程H,许用压力角 [α ].推程角δ。,远 休止角δ?,回程角δ', 从动件的运动规律见 表9-5,凸轮与曲柄共 轴。 要求:按[α]确定 凸轮机构的基本尺 寸.求出理论廓 线外凸曲线的最小曲 率半径ρ。选取滚子 半径r,绘制凸轮实际 廓线。以上内容作在 2号图纸上 压床机构设计 二、连杆机构的设计及运动分析

RCS-993E型失步解列及频率电压紧急控制装置调试大纲

报告编号: 武安发电公司2×300MW机组工程 失步解列装置静态 调试大纲 电控维护班 2011-12-27编制人:韩辉

工程名称:大唐武安发电有限公司2×300MW机组工程报告名称:失步解列装置静态调试报告 报告编号: 编制:大唐武安发电有限公司生产准备部电控维护报告编写: 审核: 批准:

目录 ~~~~~~~~~~~~~~~

1 概述 武安发电有限公司2×300MW机组工程失步解列装置采用国网电力科学研究院稳定技术研究所南京南瑞集团公司稳定技术分公司生产的RCS-993E型失步解列及频率电压紧急控制装置,两条线路共配置两套装置,一条线路对应一套装置。该装置主要用于失步震荡解列,同时可完成低频、低压自动解列、切负荷功能。 2 调试目的 本次单体调试是对失步解列装置进行定值整定试验、逻辑功能试验以及整组传动等试验,保证装置可靠动作,确保系统安全运行。 3编制标准和依据 3.1《继电保护和电网安全自动装置检验规程》DL/T 995-2006 3.2《继电保护和安全自动装置技术规程》GB/T 14285-2006 3.3《河北南部电网继电保护运行管理规程》冀电调(2007)27文 3.4 《RCS-993E型失步解列及频率电压紧急控制装置技术及使用说明书》 4调试使用仪器 4.1天进MC2000系列继电保护测试仪 4.2 Kyoritsu 3007A型绝缘摇表(500V) 5 实验前注意事项 5.1试验前应检查屏柜及装置在运输过程中是否有明显的损伤或螺丝松动。 5.2一般不要插拨装置插件,不触摸插件电路,需插拨时,必须关闭电源,释放手上静 电或佩带静电防护带 5.3使用的试验仪器必须与屏柜可靠接地。 *以下除传动试验,均应断开保护屏上的出口压板。 5.4 RCS993E 频率电压紧急控制功能判断的对象是同一系统的两段母线电压或线路电压,所以试验时如果两组电压输入都加了量时,必须两组电压输入的正序电压或频率同

电网第三道防线问题分析及失步解列

电网第三道防线问题分析及失步解列 摘要:三道防线是电力系统安全防御体系的重要组成部分,第一道是继电保护系统,第二道是包括稳控装置及切机、切负荷等措施在内的电力系统安全稳定控制系统,第三道由失步解列、频率及电压紧急控制装置构成。鉴于目前第三道防线尚存漏洞或不足,分析了振荡中心转移至主网内部、故障点切除不掉引起远后备保护无选择动作、重要联络线的相继开断造成的潮流大转移引起受端系统电压不稳定、距离保护三段在线路严重过载时误动作引起的连锁反应及大机组保护装置参数与电网不协调引发的事故等五种情况。针对这些情况提出了若干解决的对策,特别是研究和提出了构建互联电网的综合解列控制系统的方案,解决了振荡中心转移到主网内部时能及时采取解列等优化措施,解决了电压不稳定事故发生前隔离故障区域或将难以控制的电压崩溃事故转化为 容易解决的频率稳定问题等,这些对策可显著增强电网的第三道防线。 关键词:电力系统安全;三道防线;失步振荡;综合解列系统 Analysis on the Problems about the Third Defense Line of Power Systems and the Concept of Dealing with the Separation Relay after Loss of Synchronism Abstract:“Three Defence Lines”is a concept of the whole security defence system for power systems being used for a long time but clearly defined in this paper as follows: the first is the protection relay system; the second line the stability and security control including generator rejection and load shielding and the third line the separation relay after loss of synchronism followed by the frequency and the voltage emergency control. The paper argues that there exist indentation and deficiency in the third line and analyzes in detail the following five scenarios.

机械原理课程设计说明书完整版

机械原理课程设计说明 书 HEN system office room 【HEN16H-HENS2AHENS8Q8-HENH1688】

机械原理课程设计说明书 题目:压床机械方案分析 班级:机械1414班 姓名:刘宁 指导教师:李翠玲 成绩: 2016 年 11 月 8 日 目录 目录 一.题目:压床机械设计 二.原理及要求 (1).工作原理 压床机械是由六杆机构中的冲头(滑块)向下运动来冲压机械零件的。图1为其参考示意图,其执行机构主要由连杆机构和凸轮机构组成,电动机经过减速传动装置(齿轮传动)带动六杆机构的曲柄转动,曲柄通过连杆、摇杆带动滑块克服阻力F冲

压零件。当冲头向下运动时,为工作行程,冲头在内无阻力;当在工作行程后行程时,冲头受到的阻力为F;当冲头向上运动时,为空回行程,无阻力。在曲柄轴的另一端,装有供润滑连杆机构各运动副的油泵凸轮机构。 (a)机械系统示意图(b)冲头阻力曲线图 (c)执行机构运动简图 图1 压床机械参考示意图 (2).设计要求 电动机轴与曲柄轴垂直,使用寿命10年,每日一班制工作,载荷有中等冲击,允许曲柄转速偏差为±5%。要求凸轮机构的最大压力角应在许用值[α]之内,从动件运动规律见设计数据,执行构件的传动效率按计算,按小批量生产规模设计。 (3).设计数据

推程运动角 δ60°70°65°60°70°75°65°60°72°74° 远休止角 s δ10°10°10°10°10°10°10°10°10°10° 回程运动角 δ'60°70°65°60°70°75°65°60°72°74°三.机构运动尺寸的确定 转速n2 (r/min)距离x1 (mm) 距离x2 (mm) 距离y (mm) 冲头行程H (mm) 上极限角 Φ1 (°) 下极限角 Φ2(°) 884013516014012060 ( 1.以O2为原点确定点O4的位置; 2.画出CO4的两个极限位置C1O4和C2O4; 3.取B1,B2使CB=CO4*1/3,并连接B1O2,B2O2; 4.以O2为圆点O2A为半径画圆,与O2B1交于点A1; 5.延长B2O2交圆于A2; 6.取CD=*CO4。 C1 B1 D1 O4 B2 C2 A1 D2 O2 A2 (2)计算: 由题可知CO4=H=140,CB=CO4*1/3=47,O4B=93,CD=*CO4=42; Δx(O2B1)= Δx(O2B2)=OB*cos(30o)-x1=; Δy(O2B1)=y+O4B*sin(30o) =; Δy(O2B2)=y-O4B*sin(30o) =; O2B1=√[Δx(O2B1) 2+Δy(O2B1) 2]≈210; O2B2=√[Δx(O2B1) 2+Δy(O2B2) 2]≈120; AB+O2A=O2B1,AB-O2A=O2B2; 可以解得O2A=45,AB=165. 符号 单位mm 方案414093474216545

故障解列装置原理与仿真

故障解列装置原理与仿真 发表时间:2016-12-16T15:00:36.053Z 来源:《电力设备》2016年第19期作者:陈静韩静 [导读] 分析了故障解列装置的原理,在PSCAD下搭建了仿真模型,通过仿真,验证了有效性。 (国网河南卫辉市供电公司河南卫辉 453100) 摘要:分析了故障解列装置的原理,在PSCAD下搭建了仿真模型,通过仿真,验证了有效性。 关键词:故障解列;原理;PSCAD;仿真 The principle and simulation of fault disconnection device Chen Jing,han jing (Weihui Electric Power Bureau,Weihui Henan 453100,China) Abstract:The principle of the fault disconnection device,which simulation model is established in PSCAD,was proved to be effective. Key words:fault disconnection device;principle;PSCAD;simulation 0 引言 随着国民经济的快速发展,电网建设规模发展很快,越来越多的小水电、余热发电、热电项目上马,机组容量相对也越来越大,接入35kV、10kV公用线路上或直接接入终端变电站的35kV、10kV母线上。在大电源系统侧主送电源线路发生瞬时性故障情况下,由于接入终端变电站中、低压侧的小电源作用于变电站高压母线,使得系统侧检无压重合闸条件无法满足,不能可靠重合,因此必须采取措施加以避免[1]。 1 故障解列装置简介 某110kV 变电站系统接线如图1所示,1DL开关安装有线路保护,110kV 线路压变安装于线路A相,作为终端变电站的进线开关2DL未安装有线路保护,#1 主变中性点不接地运行,#1 主变中性点无零序过流保护及零序间隙过流保护。 1.1 装设必要性 (1)当110kV线路发生瞬时性单相接地故障时,灵敏段保护动作跳开1DL开关,系统与小电源解列运行,中性点电压发生偏移。目前系统中采用的多为分级绝缘的变压器,中性点绝缘水平较低,当中性点电压升高后往往容易将变压器中性点绝缘损坏,因此系统发生接地故障后必须尽快切除小电源。 图1 某110kV变电站系统接线图 (2)当110kV线路B(或C)相发生瞬时性单相接地故障,1DL开关跳开后,110kV变电站中性点电压发生偏移,A、C(或A、B)相电压升高,使220kV变电站的110kV线路的A相线路电压抬高,若此电压高于1DL开关重合闸的检无压定值时,将使1DL开关的检无压重合失败。当110kV线路发生BC相故障,1DL开关跳开后,小电源将在某110kV变电站的110kV母线A相上产生一个比较高的残压,接近于健全电压,往往会高于1DL开关重合闸的检无压定值,将使1DL开关的检无压重合失败。 为了防止上述情况的发生,非常有必要在110kV变电站的110kV母线上装设故障解列装置,当110kV线路发生瞬时性相间或单相接地故障时,故障解列装置动作跳开小电源4DL开关并闭锁重合闸,使220kV变电站1DL开关检无压重合能可靠动作。 1.2 故障解列装置原理分析 故障解列装置接入110kV变电站的高压母线电压UA、UB、UC、3U0、UN,系统发生单相接地故障时,母线上产生较高的零序电压;发生相间故障时,故障相母线电压会降低。为了满足各种故障类型情况下都能可靠动作切除小电源,故障解列装置应具有低电压动作、零序过电压动作功能,要求线电压低于低压整定值,或者外加零序电压3U0高于零序过压整定值并且自产零序电压高于8V时,开放解列功能。 2 仿真验证 根据以上原理分析,在PSCAD下搭建了故障解列装置的详细模型,并对图1所示系统在不同故障下是否装设故障解列装置进行仿真对比分析,验证了其有效性。 2.1 单相接地故障 (1)A相接地 0.505s时刻发生A相接地故障,故障持续时间为0.1s,保护于0.515s时刻跳开电源侧开关1DL。通过图2、图3对比可见,由于A相发生接地故障,电压降低,因此无论是否装设故障解列装置,1DL开关的重合闸检无压均能成功,经延时后,1DL重合闸,恢复正常供电。

浅析失步解列装置及应用

浅析失步解列装置及应用 发表时间:2018-12-12T15:57:51.107Z 来源:《基层建设》2018年第29期作者:王信 [导读] 摘要:大电网的稳定运行是电力系统的基本要求,大电网中最严重的事故事稳定性破坏即系统发生失步振荡,如处理不当会发生大面积停电。 中国水利水电第十二工程局机电安装分局浙江 323000 摘要:大电网的稳定运行是电力系统的基本要求,大电网中最严重的事故事稳定性破坏即系统发生失步振荡,如处理不当会发生大面积停电。当系统失步后,首先要解决的问题是从失步断面断开失步机群间的电气联系,消除系统振荡,然后通过切机、减载等措施实现解列后电气孤岛的稳定运行,最后当条件允许时,再逐步恢复整个系统的互联同步稳定运行。 关键词:系统振荡、失步解列、两机等值系统 一、概念阐述 在电网中,保证电力系统稳定的第三道防线由失步解列、频率及电压紧急控制装置构成,当电力系统发生失步振荡、频率异常、电压异常等事故时采取解列、切负荷、切机等控制措施,防止系统崩溃。 实际测量中,我们通常将振荡中心两侧母线电压相量之间的相角差从正常运行角度逐步增加并超过180°的现象定义为该系统已失去同步。 失步解列是电力系统稳定破坏后防止事故扩大的基本措施,在电网结构的规划中应遵循合理的分层分区原则,在电网的运行时应分析本电网各种可能的失步振荡模式,制定失步振荡解列方案,配置自动解列装置,即在预先选定的输电断面,以断开输电线路或解列发电厂或变电所母线来实现。按系统解列的不同目标,一般采用不同的起动方式。在选择系统解列断面时,应使解列后各部分系统分别保持同步和功率尽量保持平衡,并应考虑以最少的解列点和最少的断路器来实现。 二、基本原理和类型 电力系统失步时,一般可以将所有机组分为两个机群,用两机等值系统分析分析其特性。如图1所示两机等值系统电势向量图。Zm、Zn分别为装置安装处到两侧系统的等效阻抗。 图1 目前常用的有三种失步判据,以下分别介绍其原理: 1.视在阻抗轨迹判据(以南瑞继保RCS-993A失步解列装置为例): 原理为当系统发生失步振荡时,装置安装处测量的阻抗值会随着功角的变化而变化,因此通过测量阻抗轨迹来判断失步。视在阻抗轨迹在阻抗平面上表现为6个区域,如图2所示,电力系统振荡时,测量阻抗轨迹沿曲线1、2顺次移动,加速失步时依曲线1的方向移动,减速失步时依曲线2的方向移动。 图2 2.视在阻抗角判据(以南京南电SSD-540U失步解列装置为例): 相位角通过公式算出,系统振荡时,根据相位角的变化规律,将四个象限内的相位角划分为六个区(如图3): 1~ 2、 2~90°、90°~ 3、 3~ 4、 4~270°、270°~ 1。系统正常情况下一般运行在Ⅰ区或Ⅳ区,把Ⅰ-Ⅱ-Ⅲ-Ⅳ作为正方向判别区,把Ⅳ-Ⅴ-Ⅵ-Ⅰ作为反方向判别区,把Ⅰ-Ⅳ作为振荡中心判别区。

并网小电源对系统保护的影响

并网小电源对系统保护的影响 摘要:本文重点分析了35KV 侧并网小电源对系统不接地变压器保护、110KV 故障解列保护的影响及要求,以及在接有小电源的35KV 侧母线的出线发生相间故障时,并网小电源对故障点处的电流以及该侧母线电压的影响。由此提出了不接地变压器的间隙零流、间隙零压保护和110KV 故障解列保护整定配合的改进措施,理清了接有并网小电源系统的35KV 母线的出线保护定值计算和故障分析的思路。 关键词:主供电源;并网小电源;故障解列; 间隙零流;间隙零压。 1 引言 随着社会经济的发展,许多大型厂矿企业拥有自备电源,这些电源发电除自用外,有时通过35KV 馈线向电网倒送电能。随着这类电源容量和数量的增加,在实际运行中对保护的影响也不容忽视。因此,本文重点分析了35KV 侧并网小电源对不接地变压器保护,110KV 故障解列保护的影响及要求,以及在接有小电源的35KV 侧母线的出线发生相间故障时,对故障点处的电流以及35KV 侧母线电压的影响。由此提出了不接地变压器的间隙零流,间隙零压保护整定计算应注意的问题,并研究发现了110KV 故障解列保护装置本身的一些缺陷。提出了变压器保护,故障解列保护整定配合的改进措施。 2 并网小电源对系统保护的影响及保护的改进措施 2.1并网小电源对变压器保护的影响 系统为110KV 变电站,站内有两台不接地变压器,通过35KV 负荷侧联络线连接一并网小电源F1。当主网主供电源线路发生瞬时故障跳闸时,若系统110KV 侧接地故障点还存在时,变电站成为带接地故障点的中性点不接地系统,系统110KV 侧会出现很大的零序过电压,变压器 小电源 接有并网小电源的典型主接线图

机械原理课程设计—颚式破碎机设计说明书

目录 一设计题目 (1) 二已知条件及设计要求 (1) 2.1已知条件 (1) 2.2设计要求 (2) 三. 机构的结构分析 (2) 3.1六杆铰链式破碎机 (2) 3.2四杆铰链式破碎机 (2) 四. 机构的运动分析 (2) 4.1六杆铰链式颚式破碎机的运动分析 (2) 4.2四杆铰链式颚式破碎机的运动分析 (6) 五.机构的动态静力分析 (7) 5.1六杆铰链式颚式破碎机的静力分析 (7) 5.2四杆铰链式颚式破碎机的静力分析 (12) 六. 工艺阻力函数及飞轮的转动惯量函数 (17) 6.1工艺阻力函数程序 (17) 6.2飞轮的转动惯量函数程序 (17) 七 .对两种机构的综合评价 (21) 八 . 主要的收获和建议 (22) 九 . 参考文献 (22)

一.设计题目:铰链式颚式破碎机方案分析 二.已知条件及设计要求 2.1已知条件 图1.1 六杆铰链式破碎机图1.2 工艺阻力 图1.3四杆铰链式破碎机 图(a)所示为六杆铰链式破碎机方案简图。主轴1的转速为n1 = 170r/min,各部尺寸为:lO1A = 0.1m, lAB = 1.250m, lO3B = 1m, lBC = 1.15m, lO5C = 1.96m, l1=1m, l2=0.94m, h1=0.85m, h2=1m。各构件质量和转动惯量分别为:m2 = 500kg, Js2 = 25.5kg?m2, m3 = 200kg, Js3 = 9kg?m2, m4 = 200kg, Js4 = 9kg?m2, m5=900kg, Js5=50kg?m2, 构件1的质心位于O1上,其他构件的质心均在各杆的中心处。D为矿石破碎阻力作用点,设LO5D = 0.6m,破碎阻力Q在颚板5的右极限位置到左极限位置间变化,如图(b)所示,Q力垂直于颚板。 图(c)是四杆铰链式颚式破碎机方案简图。主轴1 的转速n1=170r/min。lO1A = 0.04m, lAB = 1.11m, l1=0.95m, h1=2m, lO3B=1.96m,破碎阻力Q的变化规律与六杆铰链式破碎机相同,Q力垂直于颚板O3B,Q力作用点为D,且lO3D = 0.6m。各杆的质量、转动惯量为m2 = 200kg, Js2=9kg?m2,m3 = 900kg, Js3=50kg ?m2。曲柄1的质心在O1 点处,2、3构件的质心在各构件的中心。

失步解列及安全稳控装置试验报告-上传

失步解列紧急控制装置试验报告 工程名称:XX光伏电站装置地点:二次盘室 试验日期: 2012年5月15日温度: 20 ℃相对湿度:25% RH 设备编号:失步解列柜执行标准:DL-T 995-2006 继电保护 一、试验用标准仪器数据: 名称:继电保护测试装置型号:RT-3A 编号:111 生产厂家:扬州 二、保护装置数据: 装置型号RCS-993E失步解列及频率电压紧急 控制装置生产厂家南京南瑞继保电气有限 公司 三、电流 .电压采样校验: 名称输入频率/电压测量频率(Hz)/电压(V) 备注A相B相C相 50.00Hz 50.005 50.007 50.005 57.7V 57.73 57.72 57.73 四、试验数据: 定值名称整定值动作值 备注频率\电压时间(S)频率\电压时间(S) 低频启动49.50Hz 0 49.49HZ 0.04 启动 低频解列49.00Hz0.2 48.98HZ0.24 跳闸过频启动50.50Hz0 50.51HZ0.04 启动过频第一轮51.00Hz 0.2 51.05HZ0.24 跳闸过频第二轮51.50Hz 0.2 51.54HZ0.24 跳闸过频第三轮52.00Hz 0.2 52.05HZ0.24 跳闸低压启动90.0V 0 89.8V 0.04 启动低压解列85.0V 0.2 84.8V 0.24 跳闸过压启动115.0V 0 115.5V 0.04 启动过压解列120.0V 0.2 120.6V 0.24 跳闸五、结论 合格 试验:复核:

稳定控制装置试验报告 工程名称:XX光伏电站装置地点:二次盘室 试验日期: 2012年5月18日温度: 25 ℃相对湿度:25% RH 设备编号:稳定控制柜执行标准:DL-T 995-2006 继电保护 一、试验用标准仪器数据: 名称:继电保护测试装置型号:RT-3A 编号:111 生产厂家:扬州 二、保护装置数据: 装置型号RCS-992A型分布式稳控装置生产厂家南京南瑞继保电气有限 公司 三、电流 .电压采样校验: 名称输入电流/电压测量电流(A)/电压(V) 备注A相B相C相 10.00 10 10 10 57.7V 57.75 57.74 57.74 四、传动试验: 出口名称动作情况结论1#进线跳闸正确2#进线跳闸正确3#进线跳闸正确4#进线跳闸正确备用进线跳闸正确出线跳闸正确 五、结论 合格 试验:复核: